Main
product range
Harmony electromechanical relay
[ithe] thermal current under enclosure
10 A at -40…55 °C
[uc] control circuit voltage
230 V AC 50/60Hz
name of the device
RUM
type of product or equipment
Plug-in relay
range name
Universal
[ui] rated insulation voltage
250 V conforming to IEC
300 V conforming to CSA
300 V conforming to UL
Complementary
[ie] rated operational current
10 A at 277 V AC conforming to UL
10 A at 30 V DC conforming to UL
10 A at 277 V AC (same polarity) conforming to CSA
10 A at 30 V DC conforming to CSA
5 A at 250 V AC ("O") conforming to IEC
5 A at 28 V DC ("O") conforming to IEC
10 A at 250 V AC ("F") conforming to IEC
10 A at 28 V DC ("F") conforming to IEC
contact description
3 "OF"
[uimp] rated impulse withstand voltage
4 kV (1,2/50 µs)
minimum switching capacity
170mW at 10mA, 17V
product weight
0,086 kg
protection category
RT I
nominal resistive load
10 A at 250 V AC
10 A at 28 V DC
average coil consumption in va
3 to 60 Hz
electrical life
100000 cycles for resistive load
led status
Without
duty cycle
20,00%
limits of rated operational voltage
184...253VCA
safety reliability data
B10d = 100000
contact material
AgNi
mechanical endurance
5000000 cycle
pin shape
Cylindrical
product presentation
Complete product
maximum switching power
2 500 VA/280 W
test levels
A-level
average coil resistance
6800 Ohm at 20 °C +/- 15 %
drop-out voltage threshold
>= 0.15 Uc AC
operating time
20 ms at rated voltage
mounting position
All positions
trigger time
20 ms at rated voltage
order type
Lockable test button
dielectric strength
1500 V AC between contacts with microbreak
2500 V AC between coil and contact with reinforced
2000 V AC between poles with basic
command speed
<= 18000 cycles/hour without load
<= 1200 cycles/hour under load
maximum cut-off voltage
250 V conforming to IEC
Environment
degree of pollution
2
ip degree of protection
IP40
product certificates
EAC
CSA
UL
standards
CSA C22.2 No 14
EN/CEI 61810-1
UL 508
operating temperature
-40…55 °C
storage room temperature
-40…85 °C
mechanical shock resistance
10 gn (duration = 11 ms) for operating conforming to EN/IEC 60068-2-27
10 gn (duration = 11 ms) for not operating conforming to EN/IEC 60068-2-27
vibration resistance
3 gn, amplitude = +/- 1 mm (f = 10…150 Hz) 5 cycles in operation
4 gn, amplitude = +/- 1 mm (f = 10…150 Hz) 5 cycles not in operation