Main
product range
Harmony electromechanical relay
[ithe] thermal current under enclosure
25 A at -40…55 °C relay side by side without space
30 A at -40…55 °C space 13 mm between two relays
[uc] control circuit voltage
24 V CC
name of the device
RPF
type of product or equipment
DIN Rail/Panel Mount Relays
range name
Powerful
[ui] rated insulation voltage
250 V conforming to IEC
300 V conforming to UL
medium resistance
350 Ohm at 20 °C +/- 10 %
Complementary
[ie] rated operational current
30 A at 277 V (AC) "F" conforming to UL
20 A at 28 V (DC) "F" conforming to UL
30 A at 250 V (AC) "F" conforming to IEC
25 A at 28 V (DC) "F" conforming to IEC
3 A at 277 V (AC) "O" conforming to UL
3 A at 28 V (DC) "O" conforming to UL
3 A at 250 V (AC) "O" " conforming to IEC
3 A at 28 V (DC) "O" conforming to IEC
contact description
2 "O/F"
recommended minimum switching capacity
6 000 MW 500 mA / 12 V pour "F"
170 mW 10 mA / 6 V pour "O"
[uimp] rated impulse withstand voltage
4 kV pendant 1,2/50 µs
product weight
0,082 kg
protection category
RT II
nominal resistive load
25 A at 28 V DC
30 A at 250 V AC
average coil consumption
1.7W
electrical life
100000 cycles for resistive load
duty cycle
10,00%
safety reliability data
B10d = 100000
contact material
Silver tin oxide
control circuit voltage range
19.2 to 26.4V
mechanical endurance
5000000 cycle
overall height cao
68,5 mm
pin shape
Plat
product presentation
Complete product
maximum switching power
7 500 VA/700 W
overall width cao
33,7 mm
test levels
A-level
mounting bracket
DIN Rail
Panel
drop-out voltage threshold
>= 0,1 Uc
operating time
25 ms
mounting position
All positions
trigger time
25 ms
order type
Without lockable test button
overall depth cao
39,2 mm
dielectric strength
2000 V AC between poles with basic
4000 V AC between coil and contact with reinforced
1500 V AC between contacts with microbreak
command speed
<= 1200 cycles/hour under load
<= 18000 cycles/hour without load
maximum cut-off voltage
250 V conforming to IEC
Environment
degree of pollution
3
ip degree of protection
IP40 conforming to EN/IEC 60529
product certificates
UL
GOST
CSA
CE
standards
CSA C22.2 No 14
UL 508
EN/CEI 61810-1
operating temperature
-40…55 °C
storage room temperature
-40…85 °C
mechanical shock resistance
10 gn for running
30 gn for not running
vibration resistance
3 gn, amplitude = +/- 1 mm (f = 10…150 Hz) 5 cycles in operation
10 gn, amplitude = +/- 1 mm (f = 10…150 Hz) 5 cycles not in operation