Default
Seeria
TeSyS Deca ülekoormusreleed
Main
Range
TeSys
name of the device
LR9D
thermal overload class
Class 5…30
type of product or equipment
Electronic thermal overload relay
Product Name
TeSys LRD
[ui] rated insulation voltage
Power circuit: 1000 V
Signaling circuit: 690 V
use of the relay
Motor protection
Complementary
associated accessories
LC1D09
LC1D25
LC1D32
LC1D38
LC1D12
LC1D18
[ue] rated operational voltage
690 V for power circuit
660 V for signaling circuit
[ith] conventional thermal current
5 A for signaling circuit
caliber of the fuse to be associated
5 A gG for signaling circuit
5 A BS for signaling circuit
Handle front plate colour
72,5 mm
tightening torque
Remote control: 0.8 Nm on screw clamp terminals
Power circuit: 3.1 Nm on screw clamp terminals
[uimp] rated impulse withstand voltage
6 kV
product weight
0,18 kg
thermal protection setting area
6,4…32 A
time range
1.5 to 4 min - automatic reset delay
connection mode
Remote control: screw clamp terminals 1 cable 2.5 mm² - cable stiffness: rigid or flexible - without cable end
Power circuit: screw clamp terminals 1 cable 16 mm² - cable stiffness: rigid or flexible - without cable end
width (w)
45 mm
mechanical robustness
Vibrations 10 to 150 Hz: 6 Gn conforming to IEC 60068-2-6
Shocks 11 ms: 15 gn conforming to IEC 60068-2-7
trigger point
1.25 In conforming to IEC 60947-4-1
depth
79,9 mm
mounting bracket
Under the
Platinum contactor, with specific accessories
Rail, with specific accessories
sensitivity to phase loss
Phase difference > 40% 3 s conforming to IEC 60947-4-1
maximum power consumption in w
300 mW
order type
Red push button: stop and manual reset
White 2 microswitches: adjustable trip class
Red button: automatic reset
Gray dial: full load current adjustment
dielectric strength
6 kV 50 Hz conforming to IEC 60255-5
Environment
ip degree of protection
IP20 front face conforming to IEC 60529
operating altitude
2000 m without current reduction
product certificates
CEI CE
UL
CSA
CCC certificate
electromagnetic compatibility
Resistance: 2 kV common mode conforming to IEC 61000-4-5
Resistance to electrostatic discharge: 8 kV conforming to IEC 6100-4-11
Immunity against radiated radioelectric interference: 10 V/m conforming to IEC 61000- 4-3
Immunity to fast transients: 2 kV conforming to IEC 61000-4-4
standards
EN/CEI 60947-4-1
EN/CEI 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/ T 14048.4
GB/T 14048.5
operating temperature
-25...70 °C conforming to IEC 60255-8
storage room temperature
-55…80 °C