Complementary
[un] rated nominal voltage
24V
digital input compatibility
3-wire PNP proximity sensors for digital input
local display
With
response time
10 ms (from phase 0 to phase 1) for relay output
5 ms (from phase 1 to phase 0) for relay output
tightening torque
0,5 N.m
[uimp] rated impulse withstand voltage
4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1
current state 0 guaranteed
<= 0.5 mA (IB to IG used as digital input circuit)
<= 0.75 mA (digital input circuit I1 to IA and IH to IR)
mechanical life
10000000 cycles for relay output
product weight
0,4 kg
output thermal current
5 A for 2 outputs for relay output
8 A for 8 outputs for relay output
current state 1 guaranteed
>= 1.2 mA (IB to IG used as digital input circuit)
>= 2.2 mA (digital input circuit I1 to IA and IH to IR)
digital input current
4 mA
electrical life
AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to EN/ IEC 60947-5-1
DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to EN/IEC 60947-5-1
DC-13: 500000 cycles at 24 V, 0.6 A for output relay conforming to EN/IEC 60947-5-1
connection mode
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) rigid
Screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) rigid
Screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end
clock drift
12 min/year at 0…55 °C
6 s/month at 25 °C
conversion error
+/- 5% at 25°C for analog input circuit
+/- 6.2% at 55°C for analog input circuit
immunity to micro cuts
1 ms
number of outputs
10 relays
supply voltage limits
19.2…30V
counting frequency
1 kHz for digital input
voltage state 1 guaranteed
>= 15 V for digital input circuit I1 to IA and IH to IR
>= 15 V for IB to IG used as digital input circuit
watch
With
input impedance
12 kOhm for IB to IG used as analog input circuit
12 kOhm for IB to IG used as digital input circuit
7.4 kOhm for digital input circuit I1 to IA and IH to IR
switching capacity in ma
>= 10 mA at 12 V (relay output)
power dissipation in w
10 W with extensions
6 W without extension
backup time
10 years at 25°C
output voltage limits
24...250 V AC (relay output)
5...30 V DC (relay output)
repeat accuracy
+/- 2% at 55°C for analog input circuit
voltage state 0 guaranteed
<= 5 V for digital input circuit I1 to IA and IH to IR
<= 5 V for IB to IG used as digital input circuit
number of digital inputs
16 conforming to EN/IEC 61131-2 type 1
number of control scheme lines
0…500 with FBD programming
0…240 with Ladder programming
analog input range
0...10V
0...24V
availability rate in Hz
0.1 Hz (at rated current) for relay output
10 Hz (at no load) for relay output
type and composition of contacts
"F" for relay output
logic input voltage
24 V CC
operating range
10 m between stations, with shielded cable (sensor not isolated) for analog input circuit
number of analog inputs
6
analog input resolution
8 bits
conversion time
Smart relay cycle time for analog input circuit
cycle time
6…90 ms
analog input type
Common mode
logic input type
Resistive
type of temperature sensor
NTC 10k at 25°C
NTC 1000k at 25°C
KTY81 210/220/221/222/250
Pt 500
low bit value
39 mV for analog input circuit
checks
Program memory at each power-on
Environment
degree of pollution
2 conforming to EN/IEC 61131-2
environment characteristic
EMC directive conforming to EN/IEC 61000-6-2
EMC directive conforming to EN/IEC 61000-6-3
EMC directive conforming to EN/IEC 61000-6-4
EMC directive conforming to EN/IEC 61131-2 zone B
Low voltage directive conforming to EN/IEC 61131-2
ip degree of protection
IP20 conforming to IEC 60529 (terminal block)
IP40 conforming to IEC 60529 (front face)
operating altitude
2000 m
product certificates
GL
C-Tick
CSA
UL
GOST
overvoltage category
III conforming to EN/IEC 60664-1
standards
EN/CEI 61000-4-2 level 3
EN/CEI 61000-4-5
EN/CEI 61000-4-6 level 3
EN/CEI 61000-4-11
EN/CEI 61000-4-3
EN/CEI 60068-2 -27 Ea
EN/CEI 61000-4-12
EN/CEI 60068-2-6 Fc
EN/CEI 61000-4-4 level 3
relative humidity
95% free of condensation or dripping water
disturbance written off/conducted
Class B conforming to EN 55022-11 group 1
operating temperature
-20...40 °C in an unventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2
-20...55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2
storage room temperature
-40…70 °C
transport altitude maxi
3048 m