Main
allowable temporary current amplification
1.1 x In for 60 s (low overload)
1.5 x In for 60 s (high overload)
product range
Altivar Process ATV600
product specific application
Processes and utilities
name of the device
ATV630
option board
Position A: module de communication, Profibus DP V1
Position A: module de communication, Profinet
Position A: module de communication, DeviceNet
Position A: module de communication, Modbus TCP/EtherNet/IP
Position A: module de communication, CANopen daisy chain RJ45
Position A: module de communication, CANopen SUB-D 9
Position A: module de communication, CANopen bornes à vis
Position A/position B: module d'extension E/S digital et analogique
Position A/position B: module d'extension relais
Position A: module de communication, Ethernet IP/Modbus TCP/MD-Link
Module de communication, BACnet MS/TP
Module de communication, Ethernet Powerlink
type of product or equipment
Speed variator
destination of the product
Asynchronous
motors Synchronous motors
emc filter
Integrated with 50 m max motor cable conforming to EN/IEC 61800-3 category C2
Integrated with 150 m max motor cable conforming to EN/IEC 61800-3 category C3
degree of protection
UL type 1 conforming to UL 508C
number of network phases
3 phases
communication protocol
Modbus TCP
Ethernet
Modbus série
engine power hp
15 hp light overload
10 hp heavy overload
motor power kW
11 kW (low overload)
7.5 kW (high overload)
security function
STO (safe torque off) SIL 3
variant
Version standard
Complementary
feed
External supply for digital inputs: 24 V DC (19...30 V), <1.25 mA, protection type: overload and short-circuit protection
Internal supply for reference potentiometer (1...10 kOhm): 10, 5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
External power supply for digital and STO inputs: 24 V DC (21…27 V), <200 mA, protection type : overload and short-circuit protection
[un] rated nominal voltage
380…480 V - 15...10%
digital input compatibility
DI1…DI6: level 1 PLC digital input conforming to EN/IEC 61131-2
DI5, DI6: level 1 PLC digital input conforming to IEC 65A-68
STOA, STOB: level 1 PLC digital input conforming to EN/IEC 61131 -2
maximum switching current
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
batch quantity
1
data formats
8 bits, configurable even, odd or no parity
Handle front plate colour
409 mm
installation of the box
Mural
minimum switching current
Relay output R1, R2, R3: 5 mA at 24 V DC
product weight
7,7 kg
marking
THIS
mode d'installation
Wall mounting
refresh time
Relay output (R1, R2, R3): 5ms (+/- 0.5ms)
output voltage
<= supply voltage
width (w)
171 mm
power frequency
50...60 Hz - 5...5 %
switching frequency
2...12 kHz adjustable
4...12 kHz with reduction factor
Local signalling
for local diagnostics 3 LEDs
for on-board communication status 3 LEDs (double colour)
for communication module status 4 LEDs (double colour)
for voltage presence 1 LED (red)
motor slip compensation
Adjustable
Can be suppressed
Not available in law for permanent magnet motor
Automatic whatever the load
physical interface
Ethernet
2-fils RS 485
prospective line short-circuit current
50 kA
connector type
RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP
RJ45 (on the remote graphic terminal) for Modbus serial
depth
233 mm
line current
19.8 A at 380 V (light overload)
17 A at 480 V (light overload)
14.1 A at 380 V (heavy overload)
12.5 A at 480 V (heavy overload)
motor power range ac - 3
7…11 kW at 380…440 V 3 phases
7…11 kW at 480…500 V 3 phases
power dissipation in w
Natural convection: 51 W at 380 V, switching frequency 4 kHz
Forced convection: 255 W at 380 V, switching frequency 4 kHz
continuous output current
23.5 A at 4 kHz for light overload
16.5 A at 4 kHz for heavy overload
current maximum input current per phase
19,8 A
isolation
Between power and control connections
tension de service (us)
380…480V
logic input
16 programmed speeds
maximum transient current
25.9 A for 60 s (light overload)
24.8 A for 60 s (high overload)
electrical connection
Control: removable screw terminals 0.5…1.5 mm²/4 x 1.5 mm² + 2 x 1 mm² + 2 x 0.14 mm²
