Default
Seeria
Modicon M221
Main
product range
Modicon TM3
type of product or equipment
Digital output module
digital output logic
Positive Logic (PNP)
name of sorties tor
16
Complementary
maximum filament lamp load
<3 W for transistor output
maximum distance between devices
Unshielded cable: <30 m for transistor output
power consumption
5 mA at 5 V DC at via bus connector (in off state)
0 mA at 24 V DC at via bus connector (in off state)
15 mA at 5 V DC at via bus connector (when ON)
20 mA at 24 V DC to via bus connector (when ON)
range compatibility
Modicon M241
Modicon M251
Modicon M221
Modicon M262
response time
450 µs (on)
450 µs (off)
Handle front plate colour
90 mm
maximum leakage current
0.1 mA for transistor output
maximum voltage drop
<0.4V
product weight
0,11 kg
logic output current
500 mA for transistor output
marking
THIS
tor i/o name
16
width (w)
27,4 mm
isolation
Not isolated between outputs
Between output and AC internal logic
Local signalling
for output status 1 LED per channel (green)
depth
84,6 mm
mounting bracket
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
resistance to shock waves
1 kV I/O common mode conforming to EN/IEC 61000-4-5 DC
electrical connection
10 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for outputs
logic output voltage
24V CC pour sortie transistor
logic output type
Transistor
Environment
degree of pollution
2
ip degree of protection
IP20 with protective cover in place
operating altitude
0...2000 m
product certificates
cULus
C-Tick
operating ambient temperature
-10…35 °C vertical installation
-10…55 °C horizontal installation
standards
EN/CEI 61010-2-201
EN/CEI 61131-2
storage height
0…3000 m
relative humidity
10…95%, non-condensing (operating)
10…95%, non-condensing (memory)
storage room temperature
-25…70 °C
mechanical shock resistance
15 gn pour 11 ms
electromagnetic emission
Radiated emissions - test level: 40 dBμV/m QP class A (10 m) at 30...230 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A (10 m) at 230 …1000 MHz conforming to EN/IEC 55011
vibration resistance
3.5 mm at 5…8.4 Hz on DIN rail
3 gn at 8.4…150 Hz on DIN rail
3.5 mm at 5…8.4 Hz on panel
3 gn at 8.4…150 Hz on panel
Conducted disturbance resist, induced by radio frequency fields
10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 V detection frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to approvals marine (LR, ABS, DNV, GL)
resistance to radiated electromagnetic fields
10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
resistance to electrostatic discharges
8 kV air conforming to EN/IEC 61000-4-2
4 kV contact conforming to EN/IEC 61000-4-2
resistance to fast transients
1 kV for I/O conforming to EN/IEC 61000-4-4
resistance to magnetic fields
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8