Main
Range
TeSys
[uc] control circuit voltage
24...575 V AC 40...400 Hz with coil LX1/LX9
24...460 V DC with coil LX4
100...250 V AC 50/60 Hz with coil LXE
100...380 V DC with LXE coil
job category
AC-1
name of the device
LC1F
switch application
Resistive load (AC-1)
type of product or equipment
contactor
Product Name
TeSys F
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 gr C
composition of the power pole contacts
4F
average impedance
0,35 mOhm - Ith 250 A 50 Hz
Complementary
[ie] rated operational current
250 A (at <40°C) at <= 440 V AC-1
[ue] rated operational voltage
<= 690 V CA 50/60 Hz
<= 460 V CC
compatibility code
LC1F
[ics] rated service breaking capacity
1200 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
1200 A at <40°C - 10 s
700 A at <40°C - 30 s
600 A at <40°C - 1 min
450 A at <40°C - 3 min
350 A at <40°C - 10 min
[ith] conventional thermal current
250A at <40°C)
caliber of the fuse to be associated
250 A gG at <= 440 V
Handle front plate colour
170 mm
tightening torque
Power circuit: 18 Nm
Remote control: 1.2 Nm
Remote control: 0.6 Nm
[uimp] rated impulse withstand voltage
8 kV
average fuel consumption when going
6.6…8.1 VA
3.94…4.83 VA
4.5…7.0 VA
2.5…4.0 VA
product weight
3,83 kg
average consumption on call going
690…855 VA, 40...400 Hz cos phi 0.9 (at 20 °C) with LX1/LX9 coil
543…665 VA (at 20 °C) with LX4 coil
280…310 VA, 50/60 Hz cos phi 0.5 (at 20 °C) with LXE coil
270…320 VA (at 20 °C) with LXE coil
connection mode
Power circuit: ring terminals 1 cable(s) 120 mm² - busbar section: 25 x 3 mm
Power circuit: connector 1 cable(s) 120 mm²
Power circuit: bar 2 cable(s)
Power circuit : connection by bolting
Remote control: screw clamp terminals 1 cable(s) 1...4 mm² flexible without cable end
Remote control: screw clamp terminals 2 cable(s) 1...4 mm² flexible with cable end
Remote control: screw terminal blocks clamp 1 cable(s) 1...4 mm²flexible with cable end
Remote control: screw clamp terminals 2 cable(s) 1...2.5 mm²rigid without cable end
Remote control: screw clamp terminals 1 cable(s) 1... 4 mm²
Remote control: screw clamp terminals 2 cable(s) 1...4 mm²
Remote control: screw clamp terminals 1.0 cable(s) 0.2...2.5 mm²flexible without cable end
Remote control: screw clamp terminals 1.0 cable(s) 0.25...2.5 mm²flexible with cable end cable
cross-section Remote control: screw clamp terminals 1.0 cable(s) 0.2...2.5 mm²rigid without cable end
control circuit voltage range
Operational: 0.85…1.1 Uc AC 40...400 Hz
Level loss: 0.2...0.55 Uc AC 40...400 Hz
Operational: 0.85…1.1 Uc DC
Loss level loss: 0.15...0.2 Uc DC
Operational: 85...275 V AC 50/60 Hz
Level loss: 0...60 V AC 50/60 Hz
Operational: 85...418 V DC
Loss level: 0...45 V DC
mechanical endurance
10 Mcycles
width (w)
200,5 mm
mechanical robustness
Open contactor vibrations: 2 Gn, 5 to 300 Hz
Closed contactor vibrations: 6 Gn, 5 to 300 Hz
Open contactor shocks: 9 Gn for 1/2 sine wave (11 ms)
Closed contactor shocks: 15 Gn for 1/2 sine wave( 11ms)
rated rms inrush power
1500 A conforming to IEC 60947-4-1
depth
171 mm
mounting bracket
Platinum
operating time
35 ms closing for with LX1/LX9 coil
130 ms opening for with LX1/LX9 coil
30…40 ms closing for with LX4 coil
30…50 ms opening for with LX4 coil
40…80 ms closing for with LXE coil
6...54 ms opening for with LXE coil
power loss per pole
22 W AC-1
max command speed
2400 cycles/h at <55°C
Poles description
4P
Environment
ip degree of protection
IP2x front face with guards conforming to IEC 60529
IP2x front face with guards conforming to VDE 0106
operating altitude
3000 m without current reduction
product certificates
ABS
CSA
BV
CB
RINA
RMRoS
DNV
LROS (Lloyds register of shipping)
UL
UKCA
ambient air temperature for operation
60…70 °C at Uc
overvoltage category
III
standards
EN 60947-1
JIS C8201-4-1
CEI 60947-1
CEI 60947-4-1
EN 60947-4-1
thermal dissipation
5,9…7,2 W
2,2…2,5 W
operating ambient air temperature
-40…60 °C
storage room temperature
-60…80 °C
protective treatment
TH