Default
Seeria
TeSyS Deca kontaktorid
Main
product range
TeSys D
Range
TeSys
[uc] control circuit voltage
110 V AC 50/60 Hz
job category
AC-1
AC-4
AC-3
AC-3e
name of the device
LC1D
switch application
Motor control (AC-3)
Resistive load (AC-1)
type of product or equipment
contactor
[ui] rated insulation voltage
Power circuit: 1000 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signaling circuit: 690 V conforming to IEC 60947-1
Signaling circuit: 600 V CSA Certified
Signaling Circuit: 600V UL Certified
control circuit type
AC at 50/60 Hz typical
engine power hp
7.5 hp at 120 VAC 60 Hz for single phase motors
15 hp at 230/240 VAC 60 Hz for single phase motors
30 hp at 200/208 VAC 60 Hz for 3 phase motors
30 hp at 230/240 VAC 60 Hz for 3-phase motors
60 hp at 460/480 V AC 60 Hz for 3-phase motors
60 hp at 575/600 V AC 60 Hz for 3-phase motors
composition of the power pole contacts
3F
motor power kW
25 kW at 220...230 V AC 50 Hz (AC-3)
45 kW at 380...400 V AC 50 Hz (AC-3)
45 kW at 415...440 V AC 50 Hz (AC-3 )
55 kW at 500 V CA 50 Hz (AC-3)
45 kW at 660...690 V CA 50 Hz (AC-3)
45 kW at 1000 V CA 50 Hz (AC-3)
average impedance
0.8 mOhm - Ith 125 A 50 Hz for power circuit
Complementary
[ie] rated operational current
95 A (at <60°C) at <= 440 V AC-3 for power circuit
125 A (at <60°C) at <= 690 V AC-1 for power circuit
95 A (at <60°C ) at <= 440 V AC-3e for power circuit
[ue] rated operational voltage
Power circuit: 1000 V AC 25...400 Hz
compatibility code
LC1D
[ics] rated service breaking capacity
1100 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
1100 A at <40°C - 1s for power circuit
800 A at <40°C - 10 s for power circuit
400 A at <40°C - 1 min for power circuit
135 A at <40°C - 10 min for power circuit
140 A - 100 ms for signaling circuit
120 A - 500 ms for signaling circuit
100 A - 1s for signaling circuit
[ith] conventional thermal current
10 A at <60°C) for signaling circuit
125 A at <60°C) for power circuit
caliber of the fuse to be associated
10 A gG for signaling circuit conforming to IEC 60947-5-1
200 A gG at <= 690 V type 1 coordination for power circuit
160 A gG at <= 690 V type 2 coordination for power circuit
Handle front plate colour
127 mm
tightening torque
Remote control: 1.2 Nm - on screw-clamp terminals - with flat screwdriver Ø 6 mm
Remote control: 1.2 Nm - on screw-clamp terminals - with Phillips No. 2 screwdriver
Power circuit: 12 Nm - on connector - with flat screwdriver Ø 6 to Ø 8 mm
Power circuit: 12 Nm - on hexagonal connector with 4 mm screw head
Remote control: 1.2 Nm - on screw clamp terminals - with pozidriv n°2 screwdriver
[uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947
auxiliary contacts
1 "O" + 1 "F"
average fuel consumption when going
26 VA 60 Hz cos phi 0.3 (at 20°C)
26 VA 50 Hz cos phi 0.3 (at 20°C)
minimum switching current
5 mA for signaling circuit
product weight
1,61 kg
type of auxiliary contacts
mechanically linked type 1 NC + 1 NO conforming to IEC 60947-5-1
1 NC mirror contact type conforming to IEC 60947-4-1
contact compatibility
M11
electrical life
1,2 Mcycles 95 A AC-3
1,3 Mcycles 125 A AC-1
1,2 Mcycles 95 A AC-3e
connection mode
Remote control: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Remote control: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end
Remote control: screw terminal blocks- clamp 1 1…4 mm² - cable stiffness: flexible without cable end
Remote control: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Remote control: screw clamp terminals 1 1…4 mm² - cable stiffness : rigid without cable end
Remote control: screw clamp terminals 2 1…4 mm² - cable stiffness: rigid without cable end
Power circuit: connector 1 4…50 mm² - cable stiffness: flexible without cable end
Power circuit: connector 2 4… 25 mm² - cable stiffness: flexible without cable end
Power circuit: connector 1 4…50 mm² - cable stiffness: flexible with ferrule
Power circuit: connector 2 4…16 mm² - cable stiffness: flexible with ferrule
Power circuit: connector 1 4…50 mm² - cable stiffness : rigid without cable end
Power circuit: connector 2 4…25 mm² - cable stiffness: rigid without cable end
control circuit voltage range
0.8 to 1.1 Uc -40…55 °C operational AC 50 Hz
0.85…1.1 Uc -40…55 °C operational AC 60 Hz
0.3 to 0.6 Uc -40…70 °C loss of level AC 50/60 Hz
1...1.1 Uc 55…70 °C operational AC 50/60 Hz
mechanical endurance
4 Mcycles
width (w)
85 mm
mechanical robustness
Open contactor vibrations (2 Gn, 5 to 300 Hz)
Open contactor shocks (8 Gn for 11 ms)
Closed contactor vibrations (3 Gn, 5 to 300 Hz)
Closed contactor shocks (10 Gn for 11 ms)
Flame retardance
V1 conforming to UL 94
rated rms inrush power
1100 A at 440 V AC for power circuit conforming to IEC 60947
140 A AC for signaling circuit conforming to IEC 60947-5-1
250 A DC for signaling circuit conforming to IEC 60947-5-1
depth
130 mm
mounting bracket
Rail
Platine
frequency
With
signaling circuit frequency
25 to 400 Hz
calling power goes
245 VA 60 Hz cos phi 0.75 (at 20°C)
245 VA 50 Hz cos phi 0.75 (at 20°C)
operating time
20…35 ms closing
6…20 ms opening
power loss per pole
12,5 W AC-1
7,2 W AC-3
7,2 W AC-3e
security reliability level
B10d = 1.3 Mcycles contactor with rated load conforming to EN/ISO 13849-1
B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1
max command speed
3600 cycles/h at <60°C
minimum switching voltage
17 V for signaling circuit
non-overlap time
1.5 ms on de-
energization between NC and NO contact 1.5 ms on excitation between NC and NO contact
coil technology
Without integrated interference suppression module
Poles description
3P
Environment
degree of pollution
3
ip degree of protection
IP20 front face conforming to IEC 60529
operating altitude
0...3000 m
product certificates
certificat CEI CE
UL
CSA
CCC
EAC
LROS (Lloyds register of shipping)
RINA
BV
DNV-GL
ambient air temperature for operation
-40…60 °C
60…70 °C with current reduction
overvoltage category
III
standards
EN/CEI 60947-1
EN/CEI 60947-4-1
EN/CEI 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947 -5-1
GB/T 14048.4
fire resistance
850 °C conforming to IEC 60695-2-1
thermal dissipation
6…10 W at 50/60 Hz
climatic resistance
conform to IACS E10 exposure to damp heat
protective treatment
TH conforming to IEC 60068-2-30
insulation resistance
> 10 MΩ for signaling circuit