Default
Seeria
TeSyS Deca kontaktorid
Main
product range
TeSys D
TeSys Deca
Range
TeSys
TeSys Deca
[uc] control circuit voltage
230 V AC 50/60Hz
job category
AC-4
AC-1
AC-3
AC-3e
name of the device
LC1D
switch application
Resistive load (AC-1)
Motor control (AC-3)
type of product or equipment
contactor
[ui] rated insulation voltage
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signaling circuit: 690 V conforming to IEC 60947-1
Signaling circuit: 600 V CSA certified
Signaling circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1
control circuit type
AC at 50/60 Hz typical
engine power hp
40 hp at 460/480 V AC 50/60 Hz for 3 phase motors
5 hp at 115 V AC 50/60 Hz for single phase motors
10 hp at 230/240 V AC 50/60 Hz for single phase motors
20 hp at 200/208 V AC 50/60 Hz for 3 motor phases
20 hp at 230/240 V AC 50/60 Hz for 3 motor phases
50 hp at 575/600 V AC 50/60 Hz for 3 motor phases
composition of the power pole contacts
3F
motor power kW
11 kW at 400 V AC 50/60 Hz (AC-4)
18,5 kW at 220...230 V AC 50/60 Hz (AC-3)
30 kW at 380...400 V AC 50/60 Hz (AC-3)
37 kW at 500 V AC 50/60 Hz (AC-3)
37 kW at 660...690 V AC 50/60 Hz (AC-3)
18.5 kW at 220...230 V CA 50/60 Hz (AC-3e)
30 kW à 380...400 V CA 50/60 Hz (AC-3e)
37 kW à 500 V CA 50/60 Hz (AC-3e)
37 kW à 660.. .690 V AC 50/60 Hz (AC-3e)
average impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Complementary
[ie] rated operational current
80 A (at <60°C) at <= 440 V AC AC-1 for power circuit
65 A (at <60°C) at <= 440 V AC AC-3 for power circuit
65 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[ue] rated operational voltage
Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC
compatibility code
LC1D
[ics] rated service breaking capacity
1000 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current
520 A at <40°C - 10 s for power circuit
900 A at <40°C - 1s for power circuit
110 A at <40°C - 10 min for power circuit
260 A at <40°C - 1 min for power circuit
100 A - 1s for signaling circuit
120 A - 500 ms for signaling circuit
140 A - 100 ms for signaling circuit
[ith] conventional thermal current
10 A at <60°C) for signaling circuit
80 A at <60°C) for power circuit
caliber of the fuse to be associated
10 A gG for signaling circuit conforming to IEC 60947-5-1
125 A gG at <= 690 V type 1 coordination for power circuit
125 A gG at <= 690 V type 2 coordination for power circuit
Handle front plate colour
122 mm
tightening torque
Remote control: 1.7 Nm - on EverLink BTR screw connectors - with Ø 6 mm flat screwdriver
Remote control: 1.7 Nm - on EverLink BTR screw connectors - with Phillips No. 2 screwdriver
Power circuit: 8 Nm - on connectors EverLink BTR screw connectors - cable 25...35 mm² hexagonal screw head 4 mm
Power circuit: 5 Nm - on screw connectors EverLink BTR - cable 1...25 mm² hexagonal screw head 4 mm
Remote control: 1.7 Nm - on screw connectors BTR EverLink - with pozidriv n°2 screwdriver Power
circuit: 2.5 Nm - on screw connectors BTR EverLink - with pozidriv n°2 screwdriver
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
auxiliary contacts
1 "O" + 1 "F"
average fuel consumption when going
13 VA 60 Hz cos phi 0.3 (at 20°C)
15 VA 50 Hz cos phi 0.3 (at 20°C)
minimum switching current
5 mA for signaling circuit
product weight
0,86 kg
type of auxiliary contacts
mechanically linked type 1 NC + 1 NO conforming to IEC 60947-5-1
1 NC mirror contact type conforming to IEC 60947-4-1
contact compatibility
M2
electrical life
1.4 Mcycles 80 A AC-1 at Ue <= 440 V
1.45 Mcycles 65 A AC-3 at Ue <= 440 V
1.45 Mcycles 65 A AC-3e at Ue <= 440 V
connection mode
Remote control: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Remote control: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Remote control: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Remote control: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Remote control: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Remote control: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw connection 1 1…35 mm² - cable stiffness: flexible without cable end
Power circuit: screw connection 2 1...25 mm² - cable stiffness: flexible without cable end
Power circuit: screw connection 1 1…35 mm² - cable stiffness: flexible with ferrule
Power circuit: screw connection 2 1…25 mm² - cable stiffness: flexible with ferrule
Power circuit: screw connection 1 1… 35 mm² - cable stiffness: solid without cable end
Power circuit: screw connection 2 1...25 mm² - cable stiffness: solid without cable end
control circuit voltage range
0.3...0.6 Uc -40...70 °C dropout AC 50/60 Hz
0.8...1.1 Uc -40...60 °C operational AC 50 Hz
0.85...1.1 Uc -40 …60 °C operational AC 60 Hz
1...1.1 Uc 60…70 °C operational AC 50/60 Hz
mechanical endurance
6 Mcycles
width (w)
55 mm
mechanical robustness
Open contactor vibrations (2 Gn, 5 to 300 Hz)
Closed contactor vibrations (4 Gn, 5 to 300 Hz)
Closed contactor shocks (15 Gn for 11 ms)
Open contactor shocks (10 Gn for 11 ms)
Flame retardance
V1 conforming to UL 94
rated rms inrush power
140 A AC for signaling circuit conforming to IEC 60947-5-1
250 A DC for signaling circuit conforming to IEC 60947-5-1
1000 A at 440 V for power circuit conforming to IEC 60947
depth
120 mm
mounting bracket
Rail
Platine
frequency
With
signaling circuit frequency
25 to 400 Hz
calling power goes
140 VA 60 Hz cos phi 0.75 (at 20°C)
160 VA 50 Hz cos phi 0.75 (at 20°C)
operating time
4…19 ms opening
12…26 ms closing
power loss per pole
9,6 W AC-1
6,3 W AC-3
6,3 W AC-3e
security reliability level
B10d = 1369863 contactor cycle with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 contactor cycle with mechanical load conforming to EN/ISO 13849-1
max command speed
3600 cycles/h at <60°C
minimum switching voltage
17 V for signaling circuit
non-overlap time
1.5 ms on de-
energization between NC and NO contact 1.5 ms on excitation between NC and NO contact
coil technology
Without integrated interference suppression module
Poles description
3P
Environment
degree of pollution
3
ip degree of protection
IP20 front face conforming to IEC 60529
operating altitude
0...3000 m
product certificates
UL
GOST
CSA
CCC
ambient air temperature for operation
-40…60 °C
60…70 °C with current reduction
overvoltage category
III
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
CEI 60947-4-1
CEI 60947-5-1
UL 508
CEI 60335-1
fire resistance
850 °C conforming to IEC 60695-2-1
thermal dissipation
4…5 W at 50/60 Hz
climatic resistance
conforming to IACS E10 exposure to damp heat
conforming to IEC 60947-1 Annex Q category D exposure to damp heat
protective treatment
TH conforming to IEC 60068-2-30
insulation resistance
> 10 MΩ for signaling circuit