Default
Seeria
TeSyS Deca ülekoormusreleed
Main
Range
TeSys
name of the device
LR9D
thermal overload class
Class 10 conforming to IEC 60947-4-1
type of product or equipment
Electronic thermal overload relay
Product Name
TeSys LRD
TeSys Deca
[ui] rated insulation voltage
Power circuit: 1000 V conforming to IEC 60947-4-1
Power circuit: 600 V conforming to CSA
Power circuit: 600 V conforming to UL
use of the relay
Motor protection
Complementary
associated accessories
LC1D115
LC1D150
NSX circuit breaker
[ue] rated operational voltage
690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
[un] rated nominal voltage
24 V CC
[ith] conventional thermal current
5 A for signaling circuit
caliber of the fuse to be associated
4 A gG for signaling circuit
4 A BS for signaling circuit
Handle front plate colour
118 mm
tightening torque
Warning circuit: 0.45 Nm - on screw-clamp terminals
Power circuit: 18 Nm - on M8 bars
Remote control: 1.2 Nm - on screw-clamp terminals
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-1
auxiliary contacts
1 "O" + 1 "F"
maximum voltage drop
<2.5 V closed state
temperature compensation
-20…60 °C
product weight
0,885 kg
signaling function
Alarm
thermal protection setting area
60…100 A
connection mode
Power circuit: bars
Remote control: screw clamp terminals 1 cable(s) 0.5...1.5 mm² flexible without cable end
Remote control: screw clamp terminals 2 cable(s) 0.5...1.5 mm² flexible without cable end
Warning circuit: screw clamp terminals 1 cable(s) 0.5...1.5 mm² flexible without cable end
width (w)
115 mm
mechanical robustness
Vibrations: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Shocks: 13 Gn for 11 ms conforming to IEC 60068-2-7
network frequency
50...60 Hz
supply voltage limits
17…32V
switching capacity in ma
0…150 mA
trigger point
1.05 +/- 0.06 in alarm conforming to IEC 60947-4-1
1.12 +/-0.06 In A dropout conforming to IEC 60947-4-1
depth
125 mm
mounting bracket
Under
Rail Contactor
Network type
THAT
sensitivity to phase loss
Tripping in 4 s +/- 20 % conforming to IEC 60947-4-1
order type
Red push button: stop
Blue push button: reset
dielectric strength
1.89 kV at 50 Hz conforming to IEC 60947-1
Environment
ip degree of protection
IP20 conforming to IEC 60529
operating altitude
<= 2000 m without current reduction
product certificates
UL
CSA
CCC
UKCA
standards
EN/CEI 60947-4-1
EN/CEI 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/ T 14048.4
GB/T 14048.5
operating temperature
-20...60 °C without current reduction conforming to IEC 60947-4-1
storage room temperature
-60…70 °C
climatic resistance
conform to IACS E10