Main
Range
TeSys
[uc] control circuit voltage
24...575 V AC 40...400 Hz with LX9 coil
24...460 V DC with LX4 coil
100...250 V AC 50/60 Hz with LXE coil
100...380 V DC with LXE coil
job category
AC-4
AC-1
AC-3
name of the device
LC1F
switch application
Motor control (AC-3)
Resistive load (AC-1)
type of product or equipment
contactor
Product Name
TeSys F
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 gr C
composition of the power pole contacts
3F
motor power kW
110 kW at 380...400 V AC 50/60 Hz (AC-3)
110 kW at 415 V AC 50/60 Hz (AC-3)
110 kW at 440 V CA 50/60 Hz (AC-3)
129 kW at 500 V AC 50/60 Hz (AC-3)
63 kW at 220...240 V AC 50/60 Hz (AC-3)
129 kW at 660...690 V CA 50/60 Hz (AC- 3)
40 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0,32 mOhm - Ith 315 A 50 Hz
Complementary
[ie] rated operational current
315 A (at <40°C) at <= 440 V AC-1
225 A (at <55°C) at <= 440 V AC-3
[ue] rated operational voltage
<= 690 V CA 50/60 Hz
<= 460 V CC
compatibility code
LC1F
[ics] rated service breaking capacity
1800 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
1800 A at <40°C - 10 s
1000 A at <40°C - 30 s
850 A at <40°C - 1 min
560 A at <40°C - 3 min
440 A at <40°C - 10 min
[ith] conventional thermal current
315A at <40°C)
caliber of the fuse to be associated
315 A gG at <= 440 V
250 A aM at <= 440 V
Handle front plate colour
197 mm
tightening torque
Power circuit: 35 Nm
Remote control: 1.2 Nm
Remote control: 0.6 Nm
[uimp] rated impulse withstand voltage
8 kV
average fuel consumption when going
8.9…10.9 VA
4.13…5.07 VA
4.5…7.0 VA
2.5…4.0 VA
product weight
5,55 kg
average consumption on call going
950…1180 VA, 40...400 Hz cos phi 0.9 (at 20 °C) with LX9 coil
737…902 VA (at 20 °C) with LX4 coil
280…310 VA, 50/60 Hz cos phi 0 .5 (at 20 °C) with LXE coil
270…320 VA (at 20 °C) with LXE coil
connection mode
Power circuit: ring terminals 1 cable(s) 185 mm²
Power circuit: connector 1 cable(s) 185 mm²
Power circuit: bar 2 cable(s) - busbar section: 32 x 4 mm
Power circuit : connection by bolting
Remote control: screw clamp terminals 1 cable(s) 1...4 mm² flexible without cable end
Remote control: screw clamp terminals 2 cable(s) 1...4 mm² flexible with cable end
Remote control: screw terminal blocks clamp 1 cable(s) 1...4 mm²flexible with cable end
Remote control: screw clamp terminals 2 cable(s) 1...2.5 mm²rigid without cable end
Remote control: screw clamp terminals 1 cable(s) 1... 4 mm²
Remote control: screw clamp terminals 2 cable(s) 1...4 mm²
Remote control: screw clamp terminals 1.0 cable(s) 0.2...2.5 mm²flexible without cable end
Remote control: screw clamp terminals 1.0 cable(s) 0.25...2.5 mm²flexible with cable end cable
cross-section Remote control: screw clamp terminals 1.0 cable(s) 0.2...2.5 mm²rigid without cable end
control circuit voltage range
Operational: 0.85…1.1 Uc AC 40...400 Hz
Level loss: 0.2...0.55 Uc AC 40...400 Hz
Operational: 0.85…1.1 Uc DC
Loss level loss: 0.15...0.2 Uc DC
Operational: 85...275 V AC 50/60 Hz
Level loss: 0...60 V AC 50/60 Hz
Operational: 85...418 V DC
Loss level: 0...45 V DC
mechanical endurance
10 Mcycles
width (w)
168,5 mm
mechanical robustness
Contactor open vibrations: 2 Gn, 5 to 300 Hz
Contactor closed vibrations: 5 Gn, 5 to 300 Hz
Contactor open shocks: 7 Gn for 1/2 sine wave (11 ms)
Contactor closed shocks: 15 Gn for 1/2 sine wave( 11ms)
rated rms inrush power
2250 A conforming to IEC 60947-4-1
depth
181 mm
mounting bracket
Platinum
operating time
35 ms closing for with LX9 coil
130 ms opening for with LX9 coil
30…40 ms closing for with LX4 coil
30…50 ms opening for with LX4 coil
40…80 ms closing for with LXE coil
6...54 ms opening for with LXE coil
power loss per pole
32 W AC-1
16 W AC-3
max command speed
2400 cycles/h at <55°C
Poles description
3P
Environment
ip degree of protection
IP20 front face with protectors conforming to IEC 60529
IP20 front face with protectors conforming to VDE 0106
operating altitude
3000 m without current reduction
product certificates
UL
LROS (Lloyds register of shipping)
BV
CB
ABS
DNV
CSA
RMRoS
RINA
UKCA
ambient air temperature for operation
-40…70 °C
operating ambient temperature
-5…55 °C
overvoltage category
III
standards
JIS C8201-4-1
CEI 60947-4-1
CEI 60947-1
EN 60947-4-1
EN 60947-1
thermal dissipation
8…9,8 W
2,2…2,5 W
storage room temperature
-60…80 °C
protective treatment
TH