Main
product range
TeSys K
Range
TeSys
job category
AC-1
AC-4
AC-3
AC-3e
name of the device
LP1K
switch application
Resistive load (AC-1)
Motor control (AC-3)
type of product or equipment
contactor
composition of the poles
3F
[ui] rated insulation voltage
Power circuit: 600 V conforming to UL 508
Power circuit: 690 V conforming to IEC 60947-4-1
Signaling circuit: 690 V conforming to IEC 60947-4-1
Signaling circuit: 690 V conforming to IEC 60947-5-1
Signaling circuit: 600 V conforming to UL 508
Power circuit: 600 V conforming to CSA C22.2 No 14
Signaling circuit: 600 V conforming to CSA C22.2 No 14
average impedance
3 mOhm - Ith 20 A 50 Hz for power circuit
Complementary
[ie] rated operational current
20 A (at <50°C) at <= 440 V AC AC-1 for power circuit
9 A at <= 440 V AC AC-3 for power circuit
16 A (at <70°C) at 690 V AC AC-1 for power circuit
9 A at <= 440 V AC AC-3e for power circuit
[ue] rated operational voltage
Power circuit: 690 V AC 50/60 Hz
Signaling circuit: <= 690 V AC 50/60 Hz
[ics] rated service breaking capacity
110 A at 415 V conforming to IEC 60947
110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
110 A at 220...230 V conforming to IEC 60947
110 A at 380... .400 V conforming to IEC 60947
70 A at 660...690 V conforming to IEC 60947
[ith] conventional thermal current
20 A at <50 °C) for power circuit
10 A at <50 °C) for signaling circuit
caliber of the fuse to be associated
25 A gG at <= 440 V for power circuit
25 A aM for power circuit
10 A gG for signaling circuit conforming to IEC 60947
10 A gG for signaling circuit conforming to VDE 0660
average consumption on hold in w
3W at 20°C
Handle front plate colour
58 mm
tightening torque
0.8…1.3 Nm - on Philips no. 2 cross-head screw clamp terminals
0.8…1.3 Nm - on flat screw clamp terminals Ø 6 mm
0.8…1.3 Nm - on terminal blocks screw clamp pozidriv n°2
[uimp] rated impulse withstand voltage
8 kV
auxiliary contacts
1 "O"
minimum switching current
5 mA for signaling circuit
product weight
0,225 kg
type of auxiliary contacts
instantaneous type 1 "O"
control circuit voltage range
Operational: 0.8…1.15 Uc (at <50°C)
Level loss: 0.1…0.75 Uc (at <50°C)
mechanical endurance
10 Mcycles
width (w)
45 mm
Flame retardance
V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
rated rms inrush power
110 A AC for power circuit conforming to NF C 63-110
110 A AC for power circuit conforming to IEC 60947
110 A AC for signaling circuit conforming to IEC 60947
depth
57 mm
mounting bracket
Rail
Platine
maximum inrush power in w
3W (at 20°C)
operating time
30…40 ms excitation bobine + fermeture "F"
10 ms désexcitation bobine + ouverture "F"
security reliability level
B10d = 1369863 contactor cycle with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 contactor cycle with mechanical load conforming to EN/ISO 13849-1
max command speed
3600 cyc/h
minimum switching voltage
17 V for signaling circuit
Poles description
3P
Environment
operating altitude
2000 m without derating
product certificates
UL
CSA
UKCA
operating ambient temperature
-25…50 °C
overvoltage category
III
storage room temperature
-50…80 °C
insulation resistance
> 10 MΩ for signaling circuit