Kõik kategooriad
Võrdle Ostukorv
LC1D258BD - TeSys LC1D - kontaktor - 4P (2NO+2O) - AC-1 440V - 40A - 24Vdc mähis. - Schneider Electric - TeSys LC1D - kontaktor - 4P (2NO+2O) - AC-1 440V - 40A - 24Vdc mähis. - Schneider Electric - 0
LC1D258BD - TeSys LC1D - kontaktor - 4P (2NO+2O) - AC-1 440V - 40A - 24Vdc mähis. - Schneider Electric - TeSys LC1D - kontaktor - 4P (2NO+2O) - AC-1 440V - 40A - 24Vdc mähis. - Schneider Electric - 0
Tellimisel

LC1D258BD – Schneider Electric

EAN: 3389110334135
82,04 € KM-ta
101,73 € KM-ga
TeSys LC1D - kontaktor - 4P (2NO+2O) - AC-1 440V - 40A - 24Vdc mähis. - Schneider Electric
101,73 €
SPETSIFIKATSIOONID
Default
Seeria TeSyS Deca kontaktorid
Main
product range TeSys Deca
[uc] control circuit voltage 24 V CC
job category AC-1
name of the device LC1D
switch application Resistive load (AC-1)
type of product or equipment contactor
[ui] rated insulation voltage Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signaling circuit: 690 V conforming to IEC 60947-1
Signaling circuit: 600 V CSA Certified
Signaling Circuit: 600V UL Certified
control circuit type CC standard
composition of the power pole contacts 2F+2O
average impedance 2 mOhm - Ith 40 A 50 Hz for power circuit
Complementary
[ie] rated operational current 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
compatibility code LC1D
[ics] rated service breaking capacity 450 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current 240 A at <40°C - 10 s for power circuit
380 A at <40°C - 1s for power circuit
50 A at <40°C - 10 min for power circuit
120 A at <40°C - 1 min for power circuit
100 A - 1s for signaling circuit
120 A - 500 ms for signaling circuit
140 A - 100 ms for signaling circuit
[ith] conventional thermal current 10 A at <60°C) for signaling circuit
40 A at <60°C) for power circuit
caliber of the fuse to be associated 10 A gG for signaling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V type 1 coordination for power circuit
40 A gG at <= 690 V type 2 coordination for power circuit
average consumption on hold in w 5.4W at 20°C
Handle front plate colour 91 mm
tightening torque Remote control: 1.7 Nm - on screw-clamp terminals - with Ø 6 mm flat screwdriver
Remote control: 1.7 Nm - on screw-clamp terminals - with Phillips No. 2 screwdriver
Power circuit: 1.8 Nm - on connector - with Ø 6 mm flat screwdriver
Power circuit: 1.8 Nm - on connector - with no. 2 Phillips screwdriver
Remote control: 1.7 Nm - on screw clamp terminals - with no. 2 pozidriv screwdriver Power
circuit power: 2.5 Nm - on screw clamp terminals - with pozidriv n°2 screwdriver
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
auxiliary contacts 1 "O" + 1 "F"
minimum switching current 5 mA for signaling circuit
product weight 0,585 kg
type of auxiliary contacts mechanically linked type 1 NC + 1 NO conforming to IEC 60947-5-1
1 NC mirror contact type conforming to IEC 60947-4-1
contact compatibility M7
electrical life 1.4 Mcycles 40 A AC-1 at Ue <= 440 V
connection mode Remote control: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Remote control: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Remote control: screw clamp terminals 1 1… 4 mm² - cable stiffness: flexible with cable end
Remote control: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end
Remote control: screw clamp terminals 1 1...4 mm² - cable stiffness: solid without cable end
Remote control: screw clamp terminals 2 1…4 mm² - cable stiffness: rigid without cable end
Power circuit: connector 1 2.5…10 mm² - cable stiffness: flexible without cable end
Power circuit: connector 2 2, 5...10 mm² - cable stiffness: flexible without cable end
Power circuit: connector 1 2.5…10 mm² - cable stiffness: flexible with ferrule
Power circuit: connector 2 2.5…10 mm² - cable stiffness: flexible with ferrule
Power circuit: connector 1 2.5…10 mm² 16 mm² - cable stiffness: solid without cable end
Power circuit: connector 2 2.5...16 mm² - cable stiffness: solid without cable end
control circuit voltage range 0.1...0.25 Uc -40...60°C DC level loss
0.7...1.25 Uc -40...60°C DC operational
mechanical endurance 30 Mcycles
width (w) 45 mm
mechanical robustness Contactor open vibrations (2 Gn, 5 to 300 Hz)
Contactor closed vibrations (4 Gn, 5 to 300 Hz)
Contactor closed shocks (15 Gn for 11 ms)
Contactor open shocks (8 Gn for 11 ms)
Flame retardance V1 conforming to UL 94
time constant 28 ms
rated rms inrush power 140 A AC for signaling circuit conforming to IEC 60947-5-1
250 A DC for signaling circuit conforming to IEC 60947-5-1
450 A at 440 V for power circuit conforming to IEC 60947
depth 107 mm
mounting bracket Platine
Rail
frequency With
maximum inrush power in w 5.4W (at 20°C)
signaling circuit frequency 25 to 400 Hz
operating time 53.55…72.45 ms closing
16…24 ms opening
power loss per pole 3,2 W AC-1
security reliability level B10d = 1369863 contactor cycle with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 contactor cycle with mechanical load conforming to EN/ISO 13849-1
max command speed 3600 cycles/h at <60°C
minimum switching voltage 17 V for signaling circuit
non-overlap time 1.5 ms on de-
energization between NC and NO contact 1.5 ms on excitation between NC and NO contact
coil technology Built-in bi-directional peak limit diode suppressor
Poles description 4P
Environment
degree of pollution 3
ip degree of protection IP20 front face conforming to IEC 60529
operating altitude 0...3000 m
product certificates UL
CSA
CCC
EAC
UKCA
CB
EU-RO-MR by DNV-GL
ambient air temperature for operation -40…60 °C
60…70 °C with current reduction
overvoltage category III
standards EN 60947-4-1
EN 60947-5-1
CEI 60947-4-1
CEI 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No. 60947-5-1
GB/T 14048.4
fire resistance 850 °C conforming to IEC 60695-2-1
climatic resistance conforming to IACS E10 exposure to damp heat
conforming to IEC 60947-1 Annex Q category D exposure to damp heat
protective treatment TH conforming to IEC 60068-2-30
insulation resistance > 10 MΩ for signaling circuit
KKK ja hinna lisateave

