Main
product range
TeSys F
Range
TeSys
[uc] control circuit voltage
400 V AC 40...400 Hz
job category
AC-3
AC-4
AC-1
name of the device
LC1F
switch application
Resistive load (AC-1)
Motor control (AC-3)
type of product or equipment
contactor
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 gr C
control circuit type
AC at 40...400 Hz
composition of the power pole contacts
3F
motor power kW
110 kW at 380...400 V AC 50/60 Hz (AC-3)
110 kW at 415 V AC 50/60 Hz (AC-3)
110 kW at 440 V CA 50/60 Hz (AC-3)
129 kW at 500 V AC 50/60 Hz (AC-3)
129 kW at 660...690 V AC 50/60 Hz (AC-3)
63 kW at 220...230 V CA 50/60 Hz (AC- 3)
40 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0,32 mOhm - Ith 315 A 50 Hz
Complementary
[ie] rated operational current
315 A (at <40°C) at <= 440 V AC-1
225 A (at <55°C) at <= 440 V AC-3
[ue] rated operational voltage
<= 460 V CC
<= 690 V CA 50/60 Hz
compatibility code
LC1F
[ics] rated service breaking capacity
1800 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
1800 A at <40°C - 10 s
1000 A at <40°C - 30 s
850 A at <40°C - 1 min
560 A at <40°C - 3 min
440 A at <40°C - 10 min
[ith] conventional thermal current
315A at <40°C)
caliber of the fuse to be associated
315 A gG at <= 440 V
250 A aM at <= 440 V
Handle front plate colour
197 mm
tightening torque
Remote control: 1.2 Nm
Power circuit: 35 Nm
[uimp] rated impulse withstand voltage
8 kV
average fuel consumption when going
9.9 VA, 40...400 Hz cos phi 0.9 (at 20°C)
mechanical life
10 Mcycles
product weight
4,75 kg
average consumption on call going
1070 VA, 40...400 Hz cos phi 0.9 (at 20°C)
connection mode
Remote control: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 1 cable( s) 1…4 mm²flexible with cable end
Remote control: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Remote control: screw clamp terminals 1 cable(s) 1…4 mm²rigid without end cable
length Remote control: screw clamp terminals 2 cable(s) 1...4 mm² rigid without cable end
Power circuit: bar 2 cable(s) - busbar section: 32 x 4 mm
Power circuit: ring terminals 1 cable(s) 185 mm²
Power circuit: connector 1 cable(s) 185 mm²
Power circuit: connection by bolting
control circuit voltage range
Operational: 0.85…1.1 Uc 40...400 Hz (at 55 °C)
Level loss: 0.2...0.55 Uc 40...400 Hz (at 55 °C)
width (w)
168,5 mm
depth
181 mm
engine power range
55…100 kW at 200…240 V 3 phases
110…220 kW at 480…500 V 3 phases
110…220 kW at 380…440 V 3 phases
mounting bracket
Platinum
operating time
35 ms closing (at Uc)
130 ms opening (at Uc)
power loss per pole
32 W AC-1
16 W AC-3
max command speed
2400 cycles/h at <55°C
contactor coil voltage
400 V CA standard
motor starter type
Direct line contactor
Poles description
3P
Environment
ip degree of protection
IP20 front face with protectors conforming to IEC 60529
IP20 front face with protectors conforming to VDE 0106
operating altitude
3000 m without current reduction
product certificates
ABS
LROS (Lloyds register of shipping)
RINA
DNV
BV
CSA
UL
RMRoS
CB
UKCA
ambient air temperature for operation
-40…70 °C
operating ambient temperature
-5…55 °C
overvoltage category
III
standards
CEI 60947-4-1
JIS C8201-4-1
EN 60947-4-1
EN 60947-1
CEI 60947-1
thermal dissipation
8…9.8W
storage room temperature
-60…80 °C
protective treatment
TH