Default
Seeria
TeSyS Deca kontaktorid
Main
product range
TeSys D
TeSys Deca
Range
TeSys
TeSys Deca
[uc] control circuit voltage
230 V AC 50/60Hz
job category
AC-1
name of the device
LC1D
switch application
Resistive load (AC-1)
type of product or equipment
contactor
[ui] rated insulation voltage
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signaling circuit: 690 V conforming to IEC 60947-1
Signaling circuit: 600 V CSA certified
Signaling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1
control circuit type
AC at 50/60 Hz
composition of the power pole contacts
4F
average impedance
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Complementary
[ie] rated operational current
25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC
compatibility code
LC1D
[ics] rated service breaking capacity
250 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
30 A at <40°C - 10 min for
61 A power circuit at <40°C - 1 min for
105 A power circuit at <40°C - 10 s for
210 A power circuit at <40°C - 1s for
100 A power circuit - 1s for
120 A signaling circuit - 500 ms for
140 A signaling circuit - 100 ms for signaling circuit
[ith] conventional thermal current
10 A at <60°C) for signaling circuit
25 A at <60°C) for power circuit
caliber of the fuse to be associated
10 A gG for signaling circuit conforming to IEC 60947-5-1
40 A gG at <= 690 V type 1 coordination for power circuit
25 A gG at <= 690 V type 2 coordination for power circuit
Handle front plate colour
85 mm
tightening torque
Remote control: 1.7 Nm - on screw-clamp terminals - with flat screwdriver Ø 6 mm
Remote control: 1.7 Nm - on screw-clamp terminals - with Phillips No. 2 screwdriver
Power circuit: 1.7 Nm - on screw-clamp terminals - with flat screwdriver Ø 6 mm
Power circuit: 1.7 Nm - on screw-clamp terminals - with Phillips No. 2 screwdriver
Remote control: 1.7 Nm - on screw-clamp terminals - with n°2 pozidriv screwdriver Power
circuit: 1.7 Nm - on screw clamp terminals - with n°2 pozidriv screwdriver
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
auxiliary contacts
1 "O" + 1 "F"
average fuel consumption when going
7.5 VA 60 Hz cos phi 0.3 (at 20°C)
7 VA 50 Hz cos phi 0.3 (at 20°C)
minimum switching current
5 mA for signaling circuit
product weight
0,365 kg
type of auxiliary contacts
mechanically linked type 1 NC + 1 NO conforming to IEC 60947-5-1
1 NC mirror contact type conforming to IEC 60947-4-1
contact compatibility
M6
electrical life
0.8 Mcycles 25 A AC-1 at Ue <= 440 V
connection mode
Remote control: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Remote control: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Remote control: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Remote control: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Remote control: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Remote control: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp
terminals screw clamp 2 1...4 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid without cable end
control circuit voltage range
0.3...0.6 Uc -40...70 °C dropout AC 50/60 Hz
0.8...1.1 Uc -40...60 °C operational AC 50 Hz
0.85...1.1 Uc -40 …60 °C operational AC 60 Hz
1...1.1 Uc 60…70 °C operational AC 50/60 Hz
mechanical endurance
15 Mcycles
width (w)
45 mm
mechanical robustness
Open contactor vibrations (2 Gn, 5 to 300 Hz)
Closed contactor vibrations (4 Gn, 5 to 300 Hz)
Closed contactor shocks (15 Gn for 11 ms)
Open contactor shocks (10 Gn for 11 ms)
Flame retardance
V1 conforming to UL 94
rated rms inrush power
140 A AC for signaling circuit conforming to IEC 60947-5-1
250 A DC for signaling circuit conforming to IEC 60947-5-1
250 A at 440 V for power circuit conforming to IEC 60947
depth
92 mm
mounting bracket
Platine
Rail
frequency
With
signaling circuit frequency
25 to 400 Hz
calling power goes
70 VA 60 Hz cos phi 0.75 (at 20°C)
70 VA 50 Hz cos phi 0.75 (at 20°C)
operating time
4…19 ms opening
12…22 ms closing
power loss per pole
1,56 W AC-1
security reliability level
B10d = 1369863 contactor cycle with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 contactor cycle with mechanical load conforming to EN/ISO 13849-1
max command speed
3600 cycles/h at <60°C
minimum switching voltage
17 V for signaling circuit
non-overlap time
1.5 ms on de-
energization between NC and NO contact 1.5 ms on excitation between NC and NO contact
coil technology
Without integrated interference suppression module
Poles description
4P
Environment
degree of pollution
3
ip degree of protection
IP20 front face conforming to IEC 60529
operating altitude
0...3000 m
product certificates
UL
BV
CCC
LROS (Lloyds register of shipping)
DNV
CSA
RINA
GOST
GL
ambient air temperature for operation
-40…60 °C
60…70 °C with current reduction
overvoltage category
III
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
CEI 60947-4-1
CEI 60947-5-1
UL 508
CEI 60335-1
fire resistance
850 °C conforming to IEC 60695-2-1
thermal dissipation
2…3 W at 50/60 Hz
climatic resistance
conforming to IACS E10 exposure to damp heat
conforming to IEC 60947-1 Annex Q category D exposure to damp heat
protective treatment
TH conforming to IEC 60068-2-30
insulation resistance
> 10 MΩ for signaling circuit