LC2D18KUE - TeSys Deca pöördkontaktor 3P <= 440 V 18 A AC3 100...250 V AC/DC mähis. - Schneider Electric - TeSys Deca pöördkontaktor 3P <= 440 V 18 A AC3 100...250 V AC/DC mähis. - Schneider Electric - 0
LC2D18KUE - TeSys Deca pöördkontaktor 3P <= 440 V 18 A AC3 100...250 V AC/DC mähis. - Schneider Electric - TeSys Deca pöördkontaktor 3P <= 440 V 18 A AC3 100...250 V AC/DC mähis. - Schneider Electric - 0
Tellimisel

LC2D18KUE – Schneider Electric

200,89 € KM-ta
249,10 € KM-ga
TeSys Deca pöördkontaktor 3P <= 440 V 18 A AC3 100...250 V AC/DC mähis. - Schneider Electric
249,10 €
SPETSIFIKATSIOONID
Default
Seeria TeSyS Deca kontaktorid
Main
Contactor application Resistive load
Motor control
Device short name LC2D
Interlocking type Mechanical
Range TeSys
TeSys Deca
[uc] control circuit voltage 100...250 V AC 50/60 Hz
100...250 V DC
Front cover With
Product Name TeSys D Green
TeSys Deca
Motor power hp (ul / csa) 1 hp at 115 V AC 60 Hz for 1 phase motors
3 hp at 230/240 V AC 60 Hz for 1 phase motors
5 hp at 200/208 V AC 60 Hz for 3 phases motors
5 hp at 230/240 V AC 60 Hz for 3 phases motors
10 hp at 460/480 V AC 60 Hz for 3 phases motors
15 hp at 575/600 V AC 60 Hz for 3 phases motors
[ui] rated insulation voltage Power circuit: 690 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-1
control circuit type AC at 50/60 Hz AC/DC electronic
DC AC/DC electronic
motor power kW 4 kW at 220...230 V AC 50 Hz
7.5 kW at 380...400 V AC 50 Hz
9 kW at 415 V AC 50 Hz
9 kW at 440 V AC 50 Hz
10 kW at 500 V AC 50 Hz
10 kW at 660...690 V AC 50 Hz
average impedance 2.5 mOhm - Ith 32 A 50 Hz for power circuit
Complementary
[ie] rated operational current 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
[ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
[ics] rated service breaking capacity 300 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current 40 A 40 °C - 10 min for power circuit
84 A 40 °C - 1 min for power circuit
145 A 40 °C - 10 s for power circuit
240 A 40 °C - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
[ith] conventional thermal current 32 A (at 60 °C) for power circuit
10 A (at 60 °C) for signalling circuit
Product certifications CCC
CSA
EAC
UL
KC
DNV-GL
LROS (Lloyds register of shipping)
UKCA
Handle front plate colour 77 mm
Product or component type Reversing contactor
tightening torque Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Auxiliary contact composition 1 NO + 1 NC
Connections - terminals Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid
Power circuit: screw clamp terminals 1 cable(s) 1.5…6 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1.5…6 mm²solid
Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm²solid
minimum switching current 5 mA for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
50 A gG at <= 690 V coordination type 1 for power circuit
35 A gG at <= 690 V coordination type 2 for power circuit
Auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
Control circuit voltage limits <= 0.1 Uc (-40…70 °C):drop-out AC/DC
0.85...1.1 Uc (-40…60 °C):operational AC/DC
1...1.1 Uc (60…70 °C):operational AC/DC
width (w) 90 mm
mechanical robustness Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
Shocks contactor open: 10 Gn for 11 ms
Shocks contactor closed: 15 Gn for 11 ms
Colour Grey (SE GREY 6)
Green (SE GREEN 2)
Flame retardance V1 conforming to UL 94
Heat dissipation 1.1 W at 50/60 Hz
Net weight 0.803 kg
Hold-in power consumption in va 1.6 VA (at 20 °C) 50/60 Hz
Hold-in power consumption in w 1.1 W at 20 °C
Mounting support Plate
Rail
power dissipation per pole 2.5 W AC-1
0.8 W AC-3
depth 86 mm
Inrush power in va 25 VA 50/60 Hz (at 20 °C)
inrush power in w 18 W at 20 °C
mechanical durability 15 Mcycles
electrical durability 2.2 Mcycles 15 A AC-3 at Ue <= 440 V
0.9 Mcycles 32 A AC-1 at Ue <= 440 V
Device presentation Preassembled with reversing power busbar
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
300 A at 440 V for power circuit conforming to IEC 60947
Pollution degree 3
Maximum operating rate 3600 cyc/h 60 °C
operating time 45...55 ms closing
20...90 ms opening
minimum switching voltage 17 V for signalling circuit
Power pole contact composition 3 NO
non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
coil technology Built-in bidirectional peak limiting
Poles description 3P
Utilisation category AC-1
AC-3
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Signalling circuit frequency 25...400 Hz
Environment
Ambient air temp for storage/transportation -60…80 °C
Climatic withstand conforming to IACS E10
conforming to IEC 60947-1 Annex Q category D
ip degree of protection IP20 front face conforming to IEC 60529
operating altitude 0...3000 m
ambient air temperature for operation -40…60 °C
60…70 °C with derating
overvoltage category III
standards EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
IEC 60335-1
fire resistance 850 °C conforming to IEC 60695-2-1
protective treatment TH conforming to IEC 60068-2-30
insulation resistance > 10 MOhm for signalling circuit
KKK ja hinna lisateave

Võta meiega ühendust

Professionaalne elektriseadmete müük Eestis, Lätis, Leedus ja Soomes. Sertifitseeritud madalpinge komponendid, kaitselülitid, kontaktorid ja tööstusautomaatika lahendused. Sama päeva hinnapakkumised ja kiire tarne Baltikumis ja Soomes

Baltelec
+372 5326 4976

E–R 9:00–17:00

info@baltelec.ee

Vastame 2 tunni jooksul

LC2D18KUE on toode kategooriast Tööstuslikud kontaktorid, mis on mõeldud ettevõtetele. BaltElec tegeleb hulgimüügi ja distributsiooniga Eestis, Lätis, Leedus ja Soomes.

  • Originaal Schneider Electric toode, sertifikaadid ja vastavusdokumendid saadaval.
  • Projektihind – küsi pakkumist suuremate koguste jaoks (võimalik, et sätestame MOQ).
  • Kiire tarne Baltikumis ning Soomes; koostöö tunnustatud kulleritega.
  • Tehniline tugi ja nõustamine valikul vastavalt Sinu rakendusele.

Hinnainfo: Küsi eripakkumist. Hind sõltub kogusest, tarne- ja maksetingimustest.

KKK tootele LC2D18KUE - Schneider Electric

Hiljuti vaadatud
LC2D18KUE - Schneider Electric
TeSys Deca pöördkontaktor 3P <= 440 V 18 A AC3 100...250 V AC/DC mähis.
200,89 € KM-ta
249,10 € KM-ga
Tellimisel