Complementary
lamp base
BA 9s
[ie] rated operational current
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1
[un] rated nominal voltage
<=250V
[ith] conventional thermal current
10 A conforming to EN/IEC 60947-5-1
contact description
1 "O" + 1 "F"
Handle front plate colour
47 mm
mounting diameter
22 mm
tightening torque
0.8...1.2 Nm conforming to EN 60947-1
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
product weight
0,097 kg
actuation stroke
1.5 mm (electrical state modified by "O")
2.6 mm (electrical state modified by "F")
4.3 mm (total stroke)
description of iso n°1 terminals
(21-22)NC
(13-14)NO
signaling unit head shape
round
bezel material
Chrome plated metal
electrical life
1000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0, 5 conforming to EN/IEC 60947-5-1 appendix C
resistance to high pressure cleaning
7000000Pa at 55°C, distance: 0.1m
connection mode
Screw clamp terminals, <= 2 x 1.5mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals, 1 x 0.22...2 x 2.5 mm² without cable end conforming to EN/IEC 60947-1
contact operation
Slow-action
contact material
Silver alloy (Ag/Ni)
mechanical endurance
10000000 cycle
width (w)
30 mm
electrical reliability
Λ < 10exp(-6) at 5 V and 1 mA in healthy environment conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V and 5 mA in healthy environment conforming to EN/IEC 60947 -5-4
actuation force
3.5 N electrical state modified by "O"
3.8 N
control unit profile
Orange Flush
screw head shape
Transversal compatible with Phillips n° 1 screwdriver
Transversal compatible with pozidriv n°1 screwdriver
Perforated compatible with flat Ø 4 mm screwdriver
Perforated compatible with flat Ø 5.5 mm screwdriver
product presentation
Complete product
additional control unit info
With normal lens
depth
101 mm
positive aperture
With conforming to EN/IEC 60947-5-1 appendix K
use of contacts
Contacts standards
short circuit protection
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1
light source
Lamps not included
Environment
ip degree of protection
IP66 conforming to CEI 60529
IP67
IP69
IP69K
product certificates
listé UL
CSA
DNV
LROS (Lloyds register of shipping)
BV
GL
class of protection against electric shock
Class I conforming to IEC 60536
operating ambient temperature
-40…55 °C
standards
EN/CEI 60947-1
CSA C22.2 No 14
JIS C8201-5-1
EN/CEI 60947-5-1
UL 508
EN/CEI 60947-5-4
EN/CEI 60947-5-5
JIS C8201-1
shock resistance ik
IK06 conforming to IEC 50102
storage room temperature
-40…70 °C
mechanical shock resistance
30 gn (duration = 18 ms) for acceleration on 1/2 sinusoid conforming to IEC 60068-2-27
50 gn (duration = 11 ms) for acceleration on 1/2 sinusoid conforming to IEC 60068-2-27
vibration resistance
5 gn (f= 2...500 Hz) conforming to IEC 60068-2-6
resistance to nema environment
NO 13
NO 4X
protective treatment
TH