Main
product range
TeSys F
Range
TeSys
[uc] control circuit voltage
115 V AC 40...400 Hz
job category
AC-1
AC-4
AC-3
name of the device
LC1F
switch application
Motor control (AC-3)
Resistive load (AC-1)
type of product or equipment
contactor
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 gr C
control circuit type
AC at 40...400 Hz
composition of the power pole contacts
3F
motor power kW
132 kW at 380...400 V AC 50/60 Hz (AC-3)
140 kW at 415 V AC 50/60 Hz (AC-3)
140 kW at 440 V AC 50/60 Hz (AC-3)
160 kW at 500 V AC 50/60 Hz (AC-3)
160 kW at 660...690 V AC 50/60 Hz (AC-3)
147 kW at 1000 V AC 50/60 Hz (AC-3)
75 kW à 220...230 V AC 50/60 Hz (AC-3)
51 kW à 400 V AC 50/60 Hz (AC-4)
average impedance
0,3 mOhm - Ith 350 A 50 Hz
Complementary
[ie] rated operational current
350 A (at <40°C) at <= 440 V AC AC-1
265 A (at <55°C) at <= 440 V AC AC-3
[ue] rated operational voltage
<= 1000 V AC-1
<= 690 V AC-3
<= 690 V AC-4
<= 460 V CC
compatibility code
LC1F
[ics] rated service breaking capacity
2120 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
2200 A at <40°C - 10 s
1230 A at <40°C - 30 s
950 A at <40°C - 1 min
620 A at <40°C - 3 min
480 A at <40°C - 10 min
[ith] conventional thermal current
350A at <40°C)
caliber of the fuse to be associated
315 A aM at <= 440 V
400 A gG at <= 440 V
Handle front plate colour
203 mm
tightening torque
Remote control: 1.2 Nm
Power circuit: 35 Nm
[uimp] rated impulse withstand voltage
8 kV
average fuel consumption when going
10 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
mechanical life
10 Mcycles
product weight
7,44 kg
average consumption on call going
650 VA, 40...400 Hz cos phi 0.9 (at 20°C)
connection mode
Remote control: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 1 cable( s) 1…4 mm²flexible with cable end
Remote control: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Remote control: screw clamp terminals 1 cable(s) 1…4 mm²rigid without end cable
length Remote control: screw clamp terminals 2 cable(s) 1...4 mm² rigid without cable end
Power circuit: bar 2 cable(s) - busbar section: 32 x 4 mm
Power circuit: ring terminals 1 cable(s) 240 mm²
Power circuit: connector 1 cable(s) 240 mm²
Power circuit: connection by bolting
control circuit voltage range
Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C)
Level drop: 0.15...0.2 Uc 40...400 Hz (at 55 °C)
width (w)
201,5 mm
depth
213 mm
engine power range
55…100 kW at 200…240 V 3 phases
110…220 kW at 480…500 V 3 phases
110…220 kW at 380…440 V 3 phases
mounting bracket
Platinum
operating time
40…65 ms closing
100…170 ms opening
power loss per pole
37 W AC-1
21 W AC-3
max command speed
2400 cycles/h at <55°C
contactor coil voltage
115 V CA standard
motor starter type
Direct line contactor
Poles description
3P
Environment
ip degree of protection
IP20 front face with protectors conforming to IEC 60529
IP20 front face with protectors conforming to VDE 0106
operating altitude
3000 m without current reduction
product certificates
LROS (Lloyds register of shipping)
ABS
DNV
BV
RINA
CSA
CB
UL
RMRoS
UKCA
ambient air temperature for operation
-40…70 °C
overvoltage category
III
standards
EN 60947-4-1
CEI 60947-4-1
JIS C8201-4-1
CEI 60947-1
EN 60947-1
thermal dissipation
8W
operating ambient air temperature
-5…55 °C
storage room temperature
-60…80 °C
protective treatment
TH