Main
Range
TeSys
[uc] control circuit voltage
48 V AC 50/60 Hz
job category
AC-1
AND-3
name of the device
LC1SKGC
switch application
Resistive load (AC-1)
Motor control (AC-3)
type of product or equipment
Mini-contactor
composition of the poles
2f
Product Name
TeSys SK
[ui] rated insulation voltage
Power circuit: 690 V conforming to BS 5424
Power circuit: 690 V conforming to IEC 60947
Power circuit: 690 V conforming to UL 508
Power circuit: 690 V conforming to VDE 0110 gr C
Power circuit: 690 V conforming to CSA C22.2 No 14
control circuit type
AC at 50/60 Hz
composition of the power pole contacts
2P
average impedance
4 mOhm - Ith 20 A 50 Hz for power circuit
Complementary
[ie] rated operational current
5 A at <= 400 V AC AC-3
20 A (at <50 °C) AC AC-1
[ue] rated operational voltage
Power circuit: 690 V AC 50/60 Hz
[ics] rated service breaking capacity
40 A at <= 400 V conforming to NF C 63-110
40 A at <= 400 V conforming to IEC 60947
[icw] rated short-time withstand current
40 A at <55 °C for power circuit
[ith] conventional thermal current
20 A at <55 °C) for power circuit
caliber of the fuse to be associated
20 A gI at <= 440 V for power circuit
Handle front plate colour
56 mm
tightening torque
Power circuit: 0.8 Nm - on connector - with pozidriv n°1 screwdriver
average fuel consumption when going
4.2VA 50/60Hz (at 20°C)
product weight
0,132 kg
connection mode
Connector 1 cable(s) 1.5...6 mm²rigid
Connector 2 cable(s) 1.5...4 mm²rigid
Connector 1 cable(s) 0.5...6 mm²flexible without cable end
Connector 2 cable(s) 0.35... 2.5 mm²flexible without cable end
Connector 1 cable(s) 0.35...6 mm²flexible with cable end
Connector 2 cable(s) 0.35...1.5 mm²flexible with cable end
control circuit voltage range
Operational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C)
Level loss: 0.2...0.75 Uc at 50/60 Hz (at <55 °C)
mechanical endurance
10 Mcycles
width (w)
27 mm
rated rms inrush power
50 A AC conforming to NF C 63-110
50 A AC conforming to IEC 60947
depth
55,5 mm
mounting bracket
Rail
calling power goes
16VA 50/60Hz (at 20°C)
operating time
6…8 ms désexcitation bobine + ouverture "F"
7…14 ms excitation bobine + fermeture "F"
max command speed
1200 cyc/h
Environment
ip degree of protection
IP2x conforming to VDE 0106
operating altitude
2000 m without derating
product certificates
cULus
operating ambient temperature
-20…50 °C
standards
BS 5424
NF C 63-110
VDE 0660
CEI 60947
thermal dissipation
1.4W at 50/60Hz
storage room temperature
-50…70 °C
protective treatment
TC conforming to IEC 60068
TC conforming to DIN 50015