Default
Seeria
TeSyS Deca GV7 mootorikaitselüliti
Main
Range
TeSys
sectioning ability
Yes conforming to IEC 60947-1
job category
AC-3 conforming to IEC 60947-4-1
name of the device
GV7R
type of product or equipment
Circuit breaker
Product Name
TeSys GV7
[ui] rated insulation voltage
750 V AC 50/60 Hz conforming to IEC 60947-2
thermal protection adjustment range
132…220 A
motor power kW
110 kW at 400...415 V CA 50/60 Hz
110 kW at 500 V CA 50/60 Hz
132 kW at 500 V CA 50/60 Hz
160 kW at 500 V CA 50/60 Hz
160 kW at 660.. .690 V CA 50/60 Hz
200 kW à 660...690 V CA 50/60 Hz
90 kW à 400...415 V CA 50/60 Hz
type of trigger
Thermal-magnetic
Complementary
"no" connection
35 mm without spreaders
45 mm with spreaders
[ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
application
Engine
[ics] rated service breaking capacity
100% at 440 V AC 50/60 Hz conforming to IEC 60947-2
100% at 500 V AC 50/60 Hz conforming to IEC 60947-2
100% at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
100% at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
100% at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[ith] conventional thermal current
220 A conforming to IEC 60947-4-1
Handle front plate colour
161 mm
tightening torque
10 Nm on M6 screw type of screw
15 Nm on bare cable connectors for cable 1.5...185 mm²
[uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2
product weight
2,35 kg
mode d'installation
By screws
By clips
electrical life
10000 cycles for AC-3 at 440 V In
20000 cycles for AC-3 at 440 V In/2
connection mode
Busbars
Cable with lug - external diameter: 10 mm
Screw
Bare cable connectors 1.5…185 mm²
mechanical endurance
20000 cycle
width (w)
105 mm
mechanical robustness
Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations: 2.5 Gn, 0...25 Hz conforming to IEC 60068-2-6
network frequency
50/60 Hz conforming to IEC 60947-4-1
power dissipation per pole
14.5W
assigned department
Continuous conforming to IEC 60947-4-1
depth
126 mm
mounting bracket
Board Fixing Kit
Panel Mount
Rail
Recessed
Network type
THAT
sensitivity to phase loss
Yes conforming to IEC 60947-4-1 § 7-2-1-5-2
mounting position
Vertical
power loss per pole
14.5W
order type
rocker arm
maximum control speed
25 cyc/h
Poles description
3P
Environment
degree of pollution
3
ip degree of protection
IP405 conforming to IEC 60529 (with terminal shields)
operating altitude
2000 m
product certificates
UL
DNV
standards
EN/CEI 60947-4-1
NF C 79-130
NF C 63-120
NF C 63-650
VDE 0660
EN/CEI 60947-1
VDE 0113
EN/CEI 60947-2
fire resistance
960 °C conforming to IEC 60695-2-1
operating temperature
-25…70 °C
storage room temperature
-55…95 °C
protective treatment
TC