Main
product range
Harmony electromechanical relay
[ithe] thermal current under enclosure
8 A at -40…40 °C
[uc] control circuit voltage
24 V CC
name of the device
RSB
type of product or equipment
Plug-in relay
range name
Interface relays
[ui] rated insulation voltage
400 V conforming to EN/IEC 60947
sale by indivisible quantity
10
Complementary
[ie] rated operational current
4 A (AC-1/DC-1) "O" conforms to CEI
8 A (AC-1/DC-1) "F" conforms to CEI
[ue] rated operational voltage
19.2 to 26.4 V DC
contact description
2 "O/F"
[uimp] rated impulse withstand voltage
3.6 kV conforming to IEC 61000-4-5
minimum switching capacity
300mW at 5mA
minimum switching current
5 mA
protection category
RT I
marking
THIS
nominal resistive load
8 A at 250 V AC
8 A at 28 V DC
average coil consumption
0,45 W CC
electrical life
100000 cycle, 8 A à 250 V, AC-1 "F"
100000 cycle, 4 A à 250 V, AC-1 "O"
led status
Without
contact operation
Standard
safety reliability data
B10d = 100000
contact material
Silver alloy (Ag/Ni)
mechanical endurance
30000000 cycle
pin shape
Plat
product presentation
Complete product
maximum switching power
2000 VA AC
224 W DC
average coil resistance
1440 Ohm mains: DC at 20°C +/- 10%
drop-out voltage threshold
>= 0,1 Uc CC
operating time
4 ms between coil de-energization and rep cont inhib
9 ms between coil energization and ep cont inhib
mounting position
All positions
minimum switching voltage
5V
order type
Without push button
dielectric strength
1000 V AC between contacts
2500 V AC between poles
5000 V AC between coil and contact
command speed
<= 600 cycles/hour under load
<= 72000 cycles/hour without load
maximum cut-off voltage
300 V CC
400 V CA
Environment
ip degree of protection
IP40 conforming to EN/IEC 60529
product certificates
GOST
UL
CSA
standards
EN/CEI 61810-1
UL 508
CSA C22.2 No 14
operating temperature
-40…70 °C (CA)
-40…85 °C (CC)
storage room temperature
-40…85 °C
mechanical shock resistance
10 gn (duration = 11 ms) for not operating conforming to EN/IEC 60068-2-27
5 gn (duration = 11 ms) for operating conforming to EN/IEC 60068-2-27
vibration resistance
+/- 1 mm (f= 10...55 Hz) conforming to EN/IEC 60068-2-6