Main
Range
TeSys
[uc] control circuit voltage
48...1000 V AC 40...400 Hz with coil LX1/LX9
48...440 V DC with coil LX4
job category
AC-1
name of the device
LC1F
switch application
Resistive load (AC-1)
type of product or equipment
contactor
Product Name
TeSys F
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 gr C
composition of the power pole contacts
4F
average impedance
0,12 mOhm - Ith 1000 A 50 Hz
Complementary
[ie] rated operational current
1000 A (at <40°C) at <= 440 V AC AC-1
[ue] rated operational voltage
<= 1000 V CA 50/60 Hz
<= 460 V CC
compatibility code
LC1F
[ics] rated service breaking capacity
5040 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
5050 A at <40°C - 10 s
4400 A at <40°C - 30 s
3400 A at <40°C - 1 min
2200 A at <40°C - 3 min
1600 A at <40°C - 10 min
[ith] conventional thermal current
1000A at <40°C)
1250A
caliber of the fuse to be associated
630 A aM at <= 440 V
1000 A gG at <= 440 V
Handle front plate colour
304 mm
tightening torque
Power circuit: 58 Nm
Remote control: 1.2 Nm
[uimp] rated impulse withstand voltage
8 kV
average fuel consumption when going
20...25 VA
6.5...12.5 VA
product weight
21,5 kg
average consumption on call going
1500…1730 VA, 40...400 Hz cos phi 0.9 (at 20 °C) with LX1/LX9 coil
1420…1920 VA (at 20 °C) with LX4 coil
connection mode
Power circuit: bar 2 cable(s) - busbar section: 60 x 5 mm
Power circuit: connection by bolting
Remote control: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 2 cable(s) 1...4 mm²flexible with cable end
Remote control: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end
Remote control: screw clamp terminals 2 cable(s) 1...2.5 mm²rigid without cable end
Remote control: screw clamp terminals 1 cable(s) 1...4 mm²
Remote control: screw clamp terminals 2 cable(s) 1...4 mm²
control circuit voltage range
Operational: 0.85…1.1 Uc AC 40...400 Hz
Level drop: 0.25...0.5 Uc AC 40...400 Hz
Operational: 0.85…1.1 Uc DC
Level drop : 0.2 to 0.35 Uc DC
mechanical endurance
5 Mcycles
width (w)
389 mm
mechanical robustness
Open contactor vibrations: 2 Gn, 5 to 300 Hz
Closed contactor vibrations: 4 Gn, 5 to 300 Hz
Open contactor shocks: 6 Gn for 1/2 sine wave (11 ms)
Closed contactor shocks: 15 Gn for 1/2 sine wave( 11ms)
rated rms inrush power
6300 A AC conforming to IEC 60947-4-1
depth
255 mm
mounting bracket
Platinum
operating time
40…80 ms closing for with LX1/LX9 coil
100…200 ms opening for with LX1/LX9 coil
60…70 ms closing for with LX4 coil
40…50 ms opening for with LX4 coil
power loss per pole
120 W AC-1
max command speed
1200 cycles/h at <55°C
Poles description
4P
Environment
ip degree of protection
IP20 front face with protectors conforming to IEC 60529
IP20 front face with protectors conforming to VDE 0106
operating altitude
3000 m without current reduction
product certificates
ABS
UL
RINA
DNV
CSA
CB
LROS (Lloyds register of shipping)
BV
RMRoS
UKCA
ambient air temperature for operation
-40…70 °C
operating ambient temperature
-5…55 °C
overvoltage category
III
standards
EN 60947-4-1
CEI 60947-4-1
CEI 60947-1
JIS C8201-4-1
EN 60947-1
thermal dissipation
20W
storage room temperature
-60…80 °C
protective treatment
TH