Main
product range
Harmony electromechanical relay
[ithe] thermal current under enclosure
3 A at -40…55 °C
[uc] control circuit voltage
24 V CC
name of the device
RXM
type of product or equipment
Plug-in relay
range name
Miniature
[ui] rated insulation voltage
250 V conforming to IEC
300 V conforming to CSA
300 V conforming to UL
Complementary
[ie] rated operational current
2 A at 28 V (DC) "F" conforming to IEC
2 A at 250 V (AC) "F" conforming to IEC
1 A at 28 V (DC) "O" conforming to IEC
1 A at 250 V (AC) "O" conforming to IEC
3 A at 28 V (DC) conforming to UL
3 A at 277 V (AC) conforming to UL
contact description
4 F/O
[uimp] rated impulse withstand voltage
2,5 kV pendant 1,2/50 µs
minimum switching capacity
15mW at 3mA, 5V
product weight
0,037 kg
protection category
RT I
nominal resistive load
3 A at 250 V AC
3 A at 28 V DC
Average coil consumption in w
0.9W
electrical life
100000 cycles for resistive load depending on mounting position and working environment
led status
With
duty cycle
20,00%
limits of rated operational voltage
19,2...26,4 V CC
contact material
Gold plated silver
mechanical endurance
10000000 cycle
pin shape
Plat
product presentation
Complete product
maximum switching power
750 VA/84 W
test levels
A-level
average coil resistance
650 Ohm at 20 °C +/- 10 %
drop-out voltage threshold
>= 0,1 Uc
operating time
20 ms
mounting position
All positions
trigger time
20 ms
order type
Lockable test button
dielectric strength
1300 V AC between contacts with microbreak
2000 V AC between coil and contact
2000 V AC between poles
command speed
<= 1200 cycles/hour under load
<= 18000 cycles/hour without load
maximum cut-off voltage
250 V conforming to IEC
Environment
degree of pollution
2
ip degree of protection
IP40 conforming to EN/IEC 60529
product certificates
Lloyd's
CSA
CE
UL
GOST
standards
EN/CEI 61810-1
CSA C22.2 No 14
UL 508
operating temperature
-40…55 °C
storage room temperature
-40…85 °C
mechanical shock resistance
10 gn for running
30 gn for not running
vibration resistance
3 gn, amplitude = +/- 1 mm (f = 10…150 Hz) 5 cycles in operation
5 gn, amplitude = +/- 1 mm (f = 10…150 Hz) 5 cycles not in operation