Main
allowable temporary current amplification
1,5 x In (pendant 4 s)
power supply module output current
20 A
product range
Alimentation Modicon
anti-harmonic filter
Low frequency harmonic currents
type of product or equipment
power supply
nominal power in w
480W
rated input voltage
100...120 V AC single-phase, connection(s): N-L1
200...240 V AC phase-phase, connection(s): L1-L2
kind of power supply
Regulated switching mode
Complementary
18 mm pitches
0.68 at 240 V AC
0.69 at 120 V AC
feed
SELV conforming to EN/IEC 60950-1
SELV conforming to EN/IEC 60204-1
SELV conforming to IEC 60364-4-41
output coupling
Parallel Series
Handle front plate colour
125 mm
inrush current
30 A
product weight
1,6 kg
marking
THIS
led status
1 LED (green and red) output voltage
1 LED (green, red and orange) output current
connection mode
Removable screw terminal block: 2 x 2.5 mm², for diagnostic relay
Screw type terminals: 3 x 0.5...3 x 4 mm², (AWG 22...AWG 12) for input connection
Screw type terminals: 1 x 0 .5 ...1 x 4 mm², (AWG 22...AWG 12) for input ground connection
Screw type terminals: 4 x 0.5...4 x 4 mm², (AWG 22...AWG 12) for output connection
output voltage
24 V CC
width (w)
146 mm
input voltage limits
85...132V AC
170...264V AC
depth
145 mm
mounting bracket
symmetrical profile 35x7.5mm
symmetrical profile 35x15mm
power dissipation in w
57.6W
yield
88,00%
equipment provided
Power factor correction filter conforming to IEC 61000-3-2
output voltage adjustment
Adjustable from 24 to 28.8 V
mounting position
Vertical
dielectric strength
2500 V with between input and ground
3000 V with between input and output
500 V with between output and ground
output protection type
Against overload, technological protection: manual or automatic reset
Against overvoltage, technological protection: 30 to 32 V, manual reset
Against short-circuits, technological protection: manual or automatic reset
Against undervoltage, technological protection: tripping if U < 21.6 V
Thermal, technological protection: automatic reset
Environment
environment characteristic
EMC conforming to EN 61000-6-1
EMC conforming to EN 61000-6-3
EMC conforming to EN 55024
EMC conforming to EN/IEC 61000-6-4
EMC conforming to EN/IEC 61204-3
Safety conforming to conforming to EN/IEC 60950-1
Safety conforming to EN/IEC 61204-3
ip degree of protection
IP20 conforming to EN/IEC 60529
IP10
operating altitude
2000 m
product certificates
CCSAus
EAC
KC
RCM
UL
ambient air temperature for operation
50…60 °C with reduction factor mounting position A < 2000 m
-25…50 °C without derating mounting position A < 2000 m
standards
CSA C22.2 No 60950-1
UL 508
EN/CEI 62368-1