Main
product range
TeSys F
Range
TeSys
[uc] control circuit voltage
400 V AC 40...400 Hz
job category
AC-3
AC-1
AC-4
name of the device
LC1F
switch application
Motor control (AC-3)
Resistive load (AC-1)
type of product or equipment
contactor
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 gr C
control circuit type
AC at 40...400 Hz
composition of the power pole contacts
3F
motor power kW
335 kW at 380...400 V AC 50/60 Hz (AC-3)
375 kW at 415 V AC 50/60 Hz (AC-3)
400 kW at 440 V CA 50/60 Hz (AC-3)
400 kW à 500 V AC 50/60 Hz (AC-3)
450 kW à 660...690 V AC 50/60 Hz (AC-3)
450 kW à 1000 V CA 50/60 Hz (AC-3)
200 kW à 220...230 V AC 50/60 Hz (AC-3)
100 kW à 400 V AC 50/60 Hz (AC-4)
average impedance
0,12 mOhm - Ith 1000 A 50 Hz
Complementary
[ie] rated operational current
1000 A (at <40°C) at <= 440 V AC AC-1
630 A (at <55°C) at <= 440 V AC AC-3
[ue] rated operational voltage
<= 1000 V CA 50/60 Hz
<= 460 V CC
compatibility code
LC1F
[ics] rated service breaking capacity
5040 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
5050 A at <40°C - 10 s
4400 A at <40°C - 30 s
3400 A at <40°C - 1 min
2200 A at <40°C - 3 min
1600 A at <40°C - 10 min
[ith] conventional thermal current
1000A at <40°C)
1250A
caliber of the fuse to be associated
1000 A gG at <= 440 V
630 A aM at <= 440 V
Handle front plate colour
304 mm
tightening torque
Remote control: 1.2 Nm
Power circuit: 58 Nm
[uimp] rated impulse withstand voltage
8 kV
average fuel consumption when going
22 VA, 40...400 Hz cos phi 0.9 (at 20°C)
mechanical life
5 Mcycles
product weight
18,6 kg
average consumption on call going
1650 VA, 40...400 Hz cos phi 0.9 (at 20°C)
connection mode
Remote control: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 1 cable( s) 1…4 mm²flexible with cable end
Remote control: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Remote control: screw clamp terminals 1 cable(s) 1…4 mm²rigid without end cable
length Remote control: screw clamp terminals 2 cable(s) 1...4 mm² rigid without cable end
Power circuit: bar 2 cable(s) - busbar section: 60 x 5 mm
Power circuit: connection by bolting
control circuit voltage range
Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C)
Level drop: 0.25...0.5 Uc 40...400 Hz (at 55 °C)
width (w)
309 mm
depth
255 mm
engine power range
250…500 kW at 380…440 V 3 phases
110…220 kW at 200…240 V 3 phases
250…500 kW at 480…500 V 3 phases
mounting bracket
Platinum
operating time
40…80 ms closing
100…200 ms opening
power loss per pole
120 W AC-1
48 W AC-3
max command speed
1200 cycles/h at <55°C
contactor coil voltage
400 V CA standard
motor starter type
Direct line contactor
Poles description
3P
Environment
ip degree of protection
IP20 front face with protectors conforming to IEC 60529
IP20 front face with protectors conforming to VDE 0106
operating altitude
3000 m without current reduction
product certificates
DNV
BV
RINA
LROS (Lloyds register of shipping)
CSA
ABS
UL
RMRoS
CB
UKCA
ambient air temperature for operation
-40…70 °C
operating ambient temperature
-5…55 °C
overvoltage category
III
standards
EN 60947-1
EN 60947-4-1
JIS C8201-4-1
CEI 60947-4-1
CEI 60947-1
thermal dissipation
20W
storage room temperature
-60…80 °C
protective treatment
TH