Default
Seeria
Modicon M221
Main
product range
Modicon TM3
type of product or equipment
Digital input module
Complementary
maximum distance between devices
Unshielded cable: <50m for regular input
power consumption
40 mA at 5 V DC at via bus connector (when ON)
5 mA at 5 V DC at via bus connector (when off)
0 mA at 24 V DC at via bus connector (when ON )
0 mA at 24 V DC at via bus connector (in off state)
range compatibility
Modicon M241
Modicon M251
Modicon M221
Modicon M262
response time
4 ms (on)
4 ms (off)
Handle front plate colour
90 mm
current state 0 guaranteed
<= 1mA (input)
product weight
0,1 kg
marking
THIS
current state 1 guaranteed
>= 2.5mA (input)
digital input current
7 mA for input
voltage logic input
24V
tor i/o name
16
width (w)
27,4 mm
isolation
Between input and output at 500 V AC
Not isolated between inputs
Local signalling
for input status 1 LED per channel (green)
voltage state 1 guaranteed
15…28.8 V for input
input impedance
3,4 kOhm
depth
84,6 mm
mounting bracket
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
voltage state 0 guaranteed
0…5 V for input
digital input voltage type
CC
logic input
PNP or NPN (positive/negative)
resistance to shock waves
1 kV I/O common mode conforming to EN/IEC 61000-4-5 DC
electrical connection
10 1.5 mm² removable spring terminal block with pitch 3.81 mm adjustment for inputs
number of digital inputs
16 for input conforming to IEC 61131-2 type 3
Environment
degree of pollution
2
ip degree of protection
IP20 with protective cover in place
operating altitude
0...2000 m
product certificates
C-Tick
cULus
operating ambient temperature
-10…35 °C vertical installation
-10…55 °C horizontal installation
standards
EN/CEI 61131-2
EN/CEI 61010-2-201
storage height
0…3000 m
relative humidity
10…95%, non-condensing (operating)
10…95%, non-condensing (memory)
storage room temperature
-25…70 °C
mechanical shock resistance
15 gn pour 11 ms
electromagnetic emission
Radiated emissions - test level: 40 dBμV/m QP class A (10 m) at 30...230 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A (10 m) at 230 …1000 MHz conforming to EN/IEC 55011
vibration resistance
3.5 mm at 5…8.4 Hz on DIN rail
3 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on panel
3 gn at 8.4…150 Hz on panel
Conducted disturbance resist, induced by radio frequency fields
10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 V detection frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to approvals marine (LR, ABS, DNV, GL)
resistance to radiated electromagnetic fields
10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
resistance to electrostatic discharges
8 kV air conforming to EN/IEC 61000-4-2
4 kV contact conforming to EN/IEC 61000-4-2
resistance to fast transients
1 kV for I/O conforming to EN/IEC 61000-4-4
resistance to magnetic fields
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8