Complementary
[ig] earth protection threshold adjustment range
with In > 400 A 0.2 to 1 x inch adjustable in steps of 10 A
with In <= 400 A 0.3 to 1 x inch adjustable in steps of 10 A
Ig on/off activation
[ii] instantaneous pick-up adjustment range
2...15 x In adjustable in steps of 0.5 x In with embedded HMI
2...15 x In adjustable in steps of 0.1 x In with Ecoreach software or Masterpact MTZ mobile application
Activation Ii on/off
[ue] rated operational voltage
690 V CA, +/- 10 %
application
Protection, monitoring and control of equipment
range compatibility
Masterpact (MasterPacT MTZ1) circuit breaker
Masterpact (MasterPacT MTZ2) circuit breaker
Masterpact (MasterPacT MTZ3) circuit breaker
[ir] long time pick-up adjustment range
0.4…1 x In adjustable in steps of 1 A
[isd] short-time threshold setting range
1.5...10 x Ir adjustable in steps of 0.5 x Ir with embedded HMI
1.5...10 x Ir adjustable in steps of 0.1 x Ir with Ecoreach software or Masterpact MTZ mobile application
trigger caliber
1000 A
5000 A
2500 A
3200 A
630 A
1250 A
400 A
4000 A
800 A
6300 A
1600 A
2000 A
[li mode] instantaneous delay adjustment range
0 ms in fast
20 ms in standard
accuracy class
Class 5: current total harmonic distortion rate THD (I)
Class 0.5: unbalance voltage
Class 1: active and reactive energy by pulse counting (+/- Wh, +/- VAR.h)
Class 2 : total harmonic distortion rate in voltage THD (V)
data logging
Maintenance
logs Data reports
Min/max number of instantaneous values
Alarm
logs Event reports
Timestamp
mounting location
Indoor use only
[tr] long-time delay adjustment range
12.5…600 s at 1.5 x Jump
0.5…24 s at 6 x Jump
0.7…16.6 s at 7.2 x Jump
[tsd] short-time delay adjustment range
0,1…0,4 s I²t=on
0…0,4 s I²t=off
[tg] earth fault time delay setting range
0,1…0,4 s I²t=on
0…0,4 s I²t=off
mode d'installation
Fixed
type of measurement
power meter
energy management
Active, reactive and apparent energy measurement (standard)
Electrical network measurement (standard)
Energy measurement (standard)
network frequency
50/60 Hz
thermal memory
Yes
ground-fault time delay adjustment type
Adjustable
frequency measurement range
45…250 Hz
measurement accuracy
Power factor: +/- 1 %
Active energy Ep INPUT/OUTPUT/tot: +/- 1 % - 10...10 GWh
Reactive energy Ep INPUT/OUTPUT/tot: +/- 2 % - 10...10 GVARh
Apparent energy Es INPUT/OUTPUT/tot: +/- 1 % - 10...10 GVAh
Unbalance current: +/- 0.5 %
Frequency: +/- 0.005 Hz
Voltage V21, V32, V13, VLLavg: + /- 0.5% 208...690 x 1.2 V
Voltage V21, V32, V13, VLNavg: +/- 0.5% 120...400 x 1.2 V
Apparent power S, S1, S2, S3, Sdemanded: +/- 1 %
Active power P, P1, P2, P3, P demanded: +/- 1 %
Reactive power Q, Q1, Q2, Q3, Q demanded: +/- 2 %
Current I1, I2, I3 , Iavg, Idemand for MTZ1: +/- 0.5 % 40...1600 x 1.2 A
Courant I1, I2, I3, Imoy, Idemande pour MTZ2: +/- 0,5 % 40...4000 x 1,2 A
Courant I1, I2, I3, Imoy, Idemande pour MTZ3: +/- 0,5 % 80...6300 x 1,2 A
communication port protocol
Bluetooth 4.0 LE peer-to-peer 30 kbit/s
NFC peer-to-peer conforming to ISO 15963
USB peer-to-peer 115 kbaud
Network type
THAT
type of network and machine diagnostics
System Health (HMI) Overview: Circuit Breaker Health (as standard)
Contacts State: Circuit Breaker Health (as standard)
Micrologic Lifetime: Circuit Breaker Health (as standard) as standard)
Trip cause indication: circuit breaker trip cause (as standard)
Identification card: diagnostic data (as standard)
Configured alarm summary: diagnostic data (as standard)
Monitored function: diagnostic data (as standard)
Operation: diagnostic data (as standard)
Micrologic test: test (as standard)
Protection test: test (as standard)
Selectivity test: test (as standard)
Trip context information: Management of a trip event (as standard)
Operation: advanced diagnostics (as standard)
Circuit breaker life: circuit breaker health status (as standard)
instantaneous delay setting type
Adjustable
timer setting type
Adjustable in steps of 0.5 s
type of instantaneous threshold adjustment (ii)
Adjustable
measuring voltage
145,6…828 V CA 50/60 Hz per phase
type of display
LCD display - 128 x 96 pixels
type of earth protection threshold setting (ig)
Adjustable
kind of protection
Overload protection (long time) conforming to ANSI 49
Instantaneous short-circuit protection conforming to ANSI 50
Short-time protection conforming to ANSI 51
Earth fault conforming to ANSI 51N
zsi logic selective latch area
With
type of count
Current I1, I2, I3, In, Ig: maximum (as standard)
Average voltage Vavg (as standard)
Active power P, P1, P2, P3 (as standard)
Reactive power Q, Q1, Q2, Q3 (as standard)
Power apparent current S, S1, S2, S3 (as standard)
Power factor (as standard)
Frequency (as standard)
Current total harmonic distortion rate THD (I): inst, avg, min avg, max avg fundamental voltage (as standard )
Current total harmonic distortion rate THD (I): inst, avg, min avg, max ag voltage RMS (as standard)
Voltage V21, V32, V13, V1, V2, V3: instantaneous (as standard)
Voltage V21, V32 , V13, V1, V2, V3: minimum (as standard)
Voltage V21, V32, V13, V1, V2, V3: maximum (as standard)
Total harmonic distortion in voltage THD (V): inst, avg, min avg, max avg fundamental voltage (as standard)
Total harmonic distortion rate in voltage THD (V): inst, avg, min avg, max avg RMS voltage (as standard)
Current demand I1, I2, I3, In, Iavg (as standard)
Active (P), reactive (Q) and apparent power (S) requested (as standard)