Kõik kategooriad
Võrdle Ostukorv
LV865307 - MicroLogic 7.0X juhtseade, MasterPact MTZ1, väljatõmmatavad kaitselülitid, LSIV kaitsed - Schneider Electric - MicroLogic 7.0X juhtseade, MasterPact MTZ1, väljatõmmatavad kaitselülitid, LSIV kaitsed - Schneider Electric - 0
LV865307 - MicroLogic 7.0X juhtseade, MasterPact MTZ1, väljatõmmatavad kaitselülitid, LSIV kaitsed - Schneider Electric - MicroLogic 7.0X juhtseade, MasterPact MTZ1, väljatõmmatavad kaitselülitid, LSIV kaitsed - Schneider Electric - 0
Tellimisel

LV865307 – Schneider Electric

EAN: 3606480823107
1 254,06 € KM-ta
1 555,03 € KM-ga
MicroLogic 7.0X juhtseade, MasterPact MTZ1, väljatõmmatavad kaitselülitid, LSIV kaitsed - Schneider Electric
1 555,03 €
SPETSIFIKATSIOONID
Default
Seeria Masterpact MTZ
Main
Range Masterpact
[idn] differential sensitivity threshold setting range 0.5…30 ​​A adjustable in steps of 0.1 A
circuit breaker application CEI distribution rules
name of the device Micrologic 7.0 X
type of product or equipment Control unit
trigger protection functions LSIV
poles 3P
4P
differential protection time delay setting type Adjustable
type of trigger Electronic
protected poles 4P 3d
3P 3d
4P 3d + OSN
4P 4d
4P 3d + N/2
Complementary
[ii] instantaneous pick-up adjustment range 2...15 x In adjustable in steps of 0.5 x In with embedded HMI
2...15 x In adjustable in steps of 0.1 x In with Ecoreach software or Masterpact MTZ mobile application
Activation Ii on/off
[ue] rated operational voltage 600 V CA, +/- 10 %
[un] rated nominal voltage 60…800 ms reset time
140…1000 ms pause
application Protection, monitoring and control of equipment
range compatibility Masterpact (MasterPacT MTZ1) circuit breaker
[ir] long time pick-up adjustment range 0.4…1 x In adjustable in steps of 1 A
[isd] short-time threshold setting range 1.5...10 x Ir adjustable in steps of 0.5 x Ir with embedded HMI
1.5...10 x Ir adjustable in steps of 0.1 x Ir with Ecoreach software or Masterpact MTZ mobile application
trigger caliber 400 A
630 A
800 A
1000 A
1250 A
1600 A
[li mode] instantaneous delay adjustment range 0 ms in fast
20 ms in standard
accuracy class Class 5: current total harmonic distortion rate THD (I)
Class 0.5: unbalance voltage
Class 1: active and reactive energy by pulse counting (+/- Wh, +/- VAR.h)
Class 2 : total harmonic distortion rate in voltage THD (V)
data logging Timestamp
Data
reports Event reports
Maintenance
logs Min/max number of instantaneous values
​​Alarm logs
mounting location Indoor use only
[tr] long-time delay adjustment range 12.5…600 s at 1.5 x Jump
0.5…24 s at 6 x Jump
0.7…16.6 s at 7.2 x Jump
[tsd] short-time delay adjustment range 0,1…0,4 s I²t=on
0…0,4 s I²t=off
mode d'installation Extract
type of measurement power meter
energy management Active, reactive and apparent energy measurement (standard)
Electrical network measurement (standard)
Energy measurement (standard)
network frequency 50/60 Hz
thermal memory Yes
frequency measurement range 45…250 Hz
measurement accuracy Current I1, I2, I3, Iavg, Idemand for MTZ1: +/- 0.5 % 40...1600 x 1.2 A
Reactive power Q, Q1, Q2, Q3, Q demanded: +/- 2 %
Active power P, P1, P2, P3, Prequested: +/- 1%
Apparent power S, S1, S2, S3, Srequested: +/- 1%
Voltage V21, V32, V13, VLNavg: +/- 0.5% 120. ..400 x 1.2 V
Voltage V21, V32, V13, VLLavg: +/- 0.5 % 208...690 x 1.2 V
Frequency: +/- 0.005 Hz
Unbalance current: +/- 0, 5 %
Apparent energy Es INPUT/OUTPUT/tot: +/- 1 % - 10...10 GVAh
Reactive energy Ep INPUT/OUTPUT/tot: +/- 2 % - 10...10 GVARh
Active energy Ep INPUT/OUTPUT /tot: +/- 1 % - 10...10 GWh
Power factor: +/- 1 %
communication port protocol Bluetooth 4.0 LE peer-to-peer 30 kbit/s
NFC peer-to-peer 28800 baud conforming to ISO 15963
USB peer-to-peer 115 kbaud
Network type THAT
type of network and machine diagnostics System Health (HMI) Overview: Circuit Breaker Health (as standard)
Contacts State: Circuit Breaker Health (as standard)
Micrologic Lifetime: Circuit Breaker Health (as standard) as standard)
Trip cause indication: circuit breaker trip cause (as standard)
Identification card: diagnostic data (as standard)
Configured alarm summary: diagnostic data (as standard)
Monitored function: diagnostic data (as standard)
Operation: diagnostic data (as standard)
Micrologic test: test (as standard)
Protection test: test (as standard)
Selectivity test: test (as standard)
Trip context information: Management of a trip event (as standard)
Operation: advanced diagnostics (as standard)
Circuit breaker life: circuit breaker health status (as standard)
differential protection With
instantaneous delay setting type Adjustable
timer setting type Adjustable in steps of 0.5 s
type of instantaneous threshold adjustment (ii) Adjustable
measuring voltage 100…1200 V AC 50/60 Hz per phase
type of display LCD display - 128 x 96 pixels
kind of protection Overload protection (long time) conforming to ANSI 49
Instantaneous short-circuit protection conforming to ANSI 50
Short-time protection conforming to ANSI 51 Earth-leakage
protection conforming to ANSI 51G
zsi logic selective latch area With
type of count Current I1, I2, I3, In, Ig: maximum (as standard)
Average voltage Vavg (as standard)
Active power P, P1, P2, P3 (as standard)
Reactive power Q, Q1, Q2, Q3 (as standard)
Power apparent current S, S1, S2, S3 (as standard)
Power factor (as standard)
Frequency (as standard)
Current total harmonic distortion rate THD (I): inst, avg, min avg, max avg fundamental voltage (as standard )
Current total harmonic distortion rate THD (I): inst, avg, min avg, max ag voltage RMS (as standard)
Voltage V21, V32, V13, V1, V2, V3: instantaneous (as standard)
Voltage V21, V32 , V13, V1, V2, V3: minimum (as standard)
Voltage V21, V32, V13, V1, V2, V3: maximum (as standard)
Total harmonic distortion in voltage THD (V): inst, avg, min avg, max avg fundamental voltage (as standard)
Total harmonic distortion rate in voltage THD (V): inst, avg, min avg, max avg RMS voltage (as standard)
Current demand I1, I2, I3, In, Iavg (as standard)
Active (P), reactive (Q) and apparent power (S) requested (as standard)
Environment
degree of pollution 3 conforming to IEC 60947-1
environment characteristic Wet location not approved for use conforming to IEC 61010-1
operating altitude <= 2000 m sans déclassement
<= 4000 m with operational voltage derating 600 V AC
<= 5000 m with operational voltage derating 560 V AC
electromagnetic compatibility Electrostatic discharge immunity test conforming to IEC 6100-4-11
Electromagnetic field disturbance conforming to IEC 61000-4-3
Electrical fast transient immunity test conforming to IEC
61000-4-4 immunity to shock waves 1.2/50 µs conforming to IEC 61000-4-5
Conducted RF disturbances conforming to IEC 61000-4-6
Conducted and radiated emissionsA conforming to CISPR22
overvoltage category IV conforming to IEC 61010-1
standards EN/CEI 60947-1
EN/IEC 60092-202
EN/CEI 60947-2
EN/CEI 60255-1
EN/CEI 61010-1
measurement category Category IV conforming to IEC 61010-2-30
relative humidity 95 % at 55 °C conforming to IEC 60068-2-30
operating temperature -25…70 °C (fonctionnement)
-35 °C (for start-up of product)
KKK ja hinna lisateave

