SPETSIFIKATSIOONID
Default
Seeria TeSyS LT
Main
Device short name LTME
Range TeSys
Product Name TeSys T
[ui] rated insulation voltage 690 V conforming to EN/IEC 60947-1
690 V conforming to CSA C22.2 No 14
690 V conforming to UL 508
Complementary
compatibility code LTME
range compatibility TeSys (TeSys T) LTMR motor controller
Product certifications LROS (Lloyds register of shipping)
ATEX
NOM
EAC
RMRoS
GL
UL
DNV
BV
RINA
KERI
C-Tick
CSA
CCC
ABS
Connection pitch 5.08 mm
Handle front plate colour 61 mm
Product or component type Extension module
tightening torque Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm
[uimp] rated impulse withstand voltage 4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1
6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1
Connections - terminals Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) solid without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) flexible with cable end
Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24...AWG 14) flexible without cable end
Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) solid without cable end
current state 0 guaranteed Logic input: 0...40 V and 2...15 mA for 25 ms
current state 1 guaranteed Logic input: 79...264 V and <= 15 mA for 25 ms
Device application Equipment monitoring and control
Contacts type and composition Without
input current 3.1 mA at 100 V
7.5 mA at 240 V
width (w) 45 mm
mechanical robustness Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27
Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
Net weight 0.21 kg
measurement accuracy 1 % voltage (100...830 V)
3 % power factor
5 % active and reactive power
depth 120.7 mm
Pollution degree 3
Maximum operating rate 1800 cyc/h
Logic input number 4
Maximum output switching frequency 2 Hz
Metering type Imbalance voltage
Active power P, P1, P2, P3
Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Voltage U21, U32, U13, V1, V2, V3
Reactive power Q, Q1, Q2, Q3
Frequency
Power factor
Supply Via the controller
Environment
Ambient air temp for storage/transportation -40…80 °C
ip degree of protection IP20
operating altitude <= 2000 m without derating
ambient air temperature for operation -20…60 °C
electromagnetic compatibility Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2
Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4
Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4
Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6
Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Voltage inputs: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5
Voltage inputs: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5
Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
overvoltage category III
standards CSA C22.2 No 14
IACS E10
IEC 60947-4-1
UL 508
EN 60947-4-1
fire resistance 650 °C conforming to EN/IEC 60695-2-12
960 °C conforming to UL 94
protective treatment 12 x 24 hour cycles conforming to EN/IEC 60068-2-30
48 h conforming to EN/IEC 60070-2-11
TH conforming to EN/IEC 60068
KKK ja hinna lisateave

Võta meiega ühendust

Professionaalne elektriseadmete müük Eestis, Lätis, Leedus ja Soomes. Sertifitseeritud madalpinge komponendid, kaitselülitid, kontaktorid ja tööstusautomaatika lahendused. Sama päeva hinnapakkumised ja kiire tarne Baltikumis ja Soomes

Baltelec
+372 5326 4976

E–R 9:00–17:00

info@baltelec.ee

Vastame 2 tunni jooksul

Schneider Electric LTMEV40FM on toode kategooriast Mootorihaldus, mis on mõeldud ettevõtetele. BaltElec tegeleb mahupõhise müügi ja distributsiooniga Eestis, Lätis, Leedus ja Soomes.

  • Originaal Schneider Electric toode, vastavusdokumendid päringu alusel.
  • Projektihind – küsi pakkumist suuremate koguste jaoks (võimalik, et sätestame MOQ).
  • Tõhus ja kiire logistika Baltikumis ning Soomes; koostöö tunnustatud kulleritega.
  • Tehniline tugi ja ettepanekud sobivuse kohta vastavalt Sinu rakendusele.

Hinnainfo: Küsi projektipakkumist. Hind sõltub kogusest, tarne- ja maksetingimustest.

KKK tootele LTMEV40FM - Schneider Electric

Hiljuti vaadatud
LTMEV40FM - Schneider Electric
Motor Management, TeSys T, mootorikontroller, laiendusmoodul, 4 sisendit, LTMR-kontrollerile, 100 to
133,80 € KM-ta
165,91 € KM-ga
Tellimisel