Main
product range
Harmony electromechanical relay
[ithe] thermal current under enclosure
5 A
[uc] control circuit voltage
24 V CC
name of the device
RXG
type of product or equipment
Pre-assembled plug-in relay with socket
range name
Interface relays
[ui] rated insulation voltage
250 V conforming to IEC
Complementary
[ie] rated operational current
5 A at 30 V (DC) conforming to UL
5 A at 30 V (DC) conforming to IEC
5 A at 250 V (AC) conforming to IEC
5 A at 250 V (AC) conforming to UL
contact description
2 "O/F"
[uimp] rated impulse withstand voltage
6 kV 1.2/50 µs between coil and contact
4 kV 1.2/50 µs between poles
1.2 kV 1.2/50 µs between contacts
2.5 kV 1.2/50 µs between terminals and zone LTB
1.5 kV 1.2/50 µs between terminals and base
minimum switching capacity
50 mW at 10 mA, 5 V DC
product weight
0,065 kg
protection category
RT I
coil insulation class
Classe F
average coil consumption
0,53 W CC
electrical life
100000 cycle resistive load
led status
With
connection mode
Connector, 1 x 0.25...1 x 2.5 mm² (AWG 22...AWG 14) flexible with cable end
Connector, 2 x 0.25...2 x 1 mm² (AWG 22...AWG 17) flexible with cable end
Connector, 1 x 0.5...1 x 2.5 mm² (AWG 20...AWG 14) rigid without cable end
Connector, 2 x 0.5...2 x 1.5 mm² (4 x 1.5 mm² + 2 x 1 mm² + 2 x 0 ,14 mm²) rigid without cable end
duty cycle
20,00%
hood color
Transparent
safety reliability data
B10d = 100000
charging current
5 A
contact material
Silver alloy (AgSnO2In2O3)
mechanical endurance
10000000 cycle
product presentation
Complete product
maximum switching power
1 250 VA AC
150 W DC
test levels
A-level
drop-out voltage threshold
>= 0,1 Uc CC
operating time
20 ms
mounting position
All positions
trigger time
20 ms
coil resistance
1100 Ohm +/- 10 %
max contact resistance
100 mOhm
order type
Lockable test button
torque value
0,8 N.m
0,79 N.m
dielectric strength
1000 V AC between contacts with microbreak
1300 V between terminals and base with basic insulation
3000 V between terminals and LTB zone with basic insulation
3000 V AC between poles with basic insulation
5000 V AC between coil and contact with insulation reinforced
command speed
<= 1800 cycles/hour under load
<= 18000 cycles/hour without load
maximum cut-off voltage
250V
Environment
degree of pollution
2
degree of protection (ip)
IP20
product certificates
CSA
CE
EAC
UL
DNV-GL
operating ambient temperature
-40…70 °C
overvoltage category
III
standards
CEI 61810-1
CSA C22.2 No 14
UL 508
CEI 61984
relative humidity
10…85%
storage room temperature
-40…85 °C
mechanical shock resistance
20 gn running
100 gn not running
vibration resistance
3 gn, amplitude = +/-1.5 mm (f = 10…150 Hz) in operation
5 gn, amplitude = +/-1.5 mm (f = 10…150 Hz) not in operation
insulation resistance
1000 MΩ à 500 V CC