Main
product range
Interface for digital signals
[in] maximum rated operational current
12 mA
type of product or equipment
Narrow static output module
dimension of the step in width
9,5 mm
[ui] rated insulation voltage
250 V conforming to VDE 0110 gr C
300 V conforming to IEC 60947-1
reverse polarity protection
Remote control: internal
Output circuit: internal
voltage and type of control circuit
24V
control circuit type
CC
sale by indivisible quantity
5
Complementary
[ie] rated operational current
1.5 A DC-12 vertical position, separate product conforming to IEC 60947-5-1
1.5 A DC-13 vertical position, separate product conforming to IEC 60947-5-1
0.6 A DC-14 position vertical, separate product conforming to IEC 60947-5-1
0.6 A DC-14 vertical position, product in contact conforming to IEC 60947-5-1
0.9 A DC-12 vertical position, product in contact conform to IEC 60947-5-1
0.9 A DC-13 vertical position, product in contact conforming to IEC 60947-5-1
[ith] conventional thermal current
2 A at 40 °C
contact description
1 "O"
facility category
II conforming to IEC 60947-1
response time
<= 0.05 ms from phase 0 to phase 1
<= 0.6 ms from phase 1 to phase 0
maximum residual current
1 mA
current state 0 guaranteed
2 mA
minimum switching current
1 mA
product weight
0,34 kg
current state 1 guaranteed
7.7 mA
limits of rated operational voltage
<=57.6V
control circuit voltage range
28.8V
switching frequency
<= 1 Hz DC-14 module single load cycle: 40 %
<= 6 Hz DC-13 module single load cycle: 40 %
<= 700 Hz on high resistance load load cycle: 50 %
Flame retardance
V0 conforming to UL 94
Local signalling
Green mechanical indicator for contact position and 1 green LED control signal status
voltage state 1 guaranteed
16.9V
cable section
0.6...2.5 mm², 1 or 2 wires flexible without cable end screw clamp terminals
0.27...4 mm², 1 wire rigid
0.34...2.5 mm², 1 or 2 wires flexible with cable end
dropout voltage
1.5V
mounting bracket
Symmetrical DIN rail
Asymmetric profile
Combined rail
rated service voltage (us)
5...48V
voltage state 0 guaranteed
5.6V
output circuit type
CC
mounting position
All positions
short circuit protection
3.15 A external fast-blow fuse (Ik <= 1 kA AC and Ik <= 100 A DC)
dielectric strength
2500 V between hardwired interface and ground for 1 minute
4000 V between I/O for 1 minute
Environment
degree of pollution
2 conforming to IEC 60947-1
ip degree of protection
IP20 conforming to IEC 60529
operating altitude
<= 3000 m
product certificates
UL
LROS (Lloyds register of shipping)
DNV
BV
CSA
electromagnetic compatibility
Electromagnetic field immunity test: level 3 11 V/m between 27...1000 MHz conforming to IEC 61000-4-3
Electrostatic discharge immunity test: level 3 8 kV conforming to IEC 6100-4-11
Test fast transient immunity test: level 3 on 1 kV input/output conforming to IEC 61000-4-4
Fast transient immunity test: level 3 on 2 kV supply conforming to IEC
61000-4-4 immunity to shock waves 1.2/50 µs conforming to IEC 60947-1
operating ambient temperature
-25…70 °C with Us
-5…55 °C free operation
standards
IEC 60947-5-1
fire resistance
960 °C conforming to IEC 60695-2-1
storage room temperature
-40…80 °C
mechanical shock resistance
30 gn for 11 ms conforming to IEC 60068-2-27
vibration resistance
5 gn (f = 10...150 Hz) conforming to IEC 60068-2-6
protective treatment
TC