Motor: screw terminal block 6…10 mm²/AWG 10…AWG 8
Input: screw terminal block 6 mm²/AWG 10
mode of exchange
Half duplex, full duplex, auto-négociation Ethernet/Modbus TCP
sampling time
2 ms +/- 0.5 ms (DI1…DI4) - digital input
5 ms +/- 1 ms (DI5, DI6) - digital input
5 ms +/- 0.1 ms (AI1, AI2, AI3) - input analog
10 ms +/- 1 ms (AO1) - analog output
standstill braking
4 x 2,5 mm² + 2 x 1 mm² + 2 x 0,14 mm²
linearity error
AI1, AI2, AI3: +/- 0.15% of maximum value for analog input
AO1, AO2: +/-0.2% for analog output
mounting position
Vertical +/- 10 degrees
nominal switching frequency
4 kHz
maximum output frequency
500 kHz
kind of protection
Thermal protection: motor
Safe torque off: motor Motor
phase loss: motor
Thermal protection: drive
Safe torque off: drive
Overheating: drive
Overcurrent between output phases and ground: drive
Output overvoltage: drive
Short-circuit protection : drive
Motor phase loss: drive
DC bus overvoltage: drive
Power supply overvoltage: drive Power supply
undervoltage: drive Power supply
phase loss: drive
Overspeed: drive
Break on the control circuit: dimmer
access method
Esclave Modbus TCP
variable speed drive output frequency
0,1…500 Hz
number of analog inputs
3
number of logic inputs
8
kind of cooling
Forced convection
number of analog outputs
2
precision
+/- 0.6% AI1, AI2, AI3 for a temperature variation of 60°C analog input
+/- 1% AO1, AO2 for a temperature variation of 60°C analog output
baud rate
10, 100 Mbits
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
synchronous motor control profile
Permanent magnet
motor Synchronous reluctance motor
control profile for asynchronous motor
Constant
torque Optimized
torque Variable torque
apparent power
14.1 kVA à 480 V (surcharge faible)
10.4 kVA à 480 V (surcharge importante)
number of addresses
1…247 for Modbus serial
variable speed drive application selection
Centrifugal Compressor Building - HVAC
Other Application Food & Beverage Processing
Fan Mineral & Metal
Mining Pump Mineral & Metal Mining
Fan Oil & Gas
Other Application Water & Wastewater
Screw Compressor Building - HVAC
Pump Food Processing & Beverage
Fan Food and Beverage
Processing Spraying Food and Beverage Processing
Electric Submersible
Pump Oil and Gas Water Injection Pump Oil and Gas
Jet Fuel Pump Oil and Gas
Compressor for Refinery Oil and Gas
Centrifugal pump Water and waste water
Volumetric pump Water and waste water
Submersible electric
pump Water and waste water Screw pump Water and waste water Lobe
compressor Water and waste water
Screw compressor Water and waste water
Centrifugal compressor Water and waste water
Fan Water and waste water
Conveyor Water and waste water
Mixer Water and waste water
acceleration and deceleration ramps
Linearly adjustable from 0.01 ... 9999 s
number of relay outputs
3
analog input type
AI1, AI2, AI3 voltage configurable by software: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
AI1, AI2, AI3 current configurable by software: 0...20 mA, impedance: 250 Ohm, 12 bit resolution
AI2 analog voltage input: - 10...10 V DC, impedance: 31.5 kOhm, 12 bit resolution
logic input type
DI7, DI8 programmable as pulse train input: 0…30 kHz, 24 V DC (<= 30 V)
analog output type
Voltage configurable by software AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits
Current configurable by software AQ1, AQ2: 0...20 mA, resolution 10 bits
Current configurable by software DQ-, DQ+: 30 V DC
Software configurable current DQ-, DQ+: 100 mA
logic output type
Relay outputs R1A, R1B, R1C 250 V AC 3000 mA
Relay outputs R1A, R1B, R1C 30 V DC 3000 mA
Relay outputs R2A, R2C 250 V AC 5000 mA
Relay outputs R2A, R2C 30 V DC 5000 mA
Relay outputs R3A, R3C 250 V AC 5000 mA
Relay outputs R3A, R3C 30 V DC 5000 mA
relay output type
Configurable relay R1: C/O fault relay electrical durability 100000 cycles
Configurable relay R2: sequence relay "C" electrical durability 100000 cycles
Configurable relay R3: sequence relay "C" electrical durability 100000 cycles
frequency resolution
Display unit: 0.1 Hz
Analog input: 0.012/50 Hz
transmission frame
RTU
polarization type
No impedance