Main
product range
TeSys F
Range
TeSys
[uc] control circuit voltage
415 V AC 40...400 Hz
job category
AC-1
AC-4
AC-3
name of the device
LC1F
switch application
Resistive load (AC-1)
Motor control (AC-3)
type of product or equipment
contactor
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 gr C
control circuit type
AC at 40...400 Hz
composition of the power pole contacts
3F
motor power kW
132 kW at 380...400 V AC 50/60 Hz (AC-3)
140 kW at 415 V AC 50/60 Hz (AC-3)
140 kW at 440 V AC 50/60 Hz (AC-3)
160 kW at 500 V AC 50/60 Hz (AC-3)
160 kW at 660...690 V AC 50/60 Hz (AC-3)
147 kW at 1000 V AC 50/60 Hz (AC-3)
75 kW à 220...230 V AC 50/60 Hz (AC-3)
51 kW à 400 V AC 50/60 Hz (AC-4)
average impedance
0,3 mOhm - Ith 350 A 50 Hz
Complementary
[ie] rated operational current
350 A (at <40°C) at <= 440 V AC AC-1
265 A (at <55°C) at <= 440 V AC AC-3
[ue] rated operational voltage
<= 1000 V AC-1
<= 690 V AC-3
<= 690 V AC-4
<= 460 V CC
compatibility code
LC1F
[ics] rated service breaking capacity
2120 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
2200 A at <40°C - 10 s
1230 A at <40°C - 30 s
950 A at <40°C - 1 min
620 A at <40°C - 3 min
480 A at <40°C - 10 min
[ith] conventional thermal current
350A at <40°C)
caliber of the fuse to be associated
315 A aM at <= 440 V
400 A gG at <= 440 V
Handle front plate colour
203 mm
tightening torque
Remote control: 1.2 Nm
Power circuit: 35 Nm
[uimp] rated impulse withstand voltage
8 kV
average fuel consumption when going
10 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
mechanical life
10 Mcycles
product weight
7,44 kg
average consumption on call going
650 VA, 40...400 Hz cos phi 0.9 (at 20°C)
connection mode
Remote control: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 1 cable( s) 1…4 mm²flexible with cable end
Remote control: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Remote control: screw clamp terminals 1 cable(s) 1…4 mm²rigid without end cable
length Remote control: screw clamp terminals 2 cable(s) 1...4 mm² rigid without cable end
Power circuit: bar 2 cable(s) - busbar section: 32 x 4 mm
Power circuit: ring terminals 1 cable(s) 240 mm²
Power circuit: connector 1 cable(s) 240 mm²
Power circuit: connection by bolting
control circuit voltage range
Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C)
Level drop: 0.15...0.2 Uc 40...400 Hz (at 55 °C)
width (w)
201,5 mm
depth
213 mm
mounting bracket
Platinum
operating time
40…65 ms closing
100…170 ms opening
power loss per pole
37 W AC-1
21 W AC-3
max command speed
2400 cycles/h at <55°C
Poles description
3P
Environment
ip degree of protection
IP20 front face with protectors conforming to IEC 60529
IP20 front face with protectors conforming to VDE 0106
operating altitude
3000 m without current reduction
product certificates
RINA
RMRoS
LROS (Lloyds register of shipping)
DNV
ABS
CCC
CB
UL
BV
UKCA
ambient air temperature for operation
-40…70 °C
operating ambient temperature
-5…55 °C
overvoltage category
III
standards
EN 60947-1
JIS C8201-4-1
CEI 60947-4-1
EN 60947-4-1
CEI 60947-1
thermal dissipation
8W
storage room temperature
-60…80 °C
protective treatment
TH