Default
Seeria
TeSyS Deca kontaktorid
Main
Range
TeSys
TeSys Deca
name of the device
LADN
type of product or equipment
Auxiliary contact block
composition of the poles
4 "O"
Product Name
TeSys D
TeSys Deca
[ui] rated insulation voltage
690 V conforming to IEC 60947-5-1
600 V conforming to UL
600 V conforming to CSA
Complementary
[ie] rated operational current
6 A at 120 V AC-15
1.04 A at 690 V AC-15
0.55 A at 125 V DC-13
0.1 A at 600 V DC-13
[ue] rated operational voltage
690 V AC 25...400 Hz
range compatibility
TeSys D LC1D
TeSys D CAD
TeSys F LC1F
TeSys F CR1F
TeSys Deca CAD
TeSys Deca LC1D
[ith] conventional thermal current
10A at <60°C)
allowable temporary current
100 A 1s
120 A 500 ms
140 A 100 ms
Handle front plate colour
48 mm
tightening torque
1.7 Nm - with flat screwdriver Ø 6 mm
1.7 Nm - with Phillips screwdriver no. 2
1.7 Nm - with pozidriv screwdriver no. 2
mounting location
Façade
minimum switching current
5 mA
product weight
0,05 kg
connection mode
Screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Screw clamp terminals
1 cable(s) 1...4 mm²flexible without cable end Screw clamp terminals
2 cable(s) 1...2, 5 mm²flexible with cable end Screw clamp terminals
2 cable(s) 1...4 mm²flexible without cable end Screw clamp terminals
1 cable(s) 1...4 mm²rigid without cable end Screw clamp terminals
2 cable( s) 1...4 mm² rigid without cable end
contact operation
Snap
mechanical endurance
30 Mcycles
width (w)
44 mm
Colour
Dark gray
rated rms inrush power
140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
depth
42 mm
minimum switching voltage
17V
kind of protection
Fusible gG 10 A
non-overlap time
1.5 ms on de-
energization non-overlapping between NC and NO contact 1.5 ms on excitation non-overlapping between NC and NO contact
Environment
environment characteristic
normal environment
ip degree of protection
IP20 conforming to IEC 60529
operating altitude
3000 m
product certificates
CB
UL
CSA
CCC
EAC
UKCA
operating ambient temperature
-5…60 °C
standards
EN/CEI 60947-5-1
UL 60947-5-1
CSA C22.2 No 60947-5-1
GB/T 14048.5
storage room temperature
-60…80 °C
protective treatment
TH conforming to IEC 60068
insulation resistance
> 10 MΩ