Main
power supply module output current
3,13 A
product range
Alimentation Modicon
type of product or equipment
power supply
nominal power in w
75W
rated input voltage
100...240 V AC single-phase
100...240 V AC 2-phase
140...340 V DC
kind of power supply
Regulated switching mode
optional variant
Optimized
Complementary
18 mm pitches
0.55 at 115 V AC
0.45 at 230 V AC
feed
SELV conforming to EN/IEC 60950-1
SELV conforming to EN/IEC 60204-1
SELV conforming to IEC 60364-4-41
power consumption
< 1,8 A 115 V CA
< 1 A 230 V CA
< 0,8 A 140 V CC
output coupling
Parallel
Series
Handle front plate colour
123,6 mm
maximum leakage current
1mA 240V AC
case material
Plastic
inrush current
40.0 A at 115 V
80.0 A at 230 V
expected capacitor life
10 year(s)
product weight
0,22 kg
starting with capacitive loads
5000 µF
led status
1 LED (green) output voltage
connection mode
Screw connection: 0.5...2.5 mm², (AWG 20...AWG 14) for output
Screw connection: 0.75...2.5 mm², (AWG 18...AWG 14) for input
nominal network frequency
50…60 Hz
output voltage
24 V CC
width (w)
27 mm
input voltage limits
85...264 V CA (without temperature derating)
120...375 V CC (without temperature derating)
85…120 V CC (with temperature derating)
line and load regulation
< 0,5 % network 0 to 100 % load at 25 °C
< 1 % network full voltage range in line at 25 °C
residual ripple
< 120 mV
depth
102 mm
mounting bracket
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
DIN double profile rail
power dissipation in w
15W
yield
88% at 230V AC
output voltage adjustment
21.6…26.4V
compatible network system
TN
TT
IT
mataining time
> 20 ms 115 V CA
> 40 ms 230 V CA
start-up time
< 1,2 s
mean time between failures (mtbf)
700000 H at 25 °C, pleine charge conforming to SR 332
dielectric strength
3000 V CA avec input to output
output protection type
Against overload and short-circuits, protection technology: automatic reset
Against overheating, protection technology: manual reset
Against overvoltage, protection technology: manual reset
input protection type
Integrated fuse (not interchangeable) 5 A
External protection (recommended) 20 A Curve C
External protection (recommended) 13 A Curve B
External protection (recommended) 10 A Curve C
Environment
degree of pollution
2
environment characteristic
3M4 conforming to IEC 60721-3-3
ip degree of protection
IP20
operating altitude
< 5000 m
product certificates
CE
cUL Listed cUL
Recognized
RCM
Scheme CB
EAC
KC
NEC: Class 2
ambient air temperature for operation
-20…-10 °C with 1% current reduction per °C mounting position A < 2000 m
-10…40 °C without derating mounting position A 115 V AC < 2000 m
-10…50 °C without derating mounting position A 230 V AC < 2000 m
40…70 °C with current derating of 1.67 % per °C mounting position A 115 V AC < 2000 m
50…70 °C with current derating of 2.5 % per °C mounting position A 230 V AC < 2000 m
class of protection against electric shock
Class I
standards
EN 62368-1
EN/CEI 61010-1
EN 61010-2-201
EN/CEI 61204-3
EN 61000-6-1
EN 61000-6-2
EN 61000-6-3
EN 61000-6-4
EN 61000-3 -2
EN 61000-3-3
UL 62368-1
UL 61010-1
UL 61010-2-201
CSA C22.2 No 62368-1
CSA C22.2 No 61010-1
CSA C22.2 No 61010-2-201
EN/ IEC 62368-1
mechanical shock resistance
100 m/s² pour 11 ms
electromagnetic emission
Conducted emissions conforming to EN 61000-6-3
Radiated emissions conforming to EN 61000-6-4
vibration resistance
3 mm (f= 2...9 Hz) conforming to IEC 60068-2-6
10 m/s² (f= 9...200 Hz) conforming to IEC 60068-2-6
electromagnetic immunity
Immunity to electrostatic discharge - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2
Immunity to electrostatic discharge - test level: 9 kV (air discharge) conforming to EN/ IEC 61000-4-2
Immunity to conducted RF disturbances - test level: 10 V/m (80 MHz...2 GHz) conforming to EN/IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to EN/IEC 61000-4-3
Immunity to conducted RF disturbances - test level: 3 V/m (2.7...6 GHz ) conforming to EN/IEC 61000-4-3
Immunity to fast transients - test level: 4 kV (on input-output) conforming to EN/IEC 61000-4-4
Surge immunity test - test level: 3 kV (between supply and earth) conforming to EN/IEC 61000-4-5
Surge immunity test - test level: 1.5 kV (between phases) conforming to EN/IEC 61000-4-5
Immunity to conducted RF disturbances - test level: 10 V (0.15 to 80 MHz) conforming to EN/IEC 61000-4-6
Immunity to magnetic fields - test level test: 30 A/m (50...60 Hz) conforming to EN/IEC 61000-4-8
Immunity to voltage drops conforming to EN/IEC 61000-4-11
Disturbance field emission conforming to EN 55016- 2-3
Limitation of harmonic current emission conforming to EN 61000-3-2
Disturbance emission transmitted by conduction conforming to EN 55016-1-2
Conducted disturbance emission conforming to EN 55016-2-1