Default
Seeria
TeSyS Deca ülekoormusreleed
Main
Range
TeSys
TeSys Deca
name of the device
LRD
thermal overload class
Class 10A conforming to IEC 60947-4-1
type of product or equipment
Bimetal differential
Product Name
TeSys LRD
TeSys Deca
[ui] rated insulation voltage
Power circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
Power circuit: 690 V conforming to IEC 60947-4-1
use of the relay
Motor protection
Complementary
associated accessories
LC1D65A
LC1D50A
[ue] rated operational voltage
690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
[ith] conventional thermal current
5 A for signaling circuit
caliber of the fuse to be associated
4 A gG for signaling circuit
4 A BS for signaling circuit
allowable current
0.95 A at 380 V AC-15 for signaling circuit
0.06 A at 440 V DC-13 for signaling circuit
Handle front plate colour
70 mm
tightening torque
Remote control: 1.7 Nm - on screw clamp terminal blocks
Power circuit: 5 Nm - on EverLink BTR screw connectors
[uimp] rated impulse withstand voltage
6 kV
auxiliary contacts
1 "O" + 1 "F"
temperature compensation
-20…60 °C
product weight
0,375 kg
thermal protection setting area
48…65 A
connection mode
Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm² flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm² flexible with cable end
Control circuit: terminal blocks screw clamp 2 cable(s) 1...2.5 mm² rigid without cable end
Power circuit: EverLink BTR screw connectors 1 cable(s) 1...35 mm² flexible without cable end
Power circuit: BTR screw connectors EverLink 1 cable(s) 1...35 mm² flexible with cable end
Power circuit: BTR screw connectors EverLink 1 cable(s) 1...35 mm² rigid without cable end
width (w)
55 mm
mechanical robustness
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
Vibrations: 4 gn conforming to IEC 60068-2-6
network frequency
0 to 400 Hz
Flame retardance
V1 conforming to UL 94
trigger point
1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
depth
123 mm
mounting bracket
Plate, with specific accessories
Rail, with specific accessories
Under the contactor
Network type
CC
CA
sensitivity to phase loss
Tripping current 130% of Ir on two phases, the last at level 0
order type
Red push button: stop
Blue push button: reset
dielectric strength
1.89 kV at 50 Hz conforming to IEC 60947-1
Environment
ip degree of protection
IP20 conforming to IEC 60529
product certificates
CEI
UL
CSA
CCC
EAC
DNV-GL
RMRS
EU-RO MR
LROS (Lloyds register of shipping)
ATEX INERIS
UKCA
standards
EN/CEI 60947-4-1
EN/CEI 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/ T 14048.4
GB/T 14048.5
EN 50495
operating temperature
-20...60 °C without current reduction conforming to IEC 60947-4-1
storage room temperature
-60…70 °C
climatic resistance
conform to IACS E10