Main
product range
TeSys F
Range
TeSys
[uc] control circuit voltage
48 V AC 40...400 Hz
job category
AC-3
AC-1
AC-4
name of the device
LC1F
switch application
Resistive load (AC-1)
Motor control (AC-3)
type of product or equipment
contactor
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 gr C
control circuit type
AC at 40...400 Hz
composition of the power pole contacts
3F
motor power kW
90 kW at 380...400 V AC 50/60 Hz (AC-3)
100 kW at 415 V AC 50/60 Hz (AC-3)
100 kW at 440 V CA 50/60 Hz (AC-3)
110 kW à 500 V AC 50/60 Hz (AC-3)
110 kW à 660...690 V AC 50/60 Hz (AC-3)
55 kW à 220...230 V CA 50/60 Hz (AC- 3)
33 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0,33 mOhm - Ith 275 A 50 Hz
Complementary
[ie] rated operational current
275 A (at <40°C) at <= 440 V AC-1
185 A (at <55°C) at <= 440 V AC-3
[ue] rated operational voltage
<= 460 V CC
<= 690 V CA 50/60 Hz
compatibility code
LC1F
[ics] rated service breaking capacity
1480 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
1500 A at <40°C - 10 s
920 A at <40°C - 30 s
740 A at <40°C - 1 min
500 A at <40°C - 3 min
400 A at <40°C - 10 min
[ith] conventional thermal current
275A at <40°C)
caliber of the fuse to be associated
200 A aM at <= 440 V
315 A gG at <= 440 V
Handle front plate colour
174 mm
tightening torque
Remote control: 1.2 Nm
Power circuit: 18 Nm
[uimp] rated impulse withstand voltage
8 kV
average fuel consumption when going
9.9 VA, 40...400 Hz cos phi 0.9 (at 20°C)
mechanical life
10 Mcycles
product weight
4,65 kg
average consumption on call going
1070 VA, 40...400 Hz cos phi 0.9 (at 20°C)
connection mode
Remote control: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end
Remote control: screw clamp terminals 1 cable( s) 1…4 mm²flexible with cable end
Remote control: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Remote control: screw clamp terminals 1 cable(s) 1…4 mm²rigid without end cable
length Remote control: screw clamp terminals 2 cable(s) 1...4 mm² rigid without cable end
Power circuit: bar 2 cable(s) - busbar section: 25 x 3 mm
Power circuit: ring terminals 1 cable(s) 150 mm²
Power circuit: connector 1 cable(s) 150 mm²
Power circuit: connection by bolting
control circuit voltage range
Operational: 0.85…1.1 Uc 40...400 Hz (at 55 °C)
Level loss: 0.2...0.55 Uc 40...400 Hz (at 55 °C)
width (w)
168,5 mm
depth
181 mm
engine power range
30…50 kW at 200…240 V 3 phases
55…100 kW at 200…240 V 3 phases
55…100 kW at 380…440 V 3 phases
55…100 kW at 480…500 V 3 phases
110…220 kW at 480 …500 V 3 phase
mounting bracket
Platinum
operating time
35 ms closing (at Uc)
130 ms opening (at Uc)
power loss per pole
12 W AC-3
25 W AC-1
max command speed
2400 cycles/h at <55°C
contactor coil voltage
48 V CA standard
motor starter type
Direct line contactor
Poles description
3P
Environment
ip degree of protection
IP2x front face with guards conforming to IEC 60529
IP2x front face with guards conforming to VDE 0106
operating altitude
3000 m without current reduction
product certificates
LROS (Lloyds register of shipping)
CSA
ABS
DNV
CB
RMRoS
BV
RINA
UL
UKCA
ambient air temperature for operation
-40…70 °C
operating ambient temperature
-5…55 °C
overvoltage category
III
standards
EN 60947-4-1
EN 60947-1
CEI 60947-1
CEI 60947-4-1
JIS C8201-4-1
thermal dissipation
8…9.8W
storage room temperature
-60…80 °C
protective treatment
TH