Main
product range
Wished Time
type of product or equipment
Industrial Timing Relay
dimension of the step in width
22,5 mm
timer type
L
Lt
Li
[ui] rated insulation voltage
250 V between contact circuit and control inputs IEC certified
250 V between contact circuit and power supply IEC certified
300 V between contact circuit and control inputs CSA certified
300 V between contact circuit and power supply CSA certified
component name
RE7
Complementary
[ie] rated operational current
2 A DC-13 24 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
0.1 A DC-13 250 V at 70 °C conforming to IEC 60947-5-1/1991/ VDE 0660
0.2 A DC-13 115 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
3 A AC-15 at 70 °C conforming to IEC 60947-5-1/1991/ VDE 0660
[un] rated nominal voltage
110 à 240 V AC 50/60 Hz
24 V AC/DC 50/60 Hz
42...48 V AC/DC 50/60 Hz
[ith] conventional thermal current
8 A
digital input compatibility
3/4 wire PNP/NPN sensors without internal load <50 m X1Z2 terminal(s)
3/4 wire PNP/NPN sensors without internal load <50 m X2Z2 terminal(s)
maximum switching current
1 mA (X1Z2)
1 mA (X2Z2)
Handle front plate colour
78 mm
tightening torque
0,6…1,1 N.m
minimum pulse duration
20 ms
minimum switching capacity
10mA at 12V
potentiometer characteristics
Linear 47 kOhm (+/- 20%), 0.2 W, cable length <25 m Z1Z2 connection(s)
product weight
0,15 kg
marking
THIS
power consumed in va
0.7 VA at 24 V
1.6 VA at 48 V
1.8 VA at 110 V
8.5 VA at 240 V
reset time
50 ms
connection mode
Screw terminals, 2 x 1.5 mm² flexible with cable end
Screw terminals, 2 x 2.5 mm² flexible without cable end
contact material
Contacts nickel argent 90/10
mechanical endurance
20000000 cycle
width (w)
22,5 mm
description of terminals
(B1-A2)CO
ALT
(15-16-18)OC_OFF
temperature drift
< 0,07 %/°C
voltage drift
< 0.2%/V
timing range
0,05 s...300 H
depth
80 mm
repeat accuracy
+/- 0.2%
resistance to shock waves
2 kV conforming to IEC 61000-4-5 level 3
input voltage
< 60 V X1Z2 terminal(s)
< 60 V X2Z2 terminal(s)
mounting position
All positions without derating
maximum power consumption in w
0.5W at 24V
1.2W at 48V
voltage range of use
0.85 to 1.1 Us
dielectric strength
2,5 kV
exact adjustment of the delay time
+/- 10% full scale
disengagement value
> 0,1 Uc
maximum cut-off voltage
250 V CA/CC
logic output type
Relay
Environment
degree of pollution
3 conforming to IEC 60664-1
ip degree of protection
IP20 (terminals)
IP50 (enclosure)
product certificates
UL
CSA
GL
immunity to micro-breaks
3 ms
operating ambient temperature
-20…60 °C
overvoltage category
III conforming to IEC 60664-1
standards
EN/CEI 61812-1
relative humidity
15...85 % 3K3 conforming to IEC 60721-3-3
disturbance written off/conducted
CISPR22 - Class A
Group 1 CISPR11 - Class A
storage room temperature
-40…85 °C
mechanical shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
where of non-dissipative shock
4,8 kV
vibration resistance
0.35 mm (f= 10...55 Hz) conforming to IEC 60068-2-6
resistance to radiated electromagnetic fields
10 V/m conforming to IEC 61000-4-3 level 3
resistance to electrostatic discharges
6 kV in contact conforming to IEC 61000-4-2 level 3
8 kV in air conforming to IEC 61000-4-2 level 3
resistance to fast transients
2 kV conforming to IEC 61000-4-4 level 3