Default
Seeria
TeSyS Deca kontaktorid
Main
Range
TeSys
TeSys Deca
[uc] control circuit voltage
230 V AC 50/60Hz
job category
AC-1
name of the device
LC2D
switch application
Resistive load (AC-1)
type of product or equipment
Reversing contactor
Product Name
TeSys D
TeSys Deca
[ui] rated insulation voltage
Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signaling circuit: 690 V conforming to IEC 60947-1
Signaling circuit: 600 V CSA Certified
Signaling Circuit: 600V UL Certified
control circuit type
AC at 50/60 Hz
composition of the power pole contacts
4F
average impedance
2.5 mOhm - Ith 32 A 50 Hz for power circuit
Complementary
[ie] rated operational current
32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC
[ics] rated service breaking capacity
300 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
40 A at <40°C - 10 min for
84 A power circuit at <40°C - 1 min for
145 A power circuit at <40°C - 10 s for
240 A power circuit at <40°C - 1s for
100 A power circuit - 1s for
120 A signaling circuit - 500 ms for
140 A signaling circuit - 100 ms for signaling circuit
[ith] conventional thermal current
10 A at <60°C) for signaling circuit
32 A at <60°C) for power circuit
caliber of the fuse to be associated
10 A gG for signaling circuit conforming to IEC 60947-5-1
50 A gG at <= 690 V type 1 coordination for power circuit
35 A gG at <= 690 V type 2 coordination for power circuit
Handle front plate colour
91 mm
tightening torque
Remote control: 1.7 Nm - on screw-clamp terminals - with flat screwdriver Ø 6 mm
Remote control: 1.7 Nm - on screw-clamp terminals - with Phillips No. 2 screwdriver
Power circuit: 1.7 Nm - on connector - with Ø 6 mm flat screwdriver
Power circuit: 1.7 Nm - on connector - with No. 2 Phillips screwdriver
Remote control: 1.7 Nm - on screw clamp terminals - with No. 2 pozidriv screwdriver Power
circuit power: 2.5 Nm - on screw clamp terminals - with pozidriv n°2 screwdriver
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
auxiliary contacts
1 "O" + 1 "F"
average fuel consumption when going
7.5 VA 60 Hz cos phi 0.3 (at 20°C)
7 VA 50 Hz cos phi 0.3 (at 20°C)
minimum switching current
5 mA for signaling circuit
product weight
0,85 kg
type of auxiliary contacts
mechanically linked type 1 NC + 1 NO conforming to IEC 60947-5-1
1 NC mirror contact type conforming to IEC 60947-4-1
electrical life
1 Mcycles 32 A AC-1 at Ue <= 440 V
connection mode
Remote control: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 1 cable( s) 1…4 mm²flexible with cable end
Remote control: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Remote control: screw clamp terminals 1 cable(s) 1…4 mm²rigid
Remote control: screw clamp terminals 2 cable(s) 1…4 mm²rigid
Power circuit: connector 1 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: connector 2 cable(s) 2.5…10 mm²flexible without cable end
Power circuit: connector 1 flexible cable(s) 2.5...10 mm² with cable end
Power circuit: connector 2 flexible cable(s) 2.5...10 mm² with cable end
Power circuit: connector 1 cable(s) 2.5...16 mm²rigid
Power circuit: connector 2 cable(s) 2.5...16 mm²rigid
type of lock
Mechanical
control circuit voltage range
0.3...0.6 Uc -40...70 °C dropout AC 50/60 Hz
0.8...1.1 Uc -40...60 °C operational AC 50 Hz
0.85...1.1 Uc -40 …60 °C operational AC 60 Hz
1...1.1 Uc 60…70 °C operational AC 50/60 Hz
mechanical endurance
15 Mcycles
width (w)
90 mm
mechanical robustness
Contactor open vibrations: 2 Gn, 5 to 300 Hz
Contactor closed vibrations: 4 Gn, 5 to 300 Hz
Contactor closed shocks: 15 Gn for 11 ms
Contactor open shocks: 8 Gn for 11 ms
Flame retardance
V1 conforming to UL 94
product presentation
Pre-assembled, with pre-wired electrical connections
rated rms inrush power
140 A AC for signaling circuit conforming to IEC 60947-5-1
250 A DC for signaling circuit conforming to IEC 60947-5-1
300 A at 440 V for power circuit conforming to IEC 60947
depth
98 mm
mounting bracket
Platine
Rail
frequency
With
signaling circuit frequency
25 to 400 Hz
calling power goes
70 VA 60 Hz cos phi 0.75 (at 20°C)
70 VA 50 Hz cos phi 0.75 (at 20°C)
operating time
12…22 ms closing
4…19 ms opening
power loss per pole
2,5 W AC-1
security reliability level
B10d = 1369863 contactor cycle with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 contactor cycle with mechanical load conforming to EN/ISO 13849-1
max command speed
3600 cycles/h at <60°C
minimum switching voltage
17 V for signaling circuit
non-overlap time
1.5 ms on de-
energization between NC and NO contact 1.5 ms on excitation between NC and NO contact
coil technology
Without integrated interference suppression module
Poles description
4P
Environment
degree of pollution
3
ip degree of protection
IP20 front face conforming to IEC 60529
operating altitude
0...3000 m
product certificates
UL
CSA
RINA
GOST
CCC
DNV
LROS (Lloyds register of shipping)
GL
BV
UKCA
overvoltage category
III
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
CEI 60947-4-1
CEI 60947-5-1
UL 508
CEI 60335-1
fire resistance
850 °C conforming to IEC 60695-2-1
thermal dissipation
2…3 W at 50/60 Hz
operating temperature
-40…60 °C
60…70 °C with current reduction
storage room temperature
-60…80 °C
climatic resistance
conforming to IACS E10
conforming to IEC 60947-1 Annex Q category D
protective treatment
TH conforming to IEC 60068-2-30
insulation resistance
> 10 MΩ for signaling circuit