Default
Seeria
TeSyS Deca kontaktorid
Main
product range
TeSys D
Range
TeSys
[uc] control circuit voltage
230 V AC 50/60Hz
job category
AC-1
name of the device
LC1D
switch application
Resistive load (AC-1)
type of product or equipment
contactor
[ui] rated insulation voltage
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1
control circuit type
AC at 50/60 Hz
composition of the power pole contacts
2F+2O
average impedance
1.5 mOhm - Ith 60 A 50 Hz for power circuit
Complementary
[ie] rated operational current
60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[ue] rated operational voltage
Power circuit: <= 1000 V AC 25...400 Hz
compatibility code
LC1D
[ics] rated service breaking capacity
800 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
320 A at <40°C - 10 s for power circuit
720 A at <40°C - 1s for power circuit
72 A at <40°C - 10 min for power circuit
165 A at <40°C - 1 min for power circuit
[ith] conventional thermal current
60 A at <60 °C) for power circuit
caliber of the fuse to be associated
80 A gG at <= 690 V type 1 coordination for power circuit
80 A gG at <= 690 V type 2 coordination for power circuit
Handle front plate colour
127 mm
tightening torque
Remote control: 1.7 Nm - on screw-clamp terminals - with flat screwdriver Ø 6 mm
Remote control: 1.7 Nm - on screw-clamp terminals - with Phillips no. 2 screwdriver
Power circuit: 8 Nm - on terminal blocks screw clamp - cable 25...35 mm² hexagonal screw head 4 mm
Power circuit: 5 Nm - on screw clamp terminals - cable 1...25 mm² hexagonal screw head 4 mm
Remote control: 1.7 Nm - on screw terminal blocks -caliper - with pozidriv n°2 screwdriver
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
average fuel consumption when going
13 VA 60 Hz cos phi 0.3 (at 20°C)
15 VA 50 Hz cos phi 0.3 (at 20°C)
product weight
1,44 kg
contact compatibility
M1
electrical life
1.4 Mcycles 60 A AC-1 at Ue <= 440 V
connection mode
Remote control: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Remote control: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Remote control: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Remote control: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Remote control: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Remote control: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 2.5...16 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible with cable
end power: screw clamp terminals 1 2.5…25 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: solid without cable end
control circuit voltage range
0.3...0.6 Uc -40...55 °C dropout AC 50/60 Hz
0.8...1.1 Uc -40...55 °C operational AC 50 Hz
0.85...1.1 Uc -40 …55 °C operational AC 60 Hz
mechanical endurance
6 Mcycles
width (w)
85 mm
mechanical robustness
Contactor open shocks (8 Gn for 11 ms)
Contactor closed shocks (10 Gn for 11 ms)
Contactor open vibrations (2 Gn, 5 to 300 Hz)
Contactor closed vibrations (4 Gn, 5 to 300 Hz)
Flame retardance
V1 conforming to UL 94
rated rms inrush power
800 A at 440 V for power circuit conforming to IEC 60947
depth
125 mm
mounting bracket
Platine
Rail
frequency
Without
calling power goes
245 VA 60 Hz cos phi 0.75 (at 20°C)
245 VA 50 Hz cos phi 0.75 (at 20°C)
operating time
4…19 ms opening
12…26 ms closing
power loss per pole
5,4 W AC-1
security reliability level
B10d = 1369863 contactor cycle with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 contactor cycle with mechanical load conforming to EN/ISO 13849-1
max command speed
3600 cycles/h at <60°C
coil technology
Without integrated interference suppression module
Poles description
4P
Environment
degree of pollution
3
ip degree of protection
IP20 front face conforming to IEC 60529
operating altitude
0...3000 m
product certificates
UL
CSA
CCC
EAC
UKCA
CB
EU-RO-MR by DNV-GL
ambient air temperature for operation
-40…60 °C
60…70 °C with current reduction
overvoltage category
III
standards
EN 60947-4-1
EN 60947-5-1
CEI 60947-4-1
CEI 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No. 60947-5-1
GB/T 14048.4
fire resistance
850 °C conforming to IEC 60695-2-1
thermal dissipation
4…5 W at 50/60 Hz
climatic resistance
conform to IACS E10 exposure to damp heat
protective treatment
TH conforming to IEC 60068-2-30