Default
Seeria
PowerLogic PM3000
Main
Range
PowerLogic
name of the device
PM3255
type of product or equipment
Measurement unit
Product Name
PowerLogic PM3000
Complementary
power quality analysis
up to the 15th harmonic
[in] rated current
5 A
1 A
application
Multi-tariff
Power monitoring
Sub-billing
memory capacity
512 Ko
Handle front plate colour
95 mm
accuracy class
Class 0.5S active energy conforming to IEC 62053-22
Class 1 active energy conforming to IEC 62053-21
Class 2 reactive energy conforming to IEC 62053-23
Class C active energy conforming to EN 50470-3
data logging
Energy consumption logs
15 alarms
Power
logs Timestamp
Min/max number of instantaneous values
product weight
0,26 kg
measuring current
0,02…1,2 A
0,05…6 A
mode d'installation
snap-on
power consumed in va
5 VA
type of measurement
Active and reactive
power Apparent power
Current
Voltage
Energy Power
factor
Frequency
Current total harmonic distortion THD (I)
Voltage total harmonic distortion THD (U)
information displayed
Fares (4)
width (w)
90 mm
network frequency
60 Hz
50 Hz
number of entries
2 digital 0…4 mA 11…40 V DC
number of outputs
2 digital (static)
frequency measurement range
45…65 Hz
measurement accuracy
Courant 0,3 % 0,5…6 A
Courant 0,5 % 0,1…1,2 A
Tension 0,3 % 50…330 V
Tension 0,3 % 80…570 V
communication port protocol
Modbus at 9.6…38.4 kbaud
depth
70 mm
mounting bracket
DIN rail
Network type
3P
3P + N
1P + N
support port de communication
RS485
sampling rate
32 samples/run
display resolution
128 x 96 pixels
measuring voltage
50…330 V AC 45...65 Hz direct
50…330 V AC 45...65 Hz phase-neutral
80…570 V AC 45...65 Hz direct
80…570 V AC 45...65 Hz phase -phase
570…999000 V AC 45...65 Hz with external virtual terminal
type of display
Backlit LCD
supply voltage
100…277 V CA 45...65 Hz
173…480 V CA 45...65 Hz
100…300 V CC
analog input type
courant 0...5 A
courant 0…1 A
Environment
degree of pollution
2
ip degree of protection
IP40 front face: conforming to IEC 60529
IP20 body: conforming to IEC 60529
operating altitude
< 3000 m
product certificates
CE conforming to IEC 61010-1 (safety)
CE conforming to EN 61557-12 (power control)
CE conforming to EN/IEC 61326-1 (EMC)
UKCA conforming to BS EN 61010-1 (safety)
UKCA conforming to BS EN 61557-12 (power control)
UKCA conforming to BS EN 61326-1 (EMC)
CULus conforming to EN 61010-1 (safety)
CULus conforming to UL 61010-1 (safety)
EAC (under -counter)
RCM
electromagnetic compatibility
Electrostatic discharge level 4 conforming to IEC 6100-4-11
Disturbance due to electromagnetic fields level 3 conforming to IEC 61000-4-3
Electrical fast transient immunity test level 4 conforming to IEC
61000-4-4 overvoltages level 4 conforming to IEC 61000-4-5
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Power frequency magnetic field - test level: 0.5 mT conforming to IEC 61000-4-8
Conducted and radiated emissions class B conforming to EN 55022
overvoltage category
III
standards
BS EN 61557-12
CEI 61557-12
EN 61557-12
BS EN 61326-1
CEI 61326-1
EN 61326-1
BS EN 62052-11
CEI 62052-11
EN 62052-11
BS EN 62053-21
CEI 62053-21
EN 62053 -21
BS EN 62053-22
CEI 62053-22
EN 62052-22
BS EN 62053-23
CEI 62053-23
EN 62052-23
BS EN 61010-1
EN 61010-1
CEI 61010-1
UL 61010-1
BS EN 61010-2 -30
CEI 61010-2-30
EN 61010-2-30
UL 61010-2-30
ANSI C12.20
relative humidity
5…95% at 50°C
operating temperature
-25…70 °C
storage room temperature
-40…85 °C