Complementary
feed
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection
Internal supply: 24 V DC (21… 27 V), <200 A, protection type: overload and short circuit protection
[un] rated nominal voltage
380…480 V - 15...10%
specific application
HVAC
maximum switching current
5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 sc (FL, R)
response time
FM 2 ms, tolerance +/- 0.5 ms for analog output(s)
FLA, FLC 7 ms, tolerance +/- 0.5 ms for digital output(s)
FLB, FLC 7 ms, tolerance +/- 0, 5 ms for digital output(s)
RY, RC 7 ms, tolerance +/- 0.5 ms for digital output(s)
data formats
8 bits, 1 stop bit, odd, even or non-configurable parity bits
Handle front plate colour
297 mm
tightening torque
1.3 Nm, 11.5 lbs per inch (L1/R, L2/S, L3/T)
0.6 Nm (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES )
minimum switching current
3 mA at 24 V DC for configurable logic relay
product weight
7 kg
marking
THIS
output voltage
<= supply voltage
width (w)
215 mm
network frequency
47,5…63 Hz
power frequency
50...60 Hz - 5...5 %
supply voltage limits
323…528V
switching frequency
6...16 kHz adjustable
12...16 kHz with reduction factor
Local signalling
for DC bus powered 1 LED (red)
motor slip compensation
Automatic whatever the load
Not available for motor control in voltage/frequency ratio
Adjustable
physical interface
2-wire RS 485
functionality
AVERAGE
prospective line short-circuit current
5 kA
connector type
1 open style
1 RJ45
depth
192 mm
line current
1.4A at 480V
1.7A at 380V
continuous output current
2.2A at 380V
2.2A at 460V
isolation
Electrical between power and control
logic input
Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Negative logic (sink) (F, R, RES), >= 16 V (state 0 ), <= 10 V (state 1)
maximum transient current
2.4A for 60s
electrical connection
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: bornier 2,5 mm² / AWG 14
L1/R, L2/S, L3/T: bornier 6 mm² / AWG 10
sampling time
2 ms +/- 0.5 ms F digital
2 ms +/- 0.5 ms R digital
2 ms +/- 0.5 ms RES digital
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- - 0.5ms analog VIB
standstill braking
4 x 2,5 mm² + 2 x 1 mm² + 2 x 0,14 mm²
linearity error
VIA: +/- 0.15% of maximum value for input
VIB: +/- 0.15% of maximum value for input
FM: +/-0.2% for output
mounting position
Vertical +/- 10 degrees
nominal switching frequency
12 kHz
dielectric strength
3535 V DC between ground and power supply terminals
5092 V DC between control and power supply terminals
kind of protection
Overheating protection: drive
Thermal power stage: drive
Short-circuit between motor phases: drive
Input phase breaks: drive
Overcurrent between output phases and ground: drive
Overvoltage on the DC bus: drive
Break on the control circuit: drive
Against speed limit exceeded: drive
Power supply overvoltage or undervoltage: drive
Power supply undervoltage: drive
Against input phase loss: drive
Thermal protection: motor Motor
phase loss: motor
With PTC probes: engine
variable speed drive output frequency
0,5…200 Hz
number of analog inputs
2
construction options
With heat sink
number of analog outputs
1
speed range
1…10
number of logic outputs
2
precision
+/- 0.6% (VIA) for a temperature variation of 60°C
+/- 0.6% (VIB) for a temperature variation of 60°C
+/- 1% (FM) for a variation of temperature of 60°C
baud rate
9600 bps or 19200 bps
control profile for asynchronous motor
Voltage/frequency ratio, 2 points
Voltage/frequency ratio, auto IR compensation (U/f + auto Uo)
Voltage/frequency ratio - Energy saving, quadratic U/f Flux
vector control without sensor, standard
Voltage/frequency ratio, 5 points
torque accuracy
+/- 15%
apparent power
1.6kVA at 380V
number of addresses
1…247
acceleration and deceleration ramps
Separately linearly adjustable from 0.01 to 3200 s
Automatic depending on the load
transient overtorque
120% of nominal motor torque +/- 10% for 60 s
analog input type
VIA configurable voltage by microswitch: 0...10 V DC 24 V max, impedance: 30000 Ohm, 10-bit resolution
VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, 10-bit resolution
VIB probe Configurable PTC: 0 to 6 probes, impedance: 1500 Ohm
VIA configurable switching current: 0...20 mA, impedance: 250 Ohm, 10 bit resolution
logic input type
F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
analog output type
FM voltage configurable by microswitch 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits
FM switching current configurable 0...20 mA, impedance: 970 Ohm, resolution 10 bits
logic output type
Configurable relay logic: (FLA, FLC) "NO" - 100000 cycles
Configurable relay logic: (FLB, FLC) "O" - 100000 cycles
Configurable relay logic: (RY, RC) "NO" - 100000 cycles
frequency resolution
Display unit: 0.1 Hz
Analog input: 0.024/50 Hz
cable type
Without mounting kit: 1 wire(s)IEC cable at 45°C, copper 90°C / XLPE/EPR
Without mounting kit: 1 wire(s)IEC cable at 45°C, copper 70°C / PVC
With kit UL type 1: 3 wire(s)UL 508 cable at 40°C, copper 75°C / PVC
transmission frame
RTU
polarization type
No impedance
Environment
degree of pollution
2 conforming to IEC 61800-5-1
environment characteristic
Classes 3C1 conforming to IEC 60721-3-3
Classes 3S2 conforming to IEC 60721-3-3
ip degree of protection
IP55
operating altitude
1000…3000 m limited to 2000 m for grounded corner distribution network with current reduction of 1% every 100 m
<= 1000 m without derating
product certificates
CSA
UL
C-Tick
NOM 117
electromagnetic compatibility
Electrostatic discharge immunity test level 3 conforming to IEC 6100-4-11 Radiated
radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
Electrical fast transient immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
standards
EN 61800-3 environments 2 category C1
IEC 61800-5-1
EN 61800-3 environments 1 category C2
EN 61800-3 environments 1 category C2 EN 61800-3
environments 2 category C2
IEC 61800-3 environments 1 category C1
IEC 61800-3 environments 1 category C3
EN 61800-3 environments 1 category C3
IEC 61800-3 environments 2 category C1
EN 61800-3
IEC 61800-3
EN 61800-3 environments 1 category C1
EN 61800-3 environments 2 category C3
EN 61800-5-1
EN 61800- 3 category C3
IEC 61800-3 environments 2 category C3
IEC 61800-3 environments 1 category C2
EN 55011 class A group 1
IEC 61800-3 category C3
IEC 61800-3 category C2
IEC 61800-3 environments 2 category C2
control loop
Adjustable PI controller
relative humidity
5...95 % without condensation conforming to IEC 60068-2-3
5...95 % without dripping water conforming to IEC 60068-2-3
operating ambient air temperature
-10…40 °C (without derating)
40…50 °C (with reduction factor)
storage room temperature
-25…70 °C
mechanical shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
vibration resistance
1.5 mm (f= 3...13 Hz) conforming to EN/IEC 60068-2-6
1 gn (f= 13...200 Hz) conforming to EN/IEC 60068-2-8
sound intensity
48 dB conforming to 86/188/EEC
insulation resistance
>= 1 MΩ 500 V CC pendant 1 minute
speed accuracy
+/-10% of nominal slip 0.2 Tn to Tn