Main
product range
Harmony electromechanical relay
[uc] control circuit voltage
24 V CC
name of the device
RXM
type of product or equipment
Pre-assembled plug-in relay with socket
range name
Miniature
[ui] rated insulation voltage
250 V conforming to IEC
sale by indivisible quantity
30
Complementary
[ie] rated operational current
3 A at 28 V (DC) "O" conforming to IEC
3 A at 250 V (AC) "O" conforming to IEC
6 A at 28 V (DC) "F" conforming to IEC
6 A at 250 V (AC) "F" conforming to IEC
6 A at 277 V (AC) conforming to UL
8 A at 30 V (DC) conforming to UL
contact description
4 F/O
[uimp] rated impulse withstand voltage
2,5 kV pendant 1,2/50 µs
minimum switching capacity
170mW at 10mA, 17V
minimum switching current
10 mA
product weight
0,096 kg
protection category
RT I
nominal resistive load
6 A at 250 V AC
6 A at 28 V DC
Average coil consumption in w
0,9 W, CC
electrical life
100000 cycles for resistive load
led status
With
connection mode
Connector, 1 x 0.25...1 x 2.5 mm² (AWG 22...AWG 14) flexible with cable end
Connector, 2 x 0.25...2 x 1 mm² (AWG 22...AWG 17) flexible with cable end
Connector, 1 x 0.5...1 x 2.5 mm² (AWG 20...AWG 14) rigid without cable end
Connector, 2 x 0.5...2 x 1.5 mm² (4 x 1.5 mm² + 2 x 1 mm² + 2 x 0 ,14 mm²) rigid without cable end
duty cycle
20,00%
limits of rated operational voltage
19,2...26,4 V CC
safety reliability data
B10d = 100000
contact material
AgNi
mechanical endurance
10000000 cycle
overall height cao
79 mm
product presentation
Complete product
maximum switching power
1500VA/168W AC/DC
overall width cao
26,9 mm
test levels
A-level
continuous output current
5 A
average coil resistance
650 Ohm at 20 °C +/- 10 %
drop-out voltage threshold
>= 0,1 Uc CC
operating time
20 ms
mounting position
All positions
trigger time
20 ms
minimum switching voltage
17V
order type
Lockable test button
overall depth cao
78,45 mm
torque value
1 N.m
dielectric strength
1300 V AC between contacts with microbreak
2000 V AC between coil and contact with basic insulation
2000 V AC between poles with basic insulation
command speed
<= 1200 cycles/hour under load
<= 18000 cycles/hour without load
maximum cut-off voltage
250V
Environment
degree of pollution
2
ip degree of protection
IP20 conforming to EN/IEC 60529
product certificates
CE
UL
CSA
EAC
Lloyd's
standards
UL 508
EN/CEI 61810-1
CSA C22.2 No 14
CEI 61984
operating temperature
-40…55 °C
storage room temperature
-40…85 °C
mechanical shock resistance
10 gn for running
30 gn for not running
vibration resistance
3 gn, amplitude = +/- 1 mm (f = 10…150 Hz) 5 cycles in operation