Võta meiega ühendust

Professionaalne elektriseadmete müük Eestis, Lätis, Leedus ja Soomes. Sertifitseeritud madalpinge komponendid, kaitselülitid, kontaktorid ja tööstusautomaatika lahendused. Sama päeva hinnapakkumised ja kiire tarne Baltikumis ja Soomes

Baltelec
+372 5326 4976

E–R 9:00–17:00

info@baltelec.ee

Vastame 2 tunni jooksul

Schneider Electric LC1D258BD on lahendus kategooriast Tööstuslikud kontaktorid, mis on mõeldud professionaalidele. BaltElec tegeleb hulgimüügi ja distributsiooniga Eestis, Lätis, Leedus ja Soomes.

  • Originaal Schneider Electric toode, vastavusdokumendid päringu alusel.
  • Mahupõhine hinnastus – küsi pakkumist suuremate koguste jaoks (võimalik, et sätestame MOQ).
  • Tõhus ja kiire logistika Baltikumis ning Soomes; koostöö tunnustatud kulleritega.
  • Tehniline tugi ja ettepanekud sobivuse kohta vastavalt Sinu rakendusele.

Hinnainfo: Küsi projektipakkumist. Hind sõltub kogusest, tarne- ja maksetingimustest.

KKK tootele LC1D258BD - Schneider Electric

Hiljuti vaadatud
LC1D258BD - Schneider Electric
TeSys LC1D - kontaktor - 4P (2NO+2O) - AC-1 440V - 40A - 24Vdc mähis.
82,04 € KM-ta
101,73 € KM-ga
Tellimisel