Additional Information
curve
C
Main
Range
Multi 9
sectioning ability
Yes conforming to EN/IEC 60947-2
name of the device
C60SP
type of product or equipment
miniature circuit breaker
Product Name
Multi 9 C60
[ui] rated insulation voltage
500 V AC conforming to EN/IEC 60947-2
number of poles protected
2
type of trigger
Thermal-magnetic
Complementary
9 mm pitches
4
[ue] rated operational voltage
240V AC 50
/60Hz 415V AC 50/60Hz
440V AC 50/60Hz
application
Distribution
[ics] rated service breaking capacity
4.5 kA 75% conform to EN/CEI 60947-2 - 440 V AC
7.5 kA 75% conform to EN/CEI 60947-2 - 415 V AC
15 kA 75% conform to EN/CEI 60947- 2 - 240 V AC
4.5 kA 75 % conform to GB 14048.2 - 440 V AC
7.5 kA 75 % conform to GB 14048.2 - 415 V AC
15 kA 75 % conform to GB 14048.2 - 240 V AC
Handle front plate colour
81 mm
tightening torque
3.5 Nm top or bottom
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
in rated operational current
50 A at 25 °C conforming to EN/IEC 60947-2
fully apparent cut
Yes
mode d'installation
snap-on
electrical life
10000 cycle
connection mode
Tunnel type terminal (top or bottom)1…35 mm² (AWG 18...AWG 2) - rigid
Tunnel type terminal (top or bottom)1…25 mm² (AWG 18...AWG 3) - flexible with cable end
Tunnel type terminal (top or bottom)1...25 mm² (AWG 18...AWG 3) - flexible
mechanical endurance
20000 cycle
width (w)
36 mm
Colour
Grey
voltage indication
Indication ON/OFF
wire stripping length
14mm for top or bottom connection
depth
72 mm
mounting bracket
DIN rail
magnetic trip limit
8,5 x In +/- 20 % CA
Network type
THAT
differential protection
Without
lockdown forecast
Cadenassable
order type
Just a little bit
Poles description
2P
Environment
degree of pollution
3 conforming to EN/IEC 60947-2
ip degree of protection
IP20 conforming to CEI 60529
IP40 (modular housing) conforming to CEI 60529
operating altitude
0...2000 m
product certificates
THE
CCC
UR
CSA
standards
EN/CEI 60947-2
GB 14048.2
UL 1077
CSA C22.2 No 235
relative humidity
95% at 55°C
operating temperature
-30…70 °C
storage room temperature
-40…80 °C
tropicalization
2 conforming to IEC 60068-1