Default
Seeria
TeSyS Deca kontaktorid
Main
product range
TeSys Deca
[uc] control circuit voltage
24 V CC
job category
AC-1
name of the device
LC1D
switch application
Resistive load (AC-1)
type of product or equipment
contactor
[ui] rated insulation voltage
Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signaling circuit: 690 V conforming to IEC 60947-1
Signaling circuit: 600 V CSA Certified
Signaling Circuit: 600V UL Certified
control circuit type
CC standard
composition of the power pole contacts
2F+2O
average impedance
2 mOhm - Ith 40 A 50 Hz for power circuit
Complementary
[ie] rated operational current
40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
compatibility code
LC1D
[ics] rated service breaking capacity
450 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
240 A at <40°C - 10 s for power circuit
380 A at <40°C - 1s for power circuit
50 A at <40°C - 10 min for power circuit
120 A at <40°C - 1 min for power circuit
100 A - 1s for signaling circuit
120 A - 500 ms for signaling circuit
140 A - 100 ms for signaling circuit
[ith] conventional thermal current
10 A at <60°C) for signaling circuit
40 A at <60°C) for power circuit
caliber of the fuse to be associated
10 A gG for signaling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V type 1 coordination for power circuit
40 A gG at <= 690 V type 2 coordination for power circuit
average consumption on hold in w
5.4W at 20°C
Handle front plate colour
91 mm
tightening torque
Remote control: 1.7 Nm - on screw-clamp terminals - with Ø 6 mm flat screwdriver
Remote control: 1.7 Nm - on screw-clamp terminals - with Phillips No. 2 screwdriver
Power circuit: 1.8 Nm - on connector - with Ø 6 mm flat screwdriver
Power circuit: 1.8 Nm - on connector - with no. 2 Phillips screwdriver
Remote control: 1.7 Nm - on screw clamp terminals - with no. 2 pozidriv screwdriver Power
circuit power: 2.5 Nm - on screw clamp terminals - with pozidriv n°2 screwdriver
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
auxiliary contacts
1 "O" + 1 "F"
minimum switching current
5 mA for signaling circuit
product weight
0,585 kg
type of auxiliary contacts
mechanically linked type 1 NC + 1 NO conforming to IEC 60947-5-1
1 NC mirror contact type conforming to IEC 60947-4-1
contact compatibility
M7
electrical life
1.4 Mcycles 40 A AC-1 at Ue <= 440 V
connection mode
Remote control: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Remote control: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Remote control: screw clamp terminals 1 1… 4 mm² - cable stiffness: flexible with cable end
Remote control: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end
Remote control: screw clamp terminals 1 1...4 mm² - cable stiffness: solid without cable end
Remote control: screw clamp terminals 2 1…4 mm² - cable stiffness: rigid without cable end
Power circuit: connector 1 2.5…10 mm² - cable stiffness: flexible without cable end
Power circuit: connector 2 2, 5...10 mm² - cable stiffness: flexible without cable end
Power circuit: connector 1 2.5…10 mm² - cable stiffness: flexible with ferrule
Power circuit: connector 2 2.5…10 mm² - cable stiffness: flexible with ferrule
Power circuit: connector 1 2.5…10 mm² 16 mm² - cable stiffness: solid without cable end
Power circuit: connector 2 2.5...16 mm² - cable stiffness: solid without cable end
control circuit voltage range
0.1...0.25 Uc -40...60°C DC level loss
0.7...1.25 Uc -40...60°C DC operational
mechanical endurance
30 Mcycles
width (w)
45 mm
mechanical robustness
Contactor open vibrations (2 Gn, 5 to 300 Hz)
Contactor closed vibrations (4 Gn, 5 to 300 Hz)
Contactor closed shocks (15 Gn for 11 ms)
Contactor open shocks (8 Gn for 11 ms)
Flame retardance
V1 conforming to UL 94
time constant
28 ms
rated rms inrush power
140 A AC for signaling circuit conforming to IEC 60947-5-1
250 A DC for signaling circuit conforming to IEC 60947-5-1
450 A at 440 V for power circuit conforming to IEC 60947
depth
107 mm
mounting bracket
Platine
Rail
frequency
With
maximum inrush power in w
5.4W (at 20°C)
signaling circuit frequency
25 to 400 Hz
operating time
53.55…72.45 ms closing
16…24 ms opening
power loss per pole
3,2 W AC-1
security reliability level
B10d = 1369863 contactor cycle with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 contactor cycle with mechanical load conforming to EN/ISO 13849-1
max command speed
3600 cycles/h at <60°C
minimum switching voltage
17 V for signaling circuit
non-overlap time
1.5 ms on de-
energization between NC and NO contact 1.5 ms on excitation between NC and NO contact
coil technology
Built-in bi-directional peak limit diode suppressor
Poles description
4P
Environment
degree of pollution
3
ip degree of protection
IP20 front face conforming to IEC 60529
operating altitude
0...3000 m
product certificates
UL
CSA
CCC
EAC
UKCA
CB
EU-RO-MR by DNV-GL
ambient air temperature for operation
-40…60 °C
60…70 °C with current reduction
overvoltage category
III
standards
EN 60947-4-1
EN 60947-5-1
CEI 60947-4-1
CEI 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No. 60947-5-1
GB/T 14048.4
fire resistance
850 °C conforming to IEC 60695-2-1
climatic resistance
conforming to IACS E10 exposure to damp heat
conforming to IEC 60947-1 Annex Q category D exposure to damp heat
protective treatment
TH conforming to IEC 60068-2-30
insulation resistance
> 10 MΩ for signaling circuit