Main
product range
Harmony K
[ithe] thermal current under enclosure
16 A
type of product or equipment
Cam switch complete
control unit type
Black handle, length = 35 mm
[ui] rated insulation voltage
690 V (pollution degree 3) conforming to IEC 60947-1
switch function
Switch
component name
K2
position 0
With Off position
angular positions
Right: 0° - 45°
presentation of the label
With metallic marking, 0 - 1 black marking
reminder
Without
cam controller head type
With faceplate 45 x 45 mm
Complementary
[ith] conventional thermal current
20 A
padlocking of the rotary handle
Without
[uimp] rated impulse withstand voltage
4 kV in isolation mode
6 kV conforming to IEC 947-1
mounting location
Façade
switching angle
45°
product weight
0,133 kg
short circuit current
10000 A
fixing method
Multi-fixation
electrical life
200000 cycle AC-23
200000 cycle AC-3
600000 cycle AC-15
600000 cycle AC-21
contact operation
Slow-action
mechanical endurance
1000000 cycle
overall height cao
45 mm
overall width cao
45 mm
positive aperture
With
electrical connection
Flexible captive screw clamp terminals, clamping capacity: 2 x 1.5 mm²
Rigid captive screw clamp terminals, clamping capacity: 1 x 2.5 mm²
max command speed
2.5 cc/mn AC-21
2.5 cc/mn AC-23
2.5 cc/mn AC-3
8,333 cc/mn AC-15
overall depth cao
87 mm
short circuit protection
20 A cartouche fusible, type gG
Poles description
3P
Environment
ip degree of protection
IP40 conforming to IEC 529
IP40 conforming to NF C 20-010
product certificates
CSA 240 V 3 hp 3 phase 2 -pole(s)
UL 240 V 0.33 hp single phase 2 -pole(s)
CSA 240 V 1 hp single phase
UL 240 V 1 hp 3 phase
CCC
operating ambient temperature
-25…55 °C
overvoltage category
Class II conforming to IEC 536
Class II conforming to NF C 20-030
standards
EN/CEI 60947-3 for power circuit
EN/CEI 60947-5-1 for remote control
CENELEC EN 50013
GB/T 14048.5 for remote control
GB/T 14048.3 for power circuit
storage room temperature
-40…70 °C
mechanical shock resistance
30 gn conforming to IEC 68-2-27
vibration resistance
5 gn (f = 10...150 Hz) conforming to IEC 68-2-6
protective treatment
TC