Võta meiega ühendust

Professionaalne elektriseadmete müük Eestis, Lätis, Leedus ja Soomes. Sertifitseeritud madalpinge komponendid, kaitselülitid, kontaktorid ja tööstusautomaatika lahendused. Sama päeva hinnapakkumised ja kiire tarne Baltikumis ja Soomes

Baltelec
+372 5326 4976

E–R 9:00–17:00

info@baltelec.ee

Vastame 2 tunni jooksul

LV865307 Schneider Electric on lahendus kategooriast Masterpact MTZ, mis on mõeldud ettevõtetele. BaltElec tegeleb mahupõhise müügi ja distributsiooniga Eestis, Lätis, Leedus ja Soomes.

  • Autentne Schneider Electric toode, vastavusdokumendid päringu alusel.
  • Projektihind – küsi pakkumist suuremate koguste jaoks (võimalik, et sätestame MOQ).
  • Kiire tarne Baltikumis ning Soomes; koostöö logistikapartneritega.
  • Tehniline tugi ja nõustamine valikul vastavalt Sinu rakendusele.

Hind: Küsi eripakkumist. Hind sõltub kogusest, tarne- ja maksetingimustest.

KKK tootele LV865307 - Schneider Electric

Hiljuti vaadatud
LV865307 - Schneider Electric
MicroLogic 7.0X juhtseade, MasterPact MTZ1, väljatõmmatavad kaitselülitid, LSIV kaitsed
1 254,06 € KM-ta
1 555,03 € KM-ga
Tellimisel