Default
Seeria
Harmony XALD, XALK
Main
product range
Harmony XAL
light unit power supply
Direct
name of the device
ZALV
type of product or equipment
light block
[ui] rated insulation voltage
250 V (pollution degree 3) conforming to EN/IEC 60947-1
destination of the product
For XB5 Ø 22 mm control and signaling units
type of signage
Fixed
sale by indivisible quantity
5
Complementary
electrical composition code
MR1
PR1
lamp base
All LEDs
[un] rated nominal voltage
230...240V AC
power consumption
14 mA
assembly of the block
Rear mounting
tightening torque
0.8...1.2 Nm conforming to EN 60947-1
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60947-1
product weight
0,015 kg
connection mode
Screw clamp terminals, <= 2 x 1.5mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, >= 1 x 0.22 mm² without cable end conforming to EN/IEC 60947-1
lifetime
100000 H at rated voltage and 25°C
supply voltage limits
195…264 V CA
screw head shape
Transversal compatible with Phillips n° 1 screwdriver
Transversal compatible with pozidriv n°1 screwdriver
Perforated compatible with flat Ø 4 mm screwdriver
Perforated compatible with flat Ø 5.5 mm screwdriver
resistance to shock waves
1 kV conforming to IEC 61000-5-1
Light source colour
Green
light source
Integrated and protected LED
construction options
For assembly by the customer
Environment
ip degree of protection
IP20 conforming to IEC 60529
product certificates
CSA
operating ambient temperature
-40…70 °C
standards
EN/CEI 60947-5-5
storage room temperature
-40…70 °C
mechanical shock resistance
30 gn (duration = 18 ms) for acceleration on 1/2 sinusoid conforming to EN/IEC 60068-2-27
50 gn (duration = 11 ms) for acceleration on 1/2 sinusoid conforming to EN/IEC 60068-2 -27
electromagnetic emission
Class B conforming to IEC 55011
vibration resistance
5 gn (f= 12...500 Hz) conforming to IEC 60068-2-6
resistance to radiated electromagnetic fields
10 V/m conforming to IEC 61000-4-3
protective treatment
TH
resistance to electrostatic discharges
6 kV on contact (metal parts) conforming to IEC 6100-4-11
8 kV free air (in insulating parts) conforming to IEC 6100-4-11
resistance to fast transients
2 kV conforming to IEC 61000-4-4