Seeria
Harmony RE/RM
Main
product range
Harmony Analog
type of product or equipment
Voltage/current converter
[ui] rated insulation voltage
2 kV
Complementary
[un] rated nominal voltage
24 V DC +/- 20%, isolated
power consumption
<= 70 mA for voltage output
<= 90 mA for current output
clamp terminal capacity
2 x 1,5 mm²
1 x 2,5mm²
tightening torque
0,6…1,1 N.m
abnormal analog output current
-30…0 mA, output selected 0...20 mA, when no input or input line broken
4…30 mA, output selected 4...20 mA, when no input or input line cut off
product weight
0,15 kg
fixing method
By screws (mounting plate)
By clipping (35 mm symmetrical DIN rail)
marking
THIS
temperature coefficient
1000 ppm/°C, range: 0...5 A
2000 ppm/°C, range: 0...15 A
500 ppm/°C, range: 0...1.5 A
safety reliability data
B10d = 22108
MTTFd = 23.9 years
Local signalling
for power ON LED (green)
measurement error
+/- 10% full scale at 20°C (10V/m electromagnetic interference)
+/- 5% of scale at 20°C
abnormal analog output voltage
-15...0 V, when no input or input line interrupted
repeat accuracy
+/- 0.2% full scale at 20°C
+/- 0.6% full scale at 60°C
resistance to shock waves
0.5 kV for 1.2/50 µs conforming to IEC 61000-4-5
kind of protection
Output reverse polarity
protection Output short-circuit
protection Output overvoltage protection (+/- 30 V)
analog input type
Current 0...1.5 A AC/DC 50/60 Hz
Current 0...15 A AC/DC 50/60 Hz
Current 0...5 A AC/DC 50/60 Hz
analog output type
Current 0...20 mA <= 500 Ohm with wiring
Current 4...20 mA <= 500 Ohm with wiring
Voltage 0...10 V >= 100 kOhm with wiring
Environment
degree of pollution
2 conforming to IEC 60664-1
ip degree of protection
IP20 (terminal block)
IP50 (enclosure)
product certificates
CSA
UL
GL
operating ambient temperature
0…50 °C juxtaposed assembly
0…60 °C 2 cm spacing
standards
CEI 60947-1
CEI 60584-1
fire resistance
850 °C conforming to IEC 60695-2-1
850 °C conforming to UL
disturbance written off/conducted
CISPR11
CISPR22 group 1- class B
storage room temperature
-40…85 °C
mechanical shock resistance
50 gn for 11 ms conforming to IEC 60068-2-27
vibration resistance
5 gn (f= 10...100 Hz) conforming to IEC 60068-2-6
resistance to electrostatic discharges
6 kV (in contact) conforming to IEC 6100-4-11 level 3
8 kV (in air) conforming to IEC 6100-4-11 level 3
resistance to fast transients
1 kV conforming to IEC 61000-4-4 (on input-output)
2 kV conforming to IEC 61000-4-4 (on power supply)