[uc] control circuit voltage
400 V AC 40...400 Hz
job category
AND-1
AND-3
AND-4
name of the device
LC1F
switch application
Motor control (AC-3)
Resistive load (AC-1)
type of product or equipment
contactor
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 gr C
control circuit type
AC at 40...400 Hz
composition of the power pole contacts
3F
motor power kW
250 kW at 380...400 V AC 50/60 Hz (AC-3)
280 kW at 415 V AC 50/60 Hz (AC-3)
295 kW at 440 V AC 50/60 Hz (AC-3)
355 kW at 500 V AC 50/60 Hz (AC-3)
335 kW at 660...690 V AC 50/60 Hz (AC-3)
335 kW at 1000 V CA 50/60 Hz (AC-3)
147 kW à 220...230 V AC 50/60 Hz (AC-3)
80 kW à 400 V AC 50/60 Hz (AC-4)
average impedance
0,18 mOhm - Ith 700 A 50 Hz
Complementary
[ie] rated operational current
700 A (at <40°C) at <= 440 V AC AC-1
500 A (at <55°C) at <= 440 V AC AC-3
[ue] rated operational voltage
<= 1000 V CA 50/60 Hz
<= 460 V CC
compatibility code
LC1F
[ics] rated service breaking capacity
4000 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
4200 A at <40°C - 10 s
3200 A at <40°C - 30 s
2400 A at <40°C - 1 min
1500 A at <40°C - 3 min
1200 A at <40°C - 10 min
[ith] conventional thermal current
700A at <40°C)
caliber of the fuse to be associated
500 A aM at <= 440 V
800 A gG at <= 440 V
Handle front plate colour
238 mm
tightening torque
Remote control: 1.2 Nm
Power circuit: 35 Nm
[uimp] rated impulse withstand voltage
8 kV
average fuel consumption when going
18 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
mechanical life
10 Mcycles
product weight
11,35 kg
average consumption on call going
1100 VA, 40...400 Hz cos phi 0.9 (at 20°C)
connection mode
Remote control: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 1 cable( s) 1…4 mm²flexible with cable end
Remote control: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Remote control: screw clamp terminals 1 cable(s) 1…4 mm²rigid without end cable
length Remote control: screw clamp terminals 2 cable(s) 1...4 mm² rigid without cable end
Power circuit: bar 2 cable(s) - busbar section: 40 x 5 mm
Power circuit: ring terminals 2 cable(s) 240 mm²
Power circuit: connection by bolting
control circuit voltage range
Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C)
Level drop: 0.3...0.5 Uc 40...400 Hz (at 55 °C)
width (w)
233 mm
depth
232 mm
engine power range
250…500 kW at 380…440 V 3 phases
110…220 kW at 380…440 V 3 phases
110…220 kW at 200…240 V 3 phases
250…500 kW at 480…500 V 3 phases
mounting bracket
Platinum
operating time
40…65 ms closing
100…170 ms opening
power loss per pole
88 W AC-1
45 W AC-3
max command speed
2400 cycles/h at <55°C
contactor coil voltage
400 V CA standard
motor starter type
Direct line contactor
Poles description
3P
Environment
ip degree of protection
IP20 front face with protectors conforming to IEC 60529
IP20 front face with protectors conforming to VDE 0106
operating altitude
3000 m without current reduction
product certificates
ABS
CB
RMRoS
RINA
BV
LROS (Lloyds register of shipping)
DNV
CSA
UL
UKCA
ambient air temperature for operation
-40…70 °C
operating ambient temperature
-5…55 °C
overvoltage category
III
standards
CEI 60947-4-1
CEI 60947-1
JIS C8201-4-1
EN 60947-1
EN 60947-4-1
thermal dissipation
18W
storage room temperature
-60…80 °C
protective treatment
TH