Main
product range
TeSys F
Range
TeSys
[uc] control circuit voltage
380 V AC 40...400 Hz
job category
AC-3
AC-1
AC-4
name of the device
LC1F
switch application
Motor control (AC-3)
Resistive load (AC-1)
type of product or equipment
contactor
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 gr C
control circuit type
AC at 40...400 Hz
composition of the power pole contacts
3F
motor power kW
335 kW at 380...400 V AC 50/60 Hz (AC-3)
375 kW at 415 V AC 50/60 Hz (AC-3)
400 kW at 440 V CA 50/60 Hz (AC-3)
400 kW à 500 V AC 50/60 Hz (AC-3)
450 kW à 660...690 V AC 50/60 Hz (AC-3)
450 kW à 1000 V CA 50/60 Hz (AC-3)
200 kW à 220...230 V AC 50/60 Hz (AC-3)
100 kW à 400 V AC 50/60 Hz (AC-4)
average impedance
0,12 mOhm - Ith 1000 A 50 Hz
Complementary
[ie] rated operational current
1000 A (at <40°C) at <= 440 V AC AC-1
630 A (at <55°C) at <= 440 V AC AC-3
[ue] rated operational voltage
<= 1000 V CA 50/60 Hz
<= 460 V CC
compatibility code
LC1F
[ics] rated service breaking capacity
5040 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
5050 A at <40°C - 10 s
4400 A at <40°C - 30 s
3400 A at <40°C - 1 min
2200 A at <40°C - 3 min
1600 A at <40°C - 10 min
[ith] conventional thermal current
1000A at <40°C)
1250A
caliber of the fuse to be associated
1000 A gG at <= 440 V
630 A aM at <= 440 V
Handle front plate colour
304 mm
tightening torque
Remote control: 1.2 Nm
Power circuit: 58 Nm
[uimp] rated impulse withstand voltage
8 kV
average fuel consumption when going
22 VA, 40...400 Hz cos phi 0.9 (at 20°C)
mechanical life
5 Mcycles
product weight
18,6 kg
average consumption on call going
1650 VA, 40...400 Hz cos phi 0.9 (at 20°C)
connection mode
Remote control: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 1 cable( s) 1…4 mm²flexible with cable end
Remote control: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Remote control: screw clamp terminals 1 cable(s) 1…4 mm²rigid without end cable
length Remote control: screw clamp terminals 2 cable(s) 1...4 mm² rigid without cable end
Power circuit: bar 2 cable(s) - busbar section: 60 x 5 mm
Power circuit: connection by bolting
control circuit voltage range
Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C)
Level drop: 0.25...0.5 Uc 40...400 Hz (at 55 °C)
width (w)
309 mm
depth
255 mm
mounting bracket
Platinum
operating time
40…80 ms closing
100…200 ms opening
power loss per pole
120 W AC-1
48 W AC-3
max command speed
1200 cycles/h at <55°C
Poles description
3P
Environment
ip degree of protection
IP20 front face with protectors conforming to IEC 60529
IP20 front face with protectors conforming to VDE 0106
operating altitude
3000 m without current reduction
product certificates
UL
CCC
RINA
CB
DNV
BV
ABS
RMRoS
LROS (Lloyds register of shipping)
UKCA
ambient air temperature for operation
-40…70 °C
operating ambient temperature
-5…55 °C
overvoltage category
III
standards
EN 60947-1
JIS C8201-4-1
CEI 60947-4-1
CEI 60947-1
EN 60947-4-1
thermal dissipation
20W
storage room temperature
-60…80 °C
protective treatment
TH