Complementary
[un] rated nominal voltage
24…240 V CA 50/60 Hz
24 V CC
compatibility code
RE17
[ics] rated service breaking capacity
2000 VA
contact description
1 F/O
maximum switching current
8 A CA/CC
Handle front plate colour
90 mm
tightening torque
0.6...1 Nm conforming to IEC 60947-1
[uimp] rated impulse withstand voltage
5 kV pendant 1,2/50 µs
case material
Auto-extinguible
minimum switching current
10 mA at 5 V DC
product weight
0,07 kg
marking
THIS
power consumed in va
0…32 VA at 240 V AC
reset time
120 ms on dropout typical
electrical life
100000 cycles for resistive load (8 A at 250 V AC maximum)
escape distance
4 kV/3 conforming to IEC 60664-1
connection mode
Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) rigid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) rigid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16 ) flexible with tip
duty cycle
one hundred %
safety reliability data
B10d = 270000
MTTFd = 296.8 years
contact material
Sans cadmium
mechanical endurance
10000000 cycle
width (w)
17,5 mm
power frequency
50...60 Hz +/- 5 %
power-on delay
100 ms
Local signalling
LED indicator for stabilized: relay powered, no time delay in progress
LED indicator 80% ON and 20% OFF for flashing: time delay in progress
LED indicator 5% ON and 95% OFF for pulse: relay de-energized, no timer in progress (except function Di-D, Li-L)
temperature drift
+/- 0,05 %/°C
voltage drift
+/- 0.2%/V
timing range
6…60 s
1…10 H
1…10 min
6…60 min
0,1…1 s
1…10 s
10…100 H
functionality
Timer with on-delay
depth
72 mm
mounting bracket
35 mm DIN rail conforming to EN/IEC 60715
operating frequency
10 Hz
repeat accuracy
+/- 0.5% conforming to IEC 61812-1
control signal pulse width
100 ms with typical parallel load
30 ms typical
input voltage release
10V
mounting position
Any position relative to the normal vertical mounting plane
maximum power consumption in w
0,6 W à 24 V CC
order type
Front panel selector
voltage range of use
0.85 to 1.1 Us
dielectric strength
2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
exact adjustment of the delay time
+/- 10 % full scale at 25 °C conforming to IEC 61812-1
maximum cut-off voltage
250 VCA
logic output type
Relay
Environment
ip degree of protection
IP20 conforming to IEC 60529 (terminal block)
IP40 conforming to IEC 60529 (enclosure)
IP50 conforming to IEC 60529 (front face)
product certificates
cULus
GL
CSA
electromagnetic compatibility
Electrostatic discharge immunity test: (in contact) 3.6 kV level conforming to IEC 6100-4-11
Electrostatic discharge immunity test: (in air) 3.8 kV level conforming to IEC 6100-4-11
Electromagnetic field disturbance: (80 MHz to 1 GHz) level 3.10 V/m conforming to IEC 61000-4-3
Electrical fast transient immunity test: (capacitive connection clip ) ,3.1 kV level conforming to IEC 61000-4-4
Electrical fast transient immunity test: (direct) ,3.2 kV level conforming to IEC 61000-4-4 Power
wave immunity test 1.2/50 µs shock: (differential mode) ,3.1 kV level conforming to IEC 61000-4-5
1.2/50 µs shock waves immunity test: (common mode) ,3.2 kV level conforming to IEC 61000-4-5
Conducted RF disturbances: (0.15...80 MHz) ,level 3.10 V conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test: (1 cycle) .0 % conforming to IEC 61000-4-11 Voltage
dips and interruptions immunity test voltage: (25/30 cycles) .70 % conforming to IEC 61000-4-11
Conducted and radiated emissions: .class B conforming to EN 55022
immunity to micro-breaks
20 ms
standards
EN 61000-6-4
EN 61000-6-2
EN 61000-6-3
2004/108/EC
2006/95/EC
CEI 61812-1
EN 61000-6-1
relative humidity
93 % non-condensing conforming to IEC 60068-2-30
operating ambient air temperature
-20…60 °C
storage room temperature
-30…60 °C
mechanical shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
vibration resistance
20 m/s² (f= 10...150 Hz) conforming to IEC 60068-2-6
insulation resistance
100 MΩ at 500 V DC conforming to IEC 60